OPERATIONAL LIMITATIONS
(English)
LD03801
FIG. 2A – COOLER WATER PRESSURE DROP, TOTAL (ENGLISH)
VOLTAGE LIMITATIONS
The following voltage limitations are ab-
solute and operation beyond these limita-
tions may cause serious damage to the
compressor.
TEMPERATURES AND FLOWS
410 490 TONS
MODEL
LEAVING WATER
COOLER FLOW
AIR ON
NUMBER
TEMPERATURE (°F)
(GPM)
3
CONDENSER (°F)
YCAS & YDAS
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX.
4
410
40
52
500
5
1606
5
0
130
440
40
52
500
5
1606
5
0
130
470
40
52
500
5
1606
5
0
130
490
40
52
500
5
1606
5
0
130
NOTES:
1. For leaving brine temperature below 40°F, contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 52°F, contact your nearest YORK office for application guidelines.
3. The evaporator is protected against freeze-up to -20°F with an electrical heater as standard.
4. Operation above 115°F requires the Optional High Ambient Kit.
5. YDAS Units have two coolers in parallel.
VOLTAGES
UNIT POWER
MIN.
MAX.
200-3-60
180
220
230-3-60
207
253
460-3-60
414
506
575-3-60
517
633
MODEL YDAS
COOLER CODE
410, 440, 470, 490
4