JOHNSON CONTROLS
30
FORM 155.21-O1 (615)
GENERATOR / CONDENSER SCREEN
Overview
This screen displays a cutaway view of the chiller gen-
erator and condenser. Animation indicates whether the
chiller is presently in a run condition.
Display Only
Generator - Pressure
Displays the pressure in the generator.
Steam in - Temperature and Pressure
Displays the steam inlet temperature and pressure when
the unit is setup for steam.
Hot Water - Temperature and Pressure
Displays the hot water inlet temperature and pressure
when the unit is setup for hot water.
Strong
Solution
Displays the strong solution temperature, concentration,
ADC temperature and strong solution temperature leav-
ing the solution-to-solution heat exchanger.
Min temp to Crystallize
Displays the minimum temperature calculated to crystal-
lize the strong solution.
Condenser
Displays the leaving cooling liquid temperature and re-
frigerant temperature from the Condenser.
Programmable
Load
Access Level Required:
SERVICE
This key puts the control valve into manual mode and
sends an open command to the control valve.
Unload
Access Level Required:
SERVICE
This key puts the control valve into manual mode and
sends a close command to the control valve.
Hold
Access Level Required:
SERVICE
This key puts the control valve into manual mode and
sends a hold command to the control valve.
Auto
Access Level Required:
SERVICE
This key returns the control valve to automatic mode.
Warning Reset
Access Level Required:
SERVICE
This soft key allows the technician to clear the warning
message when in SERVICE mode.
LD13814
FIGURE 7 -
GENERATOR / CONDENSER SCREEN
OptiView Control Center