5167798-YTG-J-0218
Johnson Controls Unitary Products
25
115°F
125°F
2500
77
117.2
11.2
54.3
43.9
33.2
-
-
-
104.6
12.1
64.4
42.9
31.5
-
-
-
72
106.1
10.8
74.7
63.9
53.2
42.5
-
-
94.9
11.6
74.8
64.0
53.3
42.6
-
-
67
95.0
10.4
95.0
84.0
73.3
62.6
51.8
-
85.2
11.1
85.2
85.2
75.2
64.5
53.8
-
62
85.5
10.1
85.5
85.5
81.6
70.9
60.1
49.4
76.3
10.8
76.3
76.3
76.3
70.2
59.4
48.7
3000
77
120.1
11.2
64.1
47.2
34.5
-
-
-
106.6
12.3
71.1
45.8
31.5
-
-
-
72
108.7
10.9
80.7
68.1
55.4
42.7
-
-
96.7
11.7
78.9
66.3
53.7
41.0
-
-
67
97.4
10.5
97.4
88.9
76.3
63.6
51.0
-
86.8
11.2
86.8
86.8
75.9
63.2
50.6
-
62
87.5
10.2
87.5
87.5
87.5
74.9
62.2
49.6
77.7
10.9
77.7
77.7
77.7
72.6
60.0
47.3
57
90.8
10.3
90.8
90.8
87.8
75.2
62.5
49.8
83.7
11.0
83.7
83.7
83.7
72.1
59.4
46.8
3500
77
122.9
11.3
73.9
50.5
35.9
-
-
-
108.6
12.4
77.9
48.7
31.5
-
-
-
72
111.3
10.9
86.8
72.2
57.6
43.0
-
-
98.5
11.8
83.1
68.6
54.0
39.4
-
-
67
99.7
10.6
99.7
93.9
79.3
64.7
50.1
-
88.4
11.3
88.4
88.4
76.5
62.0
47.4
-
62
89.6
10.3
89.6
89.6
93.5
78.9
64.3
49.7
79.2
11.0
79.2
79.2
79.2
75.0
60.5
45.9
57
93.0
10.4
93.0
93.0
91.3
76.7
62.1
47.5
85.3
11.1
85.3
85.3
85.2
70.6
56.1
41.5
4000
77
125.8
11.4
83.7
53.8
37.2
-
-
-
110.6
12.5
84.6
51.6
31.5
-
-
-
72
113.9
11.0
92.9
76.3
59.8
43.2
-
-
100.3
11.9
87.3
70.8
54.3
37.8
-
-
67
102.0
10.6
102.0
98.8
82.3
65.7
49.2
-
90.0
11.4
90.0
90.0
77.2
60.7
44.2
-
62
91.7
10.4
91.7
91.7
99.5
82.9
66.4
49.8
80.6
11.1
80.6
80.6
80.6
77.4
61.0
44.5
57
95.1
10.5
95.1
95.1
94.7
78.2
61.6
45.1
86.9
11.2
86.9
86.9
85.7
69.2
52.7
36.2
4500
72
115.9
11.1
99.2
81.4
63.6
45.8
-
-
102.2
12.0
93.1
75.4
57.7
40.1
-
-
67
103.8
10.7
103.8
102.2
87.6
69.8
52.0
-
91.7
11.5
91.7
91.7
82.0
64.4
46.7
-
62
93.3
10.4
93.3
93.3
97.2
79.4
61.6
43.8
82.2
11.1
82.2
82.2
82.2
71.2
53.5
35.8
57
96.8
10.5
96.8
96.8
96.6
78.8
61.0
43.2
88.5
11.3
88.5
88.5
87.9
70.3
52.6
34.9
5000
72
117.9
11.1
105.5
86.5
67.4
48.4
-
-
104.2
12.1
98.9
80.0
61.2
42.3
-
-
67
105.6
10.7
105.6
105.6
92.8
73.8
54.7
-
93.5
11.5
93.5
93.5
86.9
68.0
49.2
-
62
95.0
10.5
95.0
95.0
95.0
75.9
56.8
37.8
83.7
11.2
83.7
83.7
83.7
64.9
46.0
27.2
57
98.5
10.6
98.5
98.5
98.5
79.4
60.4
41.3
90.2
11.3
90.2
90.2
90.2
71.4
52.5
33.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZF120 (10 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65