PURGE SYSTEM SCREEN
Overview
This screen gives an overview of parameters for the
Purge System.
Display Only
Purge Pump Pressure
Displays the Purge Pump pressure, determined between
the pump isolation ball valve and solenoid valves from
PT3.
Purge Tank Pressure
Displays the Purge Tank pressure from PT4.
Last 7 Days Counter
Displays the from and to date for the 7 day purge
counter.
Auto Count
Displays the number of Autopurges performed within
the 7 day counter interval.
Manual Count
Displays the number of Manual purges performed within
the 7 day counter interval.
Autopurge Total Counter
Displays the total number of Autopurges performed.
Manual Purge Total Counter
Displays the total number of Manual purges per-
formed.
Purge
Displays the current "Auto" or "Manual" Purge system
control mode.
Purge Pump
Displays the current "ON" or "OFF" state of the Purge
pump.
7SOL
Displays the "Open" or "Closed" position of the purge
tank solenoid valve (7SOL).
8SOL
Displays the "Open" or "Closed" position of the purge
pump isolation ball valve (8SOL).
LD13816
FIGURE 9 -
PURGE SYSTEM SCREEN