FIG. 9 – CONDENSER WATER FLOW INTERLOCK

If desired, a condenser water flow interlock can be ap-
plied. Flow switch – McDonnel type FS8W, max. 150
psi (YORK Part No. 024-15793) available at additional
cost. If condenser water flow switch is not used, a
jumper must be installed between terminals 1 and 11 .

When condenser water is flowing, the flow switch con-
tact will close. Opening of the condenser water flow
switch contacts for 2 continuous seconds will cause unit
shutdown. The Flow Switch Status is checked 30 sec-
onds into “System Run” and continuously thereafter.
The OptiView Control Center will display the following
message: “CYCLING SHUTDOWN – AUTO RE-
START” and “CONDENSER FLOW SWITCH
OPEN”.

FIG. 7 – REMOTE/LOCAL CYCLING DEVICES

FIG. 7 – REMOTE/LOCAL CYCLING DEVICES

The closure of an automatic reset device across this
input will permit the unit to operate in all operating
modes. Conversely, an opening of the device contacts
will inhibit the unit from operating; the OptiView Con-
trol Center will then display the following messages:
“CYCLING SHUTDOWN – AUTO RESTART” and
“SYSTEM CYCLING – CONTACTS OPEN”.

The OptiView Control Center con-
tains a seven day time clock to select
daily schedule Start/Stop times (Sun-
day through Saturday including one
or more holidays in week) up to one
full week at a time. So automatic start
and stop of the unit on a daily basis,
at predetermined times, can be pro-
grammed as a standard feature; an ad-
ditional program timer is not required
for this function.

LD06828

FIG. 8 – MULTI-UNIT SEQUENCE

FIG. 9  – CONDENSER WATER FLOW INTERLOCK

LD06825

LD06827

FIG. 8 – MULTI-UNIT SEQUENCE

For multiple chiller installation application, Multi-Unit
Sequence contacts are available to start and stop each
unit. The maintained closure of a device contacts across
terminals   

1

   and    

9

    will permit the unit to operate in

all the operating modes with the “compressor” switch
in the “RUN” (

l

) position. Conversely, an opening of

the device contacts will inhibit the unit from operating;
the OptiView Control Center will then display the fol-
lowing message: “CYCLING SHUTDOWN – AUTO
RESTART” and “MULTIUNIT CYCLING – CON-
TACTS OPEN”. An accessory sequence control kit
for two, three or four units is available from YORK –
See Fig. 10 for Two Unit Sequence Control kit.

Summary of Contents for MILLENNIUM YK

Page 1: ...s provisions for remote control inputs and provisions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contact...

Page 2: ...ll load amperes for 1 to 255 minutes following each compressor start For more details refer to OptiView Control Center Instructions Form 160 54 O1 6 Controlling the maximum allowable compressor motor...

Page 3: ...U L or C S A Approved Units Only 8 Fig 14A Electro Mechanical Starter Manual Reset Overloads P Compressors Only 2300 to 4160 Volts U L or C S A Approved Units Only 8 Fig 15 Remote Current Limit Setpo...

Page 4: ...ion so they will allow the unit to start 4 The OptiView Control Center COMPRESSOR switch is in the RUN l position 5 The 30 minute anti recycle timer has timed out A closure of the Remote Mode Ready to...

Page 5: ...f Range FIG 5 ANTICIPATORY ALARM CONTACTS LD04604 FIG 6 REMOTE START AND STOP CONTACTS FROM ENERGY MANAGEMENT SYSTEM When the OptiView Control Center is in the Digital Analog or ISN remote operating m...

Page 6: ...lowing messages CYCLING SHUTDOWN AUTO RESTART and SYSTEM CYCLING CONTACTS OPEN The OptiView Control Center con tains a seven day time clock to select daily schedule Start Stop times Sun day through Sa...

Page 7: ...TWO UNIT SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag un...

Page 8: ...LE UNITS TWO PARALLEL OPERATION SINGLE CHILLED WATER PUMP For this piping arrangement each chiller s water sensor is located in its own leaving water nozzle This produces a constant mixed chilled wate...

Page 9: ...lts and Microboard Program Jumper JP23 has been removed Calculate the setpoint for various inputs as follows SETPOINT 100 VDC X 7 For example if the input is 5VDC the setpoint would be set to 65 as fo...

Page 10: ...dulation input is in the form of a 1 to 11 second relay contact closure that applies 115VAC to the I O Board TB4 20 for 1 to 11 seconds As shown in Fig 17 connect dry closure relay contacts between I...

Page 11: ...SET F VDC 2 REMOTE RESET TEMP RANGE 8 SETPOINT F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 40 F the setpoint would be set to 43...

Page 12: ...e set to 44 F as follows SIGNAL COMMON 5 4 J22 FIG 19 REMOTE LEAVING CHILLED LIQUID TEMP SETPOINT WITH 0 20MA OR 4 20MA SIGNAL LD04501 OFFSET F 8 10 20 80 20 4 F SETPOINT F 40 4 44 F 4 20mA As shown i...

Page 13: ...J11 1 JP27 1 SHLD GND _ 5V J11 SHLD GND _ 5V J11 SHLD GND _ 5V J12 SHLD GND _ 5V MICROBOARD 031 01730 1 PC 104 2 1 J17 J16 FIG 21 MICROBOARD DIP SWITCH FOR AUTO MANUAL RESTART AFTER POWER FAILURE LD04...

Page 14: ...er square inch psia For Metric Units temperature is in degrees Celsius C and pressure in KiloPascals kPa _ _ On Solid State Starter units only when the Current Imbalance option is selected via the Sol...

Page 15: ...un Light The control relay scheme shown in Fig 23 can also be applied for a remote Run Light AND a Remote Shutdown Indicator when an EMS is not used When Evaporator Water is flowing the flow switch co...

Page 16: ...e accomplished in sev eral ways Two flow switches a flow switch and a relay or separate contacts on the same flow switch 14 15 Do not apply voltage on field wiring terminal blocks TB4 and TB6 in YORK...

Reviews: