York MILLENNIUM YK Wiring Diagram Download Page 9

FORM 160.54-PW7

9

YORK INTERNATIONAL

REMOTE CURRENT LIMIT SETPOINT with 0-10VDC,
2-10 VDC, 0-20mA, 4-20mA or Pulse Width Modula-
tion Signal.

The Remote Current Limit setpoint can be reset over
the range of 100% to 30% Full Load Amps (FLA) by
supplying (by  others) a 0-10VDC, 2-10VDC, 0-20mA,
4-20mA or 1 to 11 second Pulse Width Modulated
(PWM) signal to the OptiView Control Center. The
OptiView Control Center must be configured appropri-
ately to accept the desired signal type as follows:

• The appropriate Remote Mode must be selected:

Analog Remote Mode must be selected when us-
ing a voltage or current signal input. Digital Re-
mote Mode must be selected when using a PWM
input.

• If Analog Remote Mode is selected, the Remote

Analog Input Range setpoint must be set to “0-
10VDC” or “2-10VDC” as detailed below, regard-
less of whether the signal is a voltage or current
input signal type.

• Microboard Program Jumper P23 must be positioned

appropriately per the input signal type as detailed
below. It is recommended that a qualified Service
Technician position this jumper.

Important! The signal type used for
Remote Current Limit Setpoint reset
and the signal type used for Remote
Leaving Chilled Liquid Temperature
setpoint reset must be the same. For
example, if a 0-10VDC signal is be-
ing used for Remote Leaving Chilled
Liquid Temperature Reset , then a 0-
10VDC signal must be used for Re-
mote Current Limit Reset.

0-10VDC - As shown in Fig. 15, connect input to
Microboard J22-1 (signal) and J22-5 (Gnd). The setpoint
varies linearly from 100% to 30% FLA as the input var-
ies from 0-10VDC. This input will only be accepted when
Analog Remote Mode is selected, the “Remote Ana-
log Input Range” 
setpoint is set for 0-10 Volts, and
Microboard Program Jumper JP23 has been removed.
Calculate the setpoint for various inputs as follows:

SETPOINT (%) = 100 – (VDC X 7)

For example, if the input is 5VDC, the setpoint would
be set to 65% as follows:

SETPOINT (%) = 100 – (5 X 7) = 100 – 35 = 65%

2-10VDC - As shown in Fig. 15, connect input to
Microboard J22-1 (signal) and J22-5 (Gnd). The setpoint
varies linearly from 100% to 30% FLA as the input
varies from 2 to 10VDC. This input will only be ac-
cepted when “Analog” Remote Mode is selected, the
“Remote Analog Input Range” setpoint is set for
“2-10 Volts” and Microboard Program Jumper JP23 has
been removed. Calculate the setpoint for various inputs
as follows:

FIG. 14 – ELECTRO-MECHANICAL STARTER
MANUAL RESET OVERLOADS

The chiller compressor type deter-
mines which terminals must be used
for this feature. Failure to use the
proper terminals could result in se-
rious chiller damage!

Terminals are available for connection of the manual re-
set overloads and/or safety devices in the high voltage
Electro-Mechanical Starter for U.L. or C.S.A. approved
units having 2300 to 4160 volt motors. The appropriate
terminals must be selected based on the chiller compres-
sor type. For chillers that are not equipped with compres-
sor code “P”, use terminals 1 and 53 as shown in Figure
14. For chillers equipped with compressor code “P”, use
terminals 15 and 53 as shown in Figure 14A. Refer to
appropriate Remote Motor Starter Specification as fol-
lows: 160.45-PA5.1 (all compressors except “P”);
160.54-PW14 (chillers equipped with “P” compressors).
An opening of the contacts causes the OptiView Control
Center to display: “CYCLING SHUTDOWN – AUTO
RESTART” and “MOTOR CONTROLLER – CON-
TACTS OPEN”. To restart the chiller, reset the external
device in the Electro-mechanical Starter that caused the
shutdown. Then the unit will automatically restart.

FIG. 15 – REMOTE CURRENT LIMIT SETPOINT WITH

0-10VDC OR 2-10VDC SIGNAL

SIGNAL

COMMON

5

1

+

J22

LD04498

Summary of Contents for MILLENNIUM YK

Page 1: ...s provisions for remote control inputs and provisions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contact...

Page 2: ...ll load amperes for 1 to 255 minutes following each compressor start For more details refer to OptiView Control Center Instructions Form 160 54 O1 6 Controlling the maximum allowable compressor motor...

Page 3: ...U L or C S A Approved Units Only 8 Fig 14A Electro Mechanical Starter Manual Reset Overloads P Compressors Only 2300 to 4160 Volts U L or C S A Approved Units Only 8 Fig 15 Remote Current Limit Setpo...

Page 4: ...ion so they will allow the unit to start 4 The OptiView Control Center COMPRESSOR switch is in the RUN l position 5 The 30 minute anti recycle timer has timed out A closure of the Remote Mode Ready to...

Page 5: ...f Range FIG 5 ANTICIPATORY ALARM CONTACTS LD04604 FIG 6 REMOTE START AND STOP CONTACTS FROM ENERGY MANAGEMENT SYSTEM When the OptiView Control Center is in the Digital Analog or ISN remote operating m...

Page 6: ...lowing messages CYCLING SHUTDOWN AUTO RESTART and SYSTEM CYCLING CONTACTS OPEN The OptiView Control Center con tains a seven day time clock to select daily schedule Start Stop times Sun day through Sa...

Page 7: ...TWO UNIT SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag un...

Page 8: ...LE UNITS TWO PARALLEL OPERATION SINGLE CHILLED WATER PUMP For this piping arrangement each chiller s water sensor is located in its own leaving water nozzle This produces a constant mixed chilled wate...

Page 9: ...lts and Microboard Program Jumper JP23 has been removed Calculate the setpoint for various inputs as follows SETPOINT 100 VDC X 7 For example if the input is 5VDC the setpoint would be set to 65 as fo...

Page 10: ...dulation input is in the form of a 1 to 11 second relay contact closure that applies 115VAC to the I O Board TB4 20 for 1 to 11 seconds As shown in Fig 17 connect dry closure relay contacts between I...

Page 11: ...SET F VDC 2 REMOTE RESET TEMP RANGE 8 SETPOINT F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 40 F the setpoint would be set to 43...

Page 12: ...e set to 44 F as follows SIGNAL COMMON 5 4 J22 FIG 19 REMOTE LEAVING CHILLED LIQUID TEMP SETPOINT WITH 0 20MA OR 4 20MA SIGNAL LD04501 OFFSET F 8 10 20 80 20 4 F SETPOINT F 40 4 44 F 4 20mA As shown i...

Page 13: ...J11 1 JP27 1 SHLD GND _ 5V J11 SHLD GND _ 5V J11 SHLD GND _ 5V J12 SHLD GND _ 5V MICROBOARD 031 01730 1 PC 104 2 1 J17 J16 FIG 21 MICROBOARD DIP SWITCH FOR AUTO MANUAL RESTART AFTER POWER FAILURE LD04...

Page 14: ...er square inch psia For Metric Units temperature is in degrees Celsius C and pressure in KiloPascals kPa _ _ On Solid State Starter units only when the Current Imbalance option is selected via the Sol...

Page 15: ...un Light The control relay scheme shown in Fig 23 can also be applied for a remote Run Light AND a Remote Shutdown Indicator when an EMS is not used When Evaporator Water is flowing the flow switch co...

Page 16: ...e accomplished in sev eral ways Two flow switches a flow switch and a relay or separate contacts on the same flow switch 14 15 Do not apply voltage on field wiring terminal blocks TB4 and TB6 in YORK...

Reviews: