background image

10

11 - Technical appendix

10 - Maintenance

The units are designed to operate for long periods of time with a minimum of maintenance. However, the following operations must be
performed regularly.

Component

Maintenance operation

Recommended frequency

Air filter

1 -  Clean with a vacuum cleaner or tap gently then 

Every month or more

wash in warm water (40°C) with a mild detergent.

often if necessary.

2 -  Rinse and dry before replacing on unit.

3 -  Never use petrol, alcohol or any other chemical 

product.

Unit casing

1 -  Remove dust from the front panel with a soft duster 

Every month or  more

or wipe a damp cloth with a mild soap solution.

often if necessary.

2 -  Never use petrol, alcohol or any other chemical 

product.

Drain pan and

1 -  Clean and check for obstructions.

Each season before start up.

evacuation piping

Indoor / outdoor coils

1 - Check condition and remove dust from between 

Each season before start up.

coil fins.

Compressor

1 -  No maintenance required.

A L L O T H E R SERVICE AND MAINTENANCE OPERATIONS MUST BE PERFORMED BY TRAINED

AND QUALIFIED PERSONNEL APPROVED BY THE SUPPLIER

Unit Capacity

Total cooling capacity can be determined by using correction fac-
tors C1, C2 and C3.
Given cooling capacity = Cooling capacity at standard rating
conditions x C1 x C2 x C3.

C1 = Capacity correction factor for temperature
C2 = Capacity correction for piping length
C3 = Capacity correction for indoor unit fan speed

Capacity correction factor for temperature (C1)

*

Conditions applicable for the "Low ambient line" / +19°C for the "Export
line".

Correction factors (C1) determine the instantaneous capacity (which
does not take account of defrosting on heat pump units). T h e s e
capacities may vary slightly, depending on the size of the unit.

Cooling capacity correction factor

Indoor temp.

Outdoor temp. °C DB

°C WB

19

25

30

35

40

46

23

-

1.20

1.15

1.11

1.06

1

19

1.10

1.08

1.04

1

0.96

0.90

14

0.88

0.86

0.84

0.82

0.79

0.74

Heating capacity correction factor

Indoor temp.

Outdoor temp. °C WB

°C DB

14

10

6

0

-8

23

1.20

1.04

0.96

0.77

0.58

20

1.25

1.10

1

0.80

0.69

17

1.30

1.13

1.04

0.83

0.63

Maximum

Minimum

Cooling mode

+46°C

0°C 

(-10 with fan stoppage)

Heating mode

+28°C 

-10°C

(heat pump mode)

Unité intérieure

Fan speed

High

Medium

Low

Correction factor C3

1

0.90

0.75

Capacity correction factor for indoor fan speed (C3)

Capacity correction factor for piping length (C2)

Operating temperature limits

Indoor unit

Piping length (m)

7.5

10

Correction factor C2

1

0.98

<--

Summary of Contents for MOC12

Page 1: ...Cassette MINISPLIT MKC MKH 12 18 24 Infrared remote control MOC MOH YORK...

Page 2: ...ning Dismantling and Disposal 1 Safety Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel Regular maintenance operations such as...

Page 3: ...0 C Indoor MKC MKH Models unit 12S 18S 24S Outdoor MOC MOH unit 12 18 25 Cooling Btu h 12 000 18 000 24 000 kW 3 5 5 3 7 Capacities Heating Btu h 12 500 18 500 25 100 kW 3 6 5 4 7 1 Electric heating k...

Page 4: ...istics table on page 3 Outdoor unit MOC MOH 12 18 Outdoor unit MOC MOH 25 H L P Clearances required for outdoor units C B E A D 5 4 2 3 660 575 1 660 1 False ceiling 2 Condensate drainage 3 Gas line c...

Page 5: ...is way and the remote control is forced off line The tempera ture setpoint is set at 24 C both in the heating and cooling mode To revert to normal remote control operation set the selector to the NOR...

Page 6: ...ulated to prevent dro plets of condensation from dripping on the false ceiling Connect the drainage tube int 12 mm coming from the pump to a P V C drainage line 32 mm mini It is advisable to install a...

Page 7: ...oid alteration of unit capacities make sure that piping lengths and changes in elevation are kept to a strict minimum Before connecting the refrigerant lines follow the procedures below if pre charged...

Page 8: ...s Fit the casing and grille together using the screws fig 5 ref b Put the filter fig 6 and the return air grille fig 6 7 back in place 8 Wiring diagram 9 Front panel installation 1 N E 2 1 N E A 2 Pow...

Page 9: ...g 6 a a a a A Cooling operation summer Coanda effect Heating operation winter Detail A Depending on the configuration of the room to be air conditioned one or two of the deflectors may be left closed...

Page 10: ...y can be determined by using correction fac tors C1 C2 and C3 Given cooling capacity Cooling capacity at standard rating conditions x C1 x C2 x C3 C1 Capacity correction factor for temperature C2 Capa...

Page 11: ...12 18 24 MKH 12 18 24 SERIAL NUMBER IS IN COMPLIANCE WITH THE REQUIREMENTS OF APPLICABLE EEC DIRECTIVES 89 392 EC 89 336 CEE NATIONAL STANDARDS AND TECHNICAL SPECIFICATIONS ISO 9001 Pr EN378 AND IN AC...

Page 12: ...very unit This refrigerant may then be re used if appropriate or returned to the manufacturer for disposal Under NO circumstances should refrigerant be vented to atmosphere Where appropriate drain the...

Reviews: