FORM 201.10-NM4
95
YORK INTERNATIONAL
4.5 HISTORY KEY
If a safety shutdown occurs on the chiller, a comprehen-
sive list of operating and programmed settings data is
stored by the Microprocessor. The information is stored
at the instant of the fault, regardless of whether the fault
caused a lockout to occur. This information is not affected
by power failures or manual resetting of a fault lockout.
The Microprocessor stores data for up to three safety shut-
downs (up to nine on YCAS 2 system units). Once this
limit is reached, a further shutdown will cause the oldest
set of data to be discarded in favor of storing the new
shutdown data. The safety shutdowns are numbered from
1-9 with number 1 always being the most recent.
If a remote printer is not connected, pressing the His-
tory key allows the operator to locally scroll through in-
formation relating to the stored safety shutdowns on
the 40 character display.
If a remote printer is connected, pressing the History
key will cause data for the last three shutdowns to be
transmitted from the Microprocessor to the remote
printer. The printout will begin with the most recent fault
which occurred. This does not affect the stored data
and as many prints as desired may be taken. See Sec-
tion 4.7 for a HISTORY printout sample.
Samples of local display information for YCAS 2 sys-
tem, YCAS 3 system and YDAS models are as follows:
4.6
FAULT HISTORY DATA
LOCAL DISPLAY MESSAGES
YCAS 2 SYSTEM MODELS:
When the History key is pressed, the following mes-
sage will appear:
To select a Safety Shutdown, press the appropriate key
on the numeric key pad, then press Enter. Remember
that the most recent fault information is stored as shut-
down No. 1.
Repetitively pressing the Enter key now scrolls through
the information available in the Safety Shutdown buffer.
This is divided into Common (whole chiller) Data and
Individual System Data displays as follows:
Common Data:
This message advises the time and date of the fault.
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
RUN TIME
0- 0-26-11 D-H-M-S
AVERAGE MTR
65 %FLA
PHASE L1 MTR
65 %FLA
PHASE L2 MTR
65 %FLA
PHASE L3 MTR
65 %FLA
DIFF OIL PRESSURE
4 PSID
SUCTION PRESSURE
70 PSIG
SATURATED SUCTION
41.0 DEGF
SUCTION TEMP
48.0 DEGF
SUPERHEAT
7.0 DEGF
DISCHARGE PRESSURE
211 PSIG
SATURATED DISCHARGE
104.4 DEGF
DISCHARGE TEMP
131.8 DEGF
OIL TEMP
85.2 DEGF
LIQUID INJECTION VALVE
OFF
FORWARD FANS
2
REVERSE FANS
OFF
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
SYSTEM 3 DATA
COMPRESSOR STATUS
ON
RUN TIME
0- 0-18-11 D-H-M-S
AVERAGE MTR
64 %FLA
PHASE L1 MTR
65 %FLA
PHASE L2 MTR
63 %FLA
PHASE L3 MTR
64 %FLA
DIFF OIL PRESSURE
7 PSID
SUCTION PRESSURE
72 PSIG
SATURATED SUCTION
42.7 DEGF
SUCTION TEMP
49.0 DEGF
SUPERHEAT
6.3 DEGF
DISCHARGE PRESSURE
214 PSIG
SATURATED DISCHARGE
107.4 DEGF
DISCHARGE TEMP
128.8 DEGF
OIL TEMP
129.2 DEGF
LIQUID INJECTION VALVE
OFF
FORWARD FANS
2
REVERSE FANS
OFF
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
S M T W T F S
* = HOLIDAY
SUN
START=00:00AM
STOP=00:00AM
MON
START=00:00AM
STOP=00:00AM
TUE
START=00:00AM
STOP=00:00AM
WED
START=00:00AM
STOP=00:00AM
THU
START=00:00AM
STOP=00:00AM
FRI
START=00:00AM
STOP=00:00AM
SAT
START=00:00AM
STOP=00:00AM
HOL
START=00:00AM
STOP=00:00AM
D I S P L A Y
S A F E T Y
S H U T -
D O W N
N O . 1
( 1
T O
9 )
S H U T D O W N
O C C U R R E D
5 : 5 9
A M
0 1
0 1
9 8