York MILLENNIUM YK Wiring Diagram Download Page 16

P.O. Box 1592, York, Pennsylvania USA  17405-1592

Subject to change without notice. Printed in USA

Copyright © by York International Corporation 2001

ALL RIGHTS RESERVED

Form 160.54-PW7 (401)
Supersedes: 160.54-PW7 (799)

Tele. 800-861-1001

www.york.com

10. Lead selector and cycling control to provide similar

lead selection and cycling of lag units for three (3)
units is available: Kit No. 366-44684D (see Product
Drawing Form 160.00-PA1.1) in NEMA I enclosure.
Consult your YORK representative.

11. Sequence control kits (see Fig.9 and Note 10)  as-

sume a constant chilled water flow and a constant
leaving chilled water temperature to sense the cool-
ing load. Sequence control kits are not designed for
variable chilled water flow or with reset of the leav-
ing chilled water temperature  – see Figs. 18 to 20
and Note 2.

12. Maximum allowable current draw between circuits

24 and 2 for field installed devices is 2 amp hold-

ing and 10 amps inrush – see OptiView Control Cen-
ter Wiring Diagram Form No. in Note 1.

13. For required field wiring connections of the chilled

water pump contacts (terminals 44 and  45 on
OptiView Control Center field wiring terminal block
TB2) and chilled water flow switch
(terminals 1 and 12 on OptiView Control Center
field wiring terminal board TB2), see Wiring Dia-
gram – Field Connections: For those chillers that are
not equipped with “P” code compressors, refer to the
following Product Drawings: 160.54-PW4 (Electro-
Mechanical Starter), 160.54-PW5 (YORK Solid State
Starter), 160.54-PW6 (YORK Variable Speed Drive).
For those chillers equipped with “P” code compres-
sors, refer to the following Product Drawings; 160.54-
PW11 (Electro-Mechanical Starter), 160.54-PW12
(YORK Solid State Starter), 160.54-PW13 (YORK
Variable Speed Drive).

The chilled water flow switch is a safety control. It
must be connected to prevent operation of the chiller
whenever chilled water flow is stopped. The use of
the chilled water flow switch for purposes other than
protection of the chiller may be accomplished in sev-
eral ways. Two flow switches, a flow switch and a
relay or separate contacts on the same flow switch.

14.

15. Do not apply voltage on field wiring terminal blocks

TB4 and TB6 in YORK OptiView Control Center, as
115VAC source is fed from terminals 1 and 2 .

1. This drawing shows recommended field control wir-

ing modifications (by others) to the standard OptiView
Control Center Wiring Diagram. For those chillers that
are not equipped with “P” code compressors, refer to
the following Product Drawings: 160.54-PW4 (Electro-
Mechanical Starter), 160.54-PW5 (YORK Solid State
Starter), 160.54-PW6 (YORK Variable Speed Drive).
For those chillers equipped with “P” code compres-
sors, refer to the following Product Drawings; 160.54-
PW11 (Electro-Mechanical Starter), 160.54-PW12
(YORK Solid State Starter), 160.54-PW13 (YORK
Variable Speed Drive).

2. If more than one of these modifications is to be uti-

lized with a particular unit, additional consideration
must be given to the application to insure proper
functioning of the control system. Consult your
YORK representative.

3. The additional controls and wiring for these modifi-

cations are to be furnished and installed in the field
(by others). (See Warning on page 2.)

4. The controls specified are recommended for use, but

other controls of equal specifications are acceptable.

5. All wiring shall be in accordance with the National

Electrical Code, and applicable State and Local
Codes.

6. Each 115VAC field connected inductive load, i.e. re-

lay coil, motor starter coil, etc., shall have a tran-
sient suppressor wired (by others) in parallel with
its coil, physically located at the coil. Spare transient
suppressors are furnished in a bag in the OptiView
Control Center.

7. The OptiView Control Center is factory furnished

for Manual Restart After Power Failure as a stan-
dard function. The control center can be field changed
from Manual restart to Auto Restart after a power
failure by setting position 5 of Dip Switch SW1 to
the ON position - See Fig. 21.

8. Two (2) unit controls schemes are suitable for 8° –

12°F water range. Constant chilled water flow is
assumed at all loads. For other requirements contact
your YORK representative.

9.

NOTES

Summary of Contents for MILLENNIUM YK

Page 1: ...s provisions for remote control inputs and provisions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contact...

Page 2: ...ll load amperes for 1 to 255 minutes following each compressor start For more details refer to OptiView Control Center Instructions Form 160 54 O1 6 Controlling the maximum allowable compressor motor...

Page 3: ...U L or C S A Approved Units Only 8 Fig 14A Electro Mechanical Starter Manual Reset Overloads P Compressors Only 2300 to 4160 Volts U L or C S A Approved Units Only 8 Fig 15 Remote Current Limit Setpo...

Page 4: ...ion so they will allow the unit to start 4 The OptiView Control Center COMPRESSOR switch is in the RUN l position 5 The 30 minute anti recycle timer has timed out A closure of the Remote Mode Ready to...

Page 5: ...f Range FIG 5 ANTICIPATORY ALARM CONTACTS LD04604 FIG 6 REMOTE START AND STOP CONTACTS FROM ENERGY MANAGEMENT SYSTEM When the OptiView Control Center is in the Digital Analog or ISN remote operating m...

Page 6: ...lowing messages CYCLING SHUTDOWN AUTO RESTART and SYSTEM CYCLING CONTACTS OPEN The OptiView Control Center con tains a seven day time clock to select daily schedule Start Stop times Sun day through Sa...

Page 7: ...TWO UNIT SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag un...

Page 8: ...LE UNITS TWO PARALLEL OPERATION SINGLE CHILLED WATER PUMP For this piping arrangement each chiller s water sensor is located in its own leaving water nozzle This produces a constant mixed chilled wate...

Page 9: ...lts and Microboard Program Jumper JP23 has been removed Calculate the setpoint for various inputs as follows SETPOINT 100 VDC X 7 For example if the input is 5VDC the setpoint would be set to 65 as fo...

Page 10: ...dulation input is in the form of a 1 to 11 second relay contact closure that applies 115VAC to the I O Board TB4 20 for 1 to 11 seconds As shown in Fig 17 connect dry closure relay contacts between I...

Page 11: ...SET F VDC 2 REMOTE RESET TEMP RANGE 8 SETPOINT F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 40 F the setpoint would be set to 43...

Page 12: ...e set to 44 F as follows SIGNAL COMMON 5 4 J22 FIG 19 REMOTE LEAVING CHILLED LIQUID TEMP SETPOINT WITH 0 20MA OR 4 20MA SIGNAL LD04501 OFFSET F 8 10 20 80 20 4 F SETPOINT F 40 4 44 F 4 20mA As shown i...

Page 13: ...J11 1 JP27 1 SHLD GND _ 5V J11 SHLD GND _ 5V J11 SHLD GND _ 5V J12 SHLD GND _ 5V MICROBOARD 031 01730 1 PC 104 2 1 J17 J16 FIG 21 MICROBOARD DIP SWITCH FOR AUTO MANUAL RESTART AFTER POWER FAILURE LD04...

Page 14: ...er square inch psia For Metric Units temperature is in degrees Celsius C and pressure in KiloPascals kPa _ _ On Solid State Starter units only when the Current Imbalance option is selected via the Sol...

Page 15: ...un Light The control relay scheme shown in Fig 23 can also be applied for a remote Run Light AND a Remote Shutdown Indicator when an EMS is not used When Evaporator Water is flowing the flow switch co...

Page 16: ...e accomplished in sev eral ways Two flow switches a flow switch and a relay or separate contacts on the same flow switch 14 15 Do not apply voltage on field wiring terminal blocks TB4 and TB6 in YORK...

Reviews: