FIG. 22 –EXTERNAL SIGNAL FOR REFRIGERATION

UNIT FAILURE (NOTE 6)

FIG. 22 – EXTERNAL SIGNAL FOR REFRIGERATION
UNIT FAILURE

When the Safety Shutdown Contacts (see Fig. 3) are not
connected to an Energy Management System they may
be employed to energize a local or remote safety alarm (by
others). When the normally open Safety Shutdown Con-
tacts close, the alarm will indicate shutdown of the unit.
The cause of shutdown will be one or more of the follow-
ing safety controls: low oil pressure; high oil pressure; high
condenser pressure; low evaporator pressure; high oil tem-
perature; high discharge temperature; auxiliary safety;
power failure when the “Auto Restart After Power Fail-
ure”
 Dip Switch on the Microboard (Fig. 21) is in the OFF
position (SW1, position 5 = OFF), which implies that the
chiller requires “Manual Restart After Failure”.

SETUP screen. Press the “English/Metric
Units”  
key to select the desired units. The data
field will toggle between English and Metric with
each press of the “        or          ” key. For English
Units, the temperature display is in degree Fahren-
heit (°F), and absolute pressure is in pounds per
square inch (psia). For Metric Units, temperature
is in degrees Celsius (°C), and pressure in
KiloPascals (kPa).

_

_

On Solid State Starter units only, when the Current
Imbalance
 option is selected via the Solid State Starter
screen, three phase current imbalance protection is pro-
vided. A safety shutdown occurs (following a 45 sec-
ond by-pass at startup) whenever the % FLA readout
exceeds 80% for 45 seconds continuously and the %
imbalance is > 30%. When all safety controls are satis-
fied, and the OptiView Control Center COMPRESSOR
switch has been manually “Reset” (de-energizing
alarm) and returned to the RUN position (“1”), the unit
may be restarted, if panel is in “Remote” mode, via
the Remote Start contacts (Fig. 6); or, if panel is in “lo-
cal” mode by momentarily pressing the keypad com-
pressor switch to the START (“

”) position.

If the unit was shut down because of
Cycling Shutdown Contacts (see Fig.
2) the alarm will not be energized, but
the unit will have been shut down. A
closure of the safety alarm contacts
means that an operator must manu-
ally reset and restart the unit.

When the Safety Shutdown contacts close, the OptiView
Control Center will display the following message:
“SAFETY  SHUTDOWN – MANUAL RESTART”,
and cause of shutdown.

_

LD06836

FIG. 23 – RUN CONTACTS / REMOTE RUN LIGHT

AND SHUTDOWN INDICATOR PLUS EMS

Summary of Contents for MILLENNIUM YK

Page 1: ...s provisions for remote control inputs and provisions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contact...

Page 2: ...ll load amperes for 1 to 255 minutes following each compressor start For more details refer to OptiView Control Center Instructions Form 160 54 O1 6 Controlling the maximum allowable compressor motor...

Page 3: ...U L or C S A Approved Units Only 8 Fig 14A Electro Mechanical Starter Manual Reset Overloads P Compressors Only 2300 to 4160 Volts U L or C S A Approved Units Only 8 Fig 15 Remote Current Limit Setpo...

Page 4: ...ion so they will allow the unit to start 4 The OptiView Control Center COMPRESSOR switch is in the RUN l position 5 The 30 minute anti recycle timer has timed out A closure of the Remote Mode Ready to...

Page 5: ...f Range FIG 5 ANTICIPATORY ALARM CONTACTS LD04604 FIG 6 REMOTE START AND STOP CONTACTS FROM ENERGY MANAGEMENT SYSTEM When the OptiView Control Center is in the Digital Analog or ISN remote operating m...

Page 6: ...lowing messages CYCLING SHUTDOWN AUTO RESTART and SYSTEM CYCLING CONTACTS OPEN The OptiView Control Center con tains a seven day time clock to select daily schedule Start Stop times Sun day through Sa...

Page 7: ...TWO UNIT SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag un...

Page 8: ...LE UNITS TWO PARALLEL OPERATION SINGLE CHILLED WATER PUMP For this piping arrangement each chiller s water sensor is located in its own leaving water nozzle This produces a constant mixed chilled wate...

Page 9: ...lts and Microboard Program Jumper JP23 has been removed Calculate the setpoint for various inputs as follows SETPOINT 100 VDC X 7 For example if the input is 5VDC the setpoint would be set to 65 as fo...

Page 10: ...dulation input is in the form of a 1 to 11 second relay contact closure that applies 115VAC to the I O Board TB4 20 for 1 to 11 seconds As shown in Fig 17 connect dry closure relay contacts between I...

Page 11: ...SET F VDC 2 REMOTE RESET TEMP RANGE 8 SETPOINT F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 40 F the setpoint would be set to 43...

Page 12: ...e set to 44 F as follows SIGNAL COMMON 5 4 J22 FIG 19 REMOTE LEAVING CHILLED LIQUID TEMP SETPOINT WITH 0 20MA OR 4 20MA SIGNAL LD04501 OFFSET F 8 10 20 80 20 4 F SETPOINT F 40 4 44 F 4 20mA As shown i...

Page 13: ...J11 1 JP27 1 SHLD GND _ 5V J11 SHLD GND _ 5V J11 SHLD GND _ 5V J12 SHLD GND _ 5V MICROBOARD 031 01730 1 PC 104 2 1 J17 J16 FIG 21 MICROBOARD DIP SWITCH FOR AUTO MANUAL RESTART AFTER POWER FAILURE LD04...

Page 14: ...er square inch psia For Metric Units temperature is in degrees Celsius C and pressure in KiloPascals kPa _ _ On Solid State Starter units only when the Current Imbalance option is selected via the Sol...

Page 15: ...un Light The control relay scheme shown in Fig 23 can also be applied for a remote Run Light AND a Remote Shutdown Indicator when an EMS is not used When Evaporator Water is flowing the flow switch co...

Page 16: ...e accomplished in sev eral ways Two flow switches a flow switch and a relay or separate contacts on the same flow switch 14 15 Do not apply voltage on field wiring terminal blocks TB4 and TB6 in YORK...

Reviews: