York MILLENNIUM YK Wiring Diagram Download Page 13

FORM 160.54-PW7

13

YORK INTERNATIONAL

FIG. 21 – MICROBOARD DIP SWITCH FOR POWER
FAILURE RESTART

This figure shows the location of the Power Failure
Restart Dip Switch 
on the Microboard. The
Microboard is mounted on the rear panel located di-
rectly behind the OptiView Control Center door.

1. Power Failure Restart Dip Switch - The Con-

trol Panel is furnished for Manual Restart After
Power Failure as a standard function. The Control
Panel can be field-changed to Automatic Restart
after a power failure if the Manual  Restart fea-
ture is not desired. Simply place position 5 of the
12-position Dip Switch (SW1) on ON and the Au-
tomatic 
Restart feature will be enabled. Place to
the OFF position to return to Manual Restart.

2. English/Metric Display Units Configuration  –

The Control Panel can present data on the Graphic
Display in English or Metric Units. In Operator Ac-
cess Level, from the HOME screen, press the
“Setpoints” key to go to the SETPOINTS screen.
Next, press the “Setup” key to go to the SETUP
screen. Press the “User”  key to go the USER

J19

J20

J15

SW

1

50

49

6

3

1

1

1
2
3
4
5
6
7
8
9
10
11
12

OFF

1

J2

N.C.

GND
GND

GTX

GRX

DTRI
TXDI
RXDI
DSRI

N.C.

N.C.

GND

R12

DTR2
CTS2
TXD2

RTS2

RXD2
DSR2
DCD2

1

J13

JP34
JP35
JP36
JP37

J5

J18

J6

1

1

1

J22

J21

J7

J8

J9

1
2

3
4

12

24

13

1

1

1

1

1

JP24 JP23 JP22 JP21

JP41

JP42

JP40

JP40

JP40
JP39

1

11

22

12

20

10

1

11

1

1

4

5

1

J1

J10

J11

1

JP27

1

SHLD

GND

+

_

5V

J11

SHLD

GND

+

_

5V

J11

SHLD

GND

+

_

5V

J12

SHLD

GND

+

_

5V

MICROBOARD

031-01730

1

PC/104

2

1

J17

J16

FIG. 21 – MICROBOARD DIP SWITCH FOR AUTO/

MANUAL RESTART AFTER POWER
FAILURE

LD04396

LD06833

FIG. 20 – REMOTE LEAVING CHILLED LIQUID TEM-

PERATURE SETPOINT WITH PWM SIGNAL

PWM – The Pulse Width Modulation input is in the
form of a 1 to 11 second relay contact closure that ap-
plies 115VAC to the I/O Board TB4-19 for 1-11 sec-
onds. As shown in Fig. 20, connect dry closure relay
contacts between I/O Board TB4-19 (input) and TB4-1
(115VAC). A contact closure time (pulse width) of 1
second produces a 0°F offset. An 11 second closure
produces the maximum allowed offset (10 or 20°F above
the local setpoint value). The relay contacts should close
for 1 to 11 seconds at least once every 30 minutes to
maintain the setpoint to the desired value. If a 1 to 11
second closure is not received within 30 minutes of the
last closure, the setpoint is defaulted to the Local setpoint
value. A closure is only accepted at rates not to exceed
once every 70 seconds. This input will only be accepted
in  “Digital” Remote Mode. Calculate the setpoint
for various pulse widths as follows:

OFFSET(°F) =

(PULSE WIDTH IN SECONDS)(REMOTE RESET TEMP. RANGE)

10

SETPOINT(°F) = LOCAL SE OFFSET

For example, if the relay contacts close for 5 seconds
and the Remote Reset Temp Range setpoint is pro-
grammed for 10°F, and the Local Leaving Chilled Liq-
uid Temperature setpoint is programmed for 40°F, the
setpoint would be set to 44°F as follows:

OFFSET (°F)

= (5 – 1)(10)

          10

= (4)(10)

      10

= 40

   10

= 4°F

SETPOINT (°F)

= 40 + 4

= 44°F

Summary of Contents for MILLENNIUM YK

Page 1: ...s provisions for remote control inputs and provisions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contact...

Page 2: ...ll load amperes for 1 to 255 minutes following each compressor start For more details refer to OptiView Control Center Instructions Form 160 54 O1 6 Controlling the maximum allowable compressor motor...

Page 3: ...U L or C S A Approved Units Only 8 Fig 14A Electro Mechanical Starter Manual Reset Overloads P Compressors Only 2300 to 4160 Volts U L or C S A Approved Units Only 8 Fig 15 Remote Current Limit Setpo...

Page 4: ...ion so they will allow the unit to start 4 The OptiView Control Center COMPRESSOR switch is in the RUN l position 5 The 30 minute anti recycle timer has timed out A closure of the Remote Mode Ready to...

Page 5: ...f Range FIG 5 ANTICIPATORY ALARM CONTACTS LD04604 FIG 6 REMOTE START AND STOP CONTACTS FROM ENERGY MANAGEMENT SYSTEM When the OptiView Control Center is in the Digital Analog or ISN remote operating m...

Page 6: ...lowing messages CYCLING SHUTDOWN AUTO RESTART and SYSTEM CYCLING CONTACTS OPEN The OptiView Control Center con tains a seven day time clock to select daily schedule Start Stop times Sun day through Sa...

Page 7: ...TWO UNIT SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag un...

Page 8: ...LE UNITS TWO PARALLEL OPERATION SINGLE CHILLED WATER PUMP For this piping arrangement each chiller s water sensor is located in its own leaving water nozzle This produces a constant mixed chilled wate...

Page 9: ...lts and Microboard Program Jumper JP23 has been removed Calculate the setpoint for various inputs as follows SETPOINT 100 VDC X 7 For example if the input is 5VDC the setpoint would be set to 65 as fo...

Page 10: ...dulation input is in the form of a 1 to 11 second relay contact closure that applies 115VAC to the I O Board TB4 20 for 1 to 11 seconds As shown in Fig 17 connect dry closure relay contacts between I...

Page 11: ...SET F VDC 2 REMOTE RESET TEMP RANGE 8 SETPOINT F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 40 F the setpoint would be set to 43...

Page 12: ...e set to 44 F as follows SIGNAL COMMON 5 4 J22 FIG 19 REMOTE LEAVING CHILLED LIQUID TEMP SETPOINT WITH 0 20MA OR 4 20MA SIGNAL LD04501 OFFSET F 8 10 20 80 20 4 F SETPOINT F 40 4 44 F 4 20mA As shown i...

Page 13: ...J11 1 JP27 1 SHLD GND _ 5V J11 SHLD GND _ 5V J11 SHLD GND _ 5V J12 SHLD GND _ 5V MICROBOARD 031 01730 1 PC 104 2 1 J17 J16 FIG 21 MICROBOARD DIP SWITCH FOR AUTO MANUAL RESTART AFTER POWER FAILURE LD04...

Page 14: ...er square inch psia For Metric Units temperature is in degrees Celsius C and pressure in KiloPascals kPa _ _ On Solid State Starter units only when the Current Imbalance option is selected via the Sol...

Page 15: ...un Light The control relay scheme shown in Fig 23 can also be applied for a remote Run Light AND a Remote Shutdown Indicator when an EMS is not used When Evaporator Water is flowing the flow switch co...

Page 16: ...e accomplished in sev eral ways Two flow switches a flow switch and a relay or separate contacts on the same flow switch 14 15 Do not apply voltage on field wiring terminal blocks TB4 and TB6 in YORK...

Reviews: