York MILLENNIUM YK Wiring Diagram Download Page 10

YORK INTERNATIONAL

10

SIGNAL

COMMON

5

2

+

J22

LD04499

FIG. 16 – REMOTE CURRENT LIMIT SETPOINT WITH

0-20mA OR 4-20mA SIGNAL

SETPOINT (%) = 100 – [(VDC – 2) X 8.75]

For example, if the input is 5VDC, the setpoint would
be set to 74% as follows:

SETPOINT (%)

= 100 – [(5-2) X 8.75]

= 100 – [3 X 8.75]

= 100 – 26.25 = 74%

0-20 mA - As shown in Fig. 16, connect input to
Microboard J22-2 (signal) and J2-5 (Gnd). The setpoint
varies linearly from 100% to 30% FLA as the input
varies from 0mA to 20mA. This input will only be ac-
cepted when “Analog” Remote Mode is selected, the
“Remote Analog Input Range” setpoint is set for 0-
10 Volts, and Microboard Program Jumper JP23 has
been placed on pins 1 and 2. Calculate the setpoint for
various inputs as follows:

SETPOINT (%) = 100 – (mA X 3.5)

For example, if the input is 8mA, the setpoint would be
set to 72% as follows:

SETPOINT (%)

= 100 – (8 X 3.5)
= 100 – 28 = 72%

4-20mA - As shown in Figure 16, connect input to
Microboard J22-2 (signal) and J2-5 (Gnd). The setpoint
varies linearly from 100% to 30% FLA as the input
varies from 4mA to 20mA. This input will only be ac-
cepted when “Analog” Remote Mode is selected, the
“Remote Analog Input Range” setpoint is set for
“2-10 Volts” and Microboard Program Jumper JP23 has
been placed on pins 1 and 2. Calculate the setpoint for
various inputs as follows:

SETPOINT (%)

= 100 – [(MA – 4) X 4.375]

For example, if the input is 8mA, the setpoint would be
set to 83% as follows:

SETPOINT (%)

= 100 – [(8 – 4) X 4.375]
= 100 – (4 X 4.375)
= 100 – 17.5
= 82.5
= 83%

FIG. 17 –  REMOTE CURRENT LIMIT SETPOINT

WITH PWM SIGNAL

LD06832

PWM - The Pulse Width Modulation input is in the form
of a 1 to 11 second relay contact closure that applies
115VAC to the I/O Board TB4-20 for 1 to 11 seconds.
As shown in Fig. 17, connect dry closure relay contacts
between I/O Board TB4-20 (signal) and TB4-1
(115VAC). The setpoint varies linearly from 100% to
30% as the relay contact closure time changes from 1
to 11 seconds. The relay contacts should close for 1 to
11 seconds at least once every 30 minutes to maintain
the setpoint to the desired value. If a 1 to 11 second
closure is not received within 30 minutes of the last clo-
sure, the setpoint is defaulted to 100%. A closure is
only accepted at rates not to exceed once every 70 sec-
onds. This input will only be accepted in “Digital” Re-
mote Mode. Calculate the setpoint for various pulse
widths as follows:

SETPOINT (%) = 100 – [(PULSE WIDTH IN SECONDS – 1) X 7]

For example, if the relay contacts close for 3 seconds,
the setpoint would be set to 86% as follows:

SETPOINT (%)

= 100 – [(3 – 1) X 7]
= 100 – (2 X 7)
= 100 – 14
= 86%

REMOTE LEAVING CHILLED LIQUID SETPOINT with
0-10VDC, 2-10VDC, 0-20mA, 4-20mA or Pulse Width
Modulation Signal

Remote Leaving Chilled Liquid Temperature Setpoint
Reset can be accomplished by supplying (by others) a
0-10VDC, 2-10VDC, 0-20mA, 4-20mA or 1 to 11 sec-
ond Pulse Width Modulated (PWM) signal to the Con-
trol Center. The Leaving Chilled Liquid Tempera-
ture Setpoint 
is programmable over the range of 38°F
to 70°F (water applications), 36°F to 70°F (water appli-
cations with Smart Freeze Protection enabled) or 10°F
to 70°F (brine applications). The Remote Input Signal
changes the setpoint by creating an offset above the
locally programmed Leaving Chilled Liquid Tempera-
ture Base Setpoint value. The setpoint can be remotely

Summary of Contents for MILLENNIUM YK

Page 1: ...s provisions for remote control inputs and provisions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contact...

Page 2: ...ll load amperes for 1 to 255 minutes following each compressor start For more details refer to OptiView Control Center Instructions Form 160 54 O1 6 Controlling the maximum allowable compressor motor...

Page 3: ...U L or C S A Approved Units Only 8 Fig 14A Electro Mechanical Starter Manual Reset Overloads P Compressors Only 2300 to 4160 Volts U L or C S A Approved Units Only 8 Fig 15 Remote Current Limit Setpo...

Page 4: ...ion so they will allow the unit to start 4 The OptiView Control Center COMPRESSOR switch is in the RUN l position 5 The 30 minute anti recycle timer has timed out A closure of the Remote Mode Ready to...

Page 5: ...f Range FIG 5 ANTICIPATORY ALARM CONTACTS LD04604 FIG 6 REMOTE START AND STOP CONTACTS FROM ENERGY MANAGEMENT SYSTEM When the OptiView Control Center is in the Digital Analog or ISN remote operating m...

Page 6: ...lowing messages CYCLING SHUTDOWN AUTO RESTART and SYSTEM CYCLING CONTACTS OPEN The OptiView Control Center con tains a seven day time clock to select daily schedule Start Stop times Sun day through Sa...

Page 7: ...TWO UNIT SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag un...

Page 8: ...LE UNITS TWO PARALLEL OPERATION SINGLE CHILLED WATER PUMP For this piping arrangement each chiller s water sensor is located in its own leaving water nozzle This produces a constant mixed chilled wate...

Page 9: ...lts and Microboard Program Jumper JP23 has been removed Calculate the setpoint for various inputs as follows SETPOINT 100 VDC X 7 For example if the input is 5VDC the setpoint would be set to 65 as fo...

Page 10: ...dulation input is in the form of a 1 to 11 second relay contact closure that applies 115VAC to the I O Board TB4 20 for 1 to 11 seconds As shown in Fig 17 connect dry closure relay contacts between I...

Page 11: ...SET F VDC 2 REMOTE RESET TEMP RANGE 8 SETPOINT F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 40 F the setpoint would be set to 43...

Page 12: ...e set to 44 F as follows SIGNAL COMMON 5 4 J22 FIG 19 REMOTE LEAVING CHILLED LIQUID TEMP SETPOINT WITH 0 20MA OR 4 20MA SIGNAL LD04501 OFFSET F 8 10 20 80 20 4 F SETPOINT F 40 4 44 F 4 20mA As shown i...

Page 13: ...J11 1 JP27 1 SHLD GND _ 5V J11 SHLD GND _ 5V J11 SHLD GND _ 5V J12 SHLD GND _ 5V MICROBOARD 031 01730 1 PC 104 2 1 J17 J16 FIG 21 MICROBOARD DIP SWITCH FOR AUTO MANUAL RESTART AFTER POWER FAILURE LD04...

Page 14: ...er square inch psia For Metric Units temperature is in degrees Celsius C and pressure in KiloPascals kPa _ _ On Solid State Starter units only when the Current Imbalance option is selected via the Sol...

Page 15: ...un Light The control relay scheme shown in Fig 23 can also be applied for a remote Run Light AND a Remote Shutdown Indicator when an EMS is not used When Evaporator Water is flowing the flow switch co...

Page 16: ...e accomplished in sev eral ways Two flow switches a flow switch and a relay or separate contacts on the same flow switch 14 15 Do not apply voltage on field wiring terminal blocks TB4 and TB6 in YORK...

Reviews: