JOHNSON CONTROLS
50
FORM 155.21-O1 (615)
Programmable
Pri Trig
Access Level required:
OPERATOR
This key allows the Operator to select the first parameter
to be evaluated. Selection is made from a pre-defined
list.
Pri Oper
Access Level required:
OPERATOR
This key allows the Operator to select the comparator for
the Primary Trigger’s relationship to the Primary Test.
If the Primary Trigger is an analog value, selections are:
<, <=, =, =>, >. If the Primary Trigger is a digital event,
selections are: Equal To, Not Equal To.
Pri Test
Access Level required:
OPERATOR
This key allows the Operator to select the value or condi-
tion that the Primary Trigger is compared to. Selection
ranges from the Primary Trigger minimum value to the
Primary Trigger maximum value.
Trig Action
Access Level required:
OPERATOR
This key allows the Operator to select whether the trend
data collection will Start or Stop when the Trigger com-
parisons are true. If set to Start, data collection will stop
after one screen of data is collected.
Trig Delay
Allows the data collection start or stop to be delayed
after the Triggers evaluate as true. The delay is select-
able from 1 to 1,600 seconds (26 min.). Display is in
minutes and seconds. The delay timer begins when the
triggers evaluate as true. If the Trigger Action is set
to START, data collection will begin after the triggers
evaluate as true and the delay timer has elapsed. If the
Trigger Action is set to STOP, data collection will stop
after the Triggers evaluate as true and the delay timer
has elapsed.
Pri to Sec
This key allows the Operator to select whether the
Primary Trigger, Secondary Trigger or both have to be
true in order to start or stop data collection. Selections
are AND, OR, XOR and None.
• If NONE is selected, the Secondary Trigger is dis
-
abled.
Data collection will start/stop (as selected with Trigger
Action) when:
• If AND selected: Both Primary AND Secondary are
true.
• If OR selected: Either Primary OR Secondary (or
both) are true.
• If XOR selected: Either Primary OR Secondary (but
not both) are true.
Sec Trig
This key allows the Operator to select the second pa-
rameter to be evaluated. Selection is made from the Slot
Numbers listing on the Trend Common Slots Screen or
the Master Slot Numbers List in this book. Setting this
slot number to zero disables the Secondary Trigger.
Sec Oper
This key allows the Operator to select the comparator for
the Secondary Trigger’s relationship to the Secondary
Test. If the Secondary trigger is an Analog value, selec-
tions are: <, <=, =, =>, >. If the Secondary Trigger is a
digital event, selections are: Equal To, Not Equal To.
Sec Test
This key allows the Operator to select the value or
condition that the Secondary Trigger is compared to.
Selection ranges from the Secondary Trigger minimum
to the Secondary Trigger maximum.
Navigation
Home
Causes an instant return to the Home Screen.
Trending
Causes an instant return to the Trending Screen.
Trend Setup
Causes an instant return to the Trend Setup Screen.
OptiView Control Center