York MILLENNIUM YK Wiring Diagram Download Page 2

YORK INTERNATIONAL

2

3. The OptiView Control Center has a programmable

time clock function as a standard feature with holi-
day capability. This offers one preset automatic
Start-Stop per day on a seven day calendar basis
with the ability to program a single additional holi-
day start and stop time up to a week in advance.
Chilled water pump control contacts (see Note 13)
are also provided, allowing for efficient automatic
operation of the chilled water pump to reduce en-
ergy. Two chilled water pump operating modes are
available via the CHW PUMP programming dip
switch (position 8 of SW1) on the Microboard. With
the switch in the OFF position, the chilled water
pump operates for 30 seconds prior to chiller start,
during chiller operation, coastdown, and LWT cy-
cling shutdowns. With the switch in the ON posi-
tion, the chilled water pump operates as above plus
it operates during MULTI-UNIT and REMOTE/
LOCAL cycling shutdowns.

4. Reduce the compressor-motor kW input (and thus

amps), by raising the leaving chilled liquid
temperature through remote temperature control
setpoint in the “remote” operating mode. When
remote temperature reset is accomplished by sup-
plying a 1 to 11 second pulse-width modulated sig-
nal, refer to Fig. 20. Through use of the remote
temperature control analog input on the Microboard,
the leaving chilled liquid temperature may be reset
via a 0 to 20 or 4 to 20mA D.C. current signal, a 0
to 10 or 2 to 10 volt D.C. signal.

5. Current limiting of demand during pulldown may

be accomplished by using the standard
PULLDOWN DEMAND LIMIT function pro-
vided in the OptiView Control Center. The
“Pulldown Demand Limit” key can be programmed
to limit compressor motor current from 30 to 100
percent of full load amperes, for 1 to 255 minutes
following each compressor start. For more details
refer to OptiView Control Center Instructions, Form
160.54-O1.

6. Controlling the maximum allowable compressor

motor amps from 30 to 100% through remote cur-
rent limit setpoint. Refer to Fig. 17 when the re-
mote current limit is accomplished by supplying a 1
to 11 second pulse-width modulated signal in the
“remote” operating mode. A jumper configurable
analog input is available for remote current limit
setpoint via a 0 to 20 or 4 to 20mA D.C. current
signal, a 0 to 10 or 2 to 10 volt D.C. signal.

7. The YORK ISN System may be interfaced with

the chiller OptiView Control Center to provide uni-
fied chiller plant system control. The ISN System
directly communicates with the OptiView Control
Center via the ISN Microgateway card which may
be installed in the Control Center. All temperatures,
pressures, safety alarms and cycling information
known to the OptiView Control Center are then avail-
able to the ISN System for integrated chiller plant
control, data logging, and local and remote operator
displays. The ISN Microgateway card also allows
the ISN to start, stop, and reset the chiller’s leaving
chilled water and current limit setpoints.

ENERGY MANAGEMENTS SYSTEMS (CONT’D)

External wiring, unless specified as
an optional connection in the
manufacturer’s product literature, is
not to be connected inside this cabi-
net. Furthermore, auxiliary devices

such as relays, switches, transducers and controls
may not be installed inside this enclosure. All
wiring must be in accordance with YORK’s pub-

lished specifications and must be performed only
by qualified personnel. YORK will not be respon-
sible for damages resulting from improper con-
nection to these controls or application of im-
proper control signals. Failure to follow this
warning will void the manufacturer’s warranty
and may cause serious damage to property or in-
jury to persons.

Summary of Contents for MILLENNIUM YK

Page 1: ...s provisions for remote control inputs and provisions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contact...

Page 2: ...ll load amperes for 1 to 255 minutes following each compressor start For more details refer to OptiView Control Center Instructions Form 160 54 O1 6 Controlling the maximum allowable compressor motor...

Page 3: ...U L or C S A Approved Units Only 8 Fig 14A Electro Mechanical Starter Manual Reset Overloads P Compressors Only 2300 to 4160 Volts U L or C S A Approved Units Only 8 Fig 15 Remote Current Limit Setpo...

Page 4: ...ion so they will allow the unit to start 4 The OptiView Control Center COMPRESSOR switch is in the RUN l position 5 The 30 minute anti recycle timer has timed out A closure of the Remote Mode Ready to...

Page 5: ...f Range FIG 5 ANTICIPATORY ALARM CONTACTS LD04604 FIG 6 REMOTE START AND STOP CONTACTS FROM ENERGY MANAGEMENT SYSTEM When the OptiView Control Center is in the Digital Analog or ISN remote operating m...

Page 6: ...lowing messages CYCLING SHUTDOWN AUTO RESTART and SYSTEM CYCLING CONTACTS OPEN The OptiView Control Center con tains a seven day time clock to select daily schedule Start Stop times Sun day through Sa...

Page 7: ...TWO UNIT SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag un...

Page 8: ...LE UNITS TWO PARALLEL OPERATION SINGLE CHILLED WATER PUMP For this piping arrangement each chiller s water sensor is located in its own leaving water nozzle This produces a constant mixed chilled wate...

Page 9: ...lts and Microboard Program Jumper JP23 has been removed Calculate the setpoint for various inputs as follows SETPOINT 100 VDC X 7 For example if the input is 5VDC the setpoint would be set to 65 as fo...

Page 10: ...dulation input is in the form of a 1 to 11 second relay contact closure that applies 115VAC to the I O Board TB4 20 for 1 to 11 seconds As shown in Fig 17 connect dry closure relay contacts between I...

Page 11: ...SET F VDC 2 REMOTE RESET TEMP RANGE 8 SETPOINT F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 40 F the setpoint would be set to 43...

Page 12: ...e set to 44 F as follows SIGNAL COMMON 5 4 J22 FIG 19 REMOTE LEAVING CHILLED LIQUID TEMP SETPOINT WITH 0 20MA OR 4 20MA SIGNAL LD04501 OFFSET F 8 10 20 80 20 4 F SETPOINT F 40 4 44 F 4 20mA As shown i...

Page 13: ...J11 1 JP27 1 SHLD GND _ 5V J11 SHLD GND _ 5V J11 SHLD GND _ 5V J12 SHLD GND _ 5V MICROBOARD 031 01730 1 PC 104 2 1 J17 J16 FIG 21 MICROBOARD DIP SWITCH FOR AUTO MANUAL RESTART AFTER POWER FAILURE LD04...

Page 14: ...er square inch psia For Metric Units temperature is in degrees Celsius C and pressure in KiloPascals kPa _ _ On Solid State Starter units only when the Current Imbalance option is selected via the Sol...

Page 15: ...un Light The control relay scheme shown in Fig 23 can also be applied for a remote Run Light AND a Remote Shutdown Indicator when an EMS is not used When Evaporator Water is flowing the flow switch co...

Page 16: ...e accomplished in sev eral ways Two flow switches a flow switch and a relay or separate contacts on the same flow switch 14 15 Do not apply voltage on field wiring terminal blocks TB4 and TB6 in YORK...