background image

9

Directing the airflow

With direct air discharge, pay particular attention to the direction
in which the air is discharged.

• Air deflectors (ref a)
These deflectors should be directed so that a maximum volume is
given to the envelope of the airstream. Below, the diagram shows
the optimum position required to acheive the best possible airflow
performance.

• Integral diffuser
In the cooling mode, cool air is discharged horizontally just below
the ceiling, ensuring even air distribution in the room due to the
«coanda» effect without causing drafts.
In the heating mode, airflow can be directed so as to prevent stag-
nation at certain places in the room (stratification of hot air).

9 - Front panel installation (cont’d)

Fig. 7

Fig. 6

a

a

a

a

A

Cooling operation (summer)

Coanda effect

Heating operation (winter)

Detail A

Depending on the configuration of the room to be air conditioned,one or two of the deflectors may be left closed.

Summer position

Winter position

YES

YES

NO

Depending on the layout of the conditioned space, 1 or 2 dampers may be closed. This is necessary for air discharge through a
discharge satellite into an adjacent room or when the cassette unit is installed too close to a wall.

Operation in heating mode only : Although the unit has an anti-stratification
function, it may be necessary to offset the return air sensor setpoint, in cases
where ceilings are particularly high for example. This can be done with the two
microswitches on the control board. Setpoint offsetting is only effective in the
heating mode and has no effect on the cooling mode.

Temp. 

Switch

difference °C

2

1

0

OFF

OFF

1

OFF

ON

3

ON

OFF

5

ON

ON

2

ON

OFF

<--

Summary of Contents for MOC12

Page 1: ...Cassette MINISPLIT MKC MKH 12 18 24 Infrared remote control MOC MOH YORK...

Page 2: ...ning Dismantling and Disposal 1 Safety Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel Regular maintenance operations such as...

Page 3: ...0 C Indoor MKC MKH Models unit 12S 18S 24S Outdoor MOC MOH unit 12 18 25 Cooling Btu h 12 000 18 000 24 000 kW 3 5 5 3 7 Capacities Heating Btu h 12 500 18 500 25 100 kW 3 6 5 4 7 1 Electric heating k...

Page 4: ...istics table on page 3 Outdoor unit MOC MOH 12 18 Outdoor unit MOC MOH 25 H L P Clearances required for outdoor units C B E A D 5 4 2 3 660 575 1 660 1 False ceiling 2 Condensate drainage 3 Gas line c...

Page 5: ...is way and the remote control is forced off line The tempera ture setpoint is set at 24 C both in the heating and cooling mode To revert to normal remote control operation set the selector to the NOR...

Page 6: ...ulated to prevent dro plets of condensation from dripping on the false ceiling Connect the drainage tube int 12 mm coming from the pump to a P V C drainage line 32 mm mini It is advisable to install a...

Page 7: ...oid alteration of unit capacities make sure that piping lengths and changes in elevation are kept to a strict minimum Before connecting the refrigerant lines follow the procedures below if pre charged...

Page 8: ...s Fit the casing and grille together using the screws fig 5 ref b Put the filter fig 6 and the return air grille fig 6 7 back in place 8 Wiring diagram 9 Front panel installation 1 N E 2 1 N E A 2 Pow...

Page 9: ...g 6 a a a a A Cooling operation summer Coanda effect Heating operation winter Detail A Depending on the configuration of the room to be air conditioned one or two of the deflectors may be left closed...

Page 10: ...y can be determined by using correction fac tors C1 C2 and C3 Given cooling capacity Cooling capacity at standard rating conditions x C1 x C2 x C3 C1 Capacity correction factor for temperature C2 Capa...

Page 11: ...12 18 24 MKH 12 18 24 SERIAL NUMBER IS IN COMPLIANCE WITH THE REQUIREMENTS OF APPLICABLE EEC DIRECTIVES 89 392 EC 89 336 CEE NATIONAL STANDARDS AND TECHNICAL SPECIFICATIONS ISO 9001 Pr EN378 AND IN AC...

Page 12: ...very unit This refrigerant may then be re used if appropriate or returned to the manufacturer for disposal Under NO circumstances should refrigerant be vented to atmosphere Where appropriate drain the...

Reviews: