FORM 201.10-NM4
43
YORK INTERNATIONAL
ELEMENTARY DIAGRAM
FIG. 22
YDAS 410 - 490 (SYSTEMS 1 & 2) ELEMENTARY DIAGRAM WYE-DELTA START (CONTD)
CAUTION:
No Controls (relays, etc.)
should be mounted in the
Smart Panel enclosure or
connected to power supplies
in the control panel. Addition-
ally, control wiring not con-
nected to the Smart Panel
should not be run through the
cabinet. This could result in
nuisance faults.
CAUTION:
Any inductive devices (relays)
wired in series with the flow
switch for start/stop, into the
Alarm circuitry, or pilot relays
for pump star ters wired
through motor contactor aux-
iliary contacts must be sup-
pressed with YORK
P/N 031-00808-000 suppres-
sor across the relay/contactor
coil which activates the con-
tacts.
Any contacts connected to
flow switch inputs or BAS in-
puts on terminals 13 - 19 or
TB3, or any other terminals,
must be suppressed with a
YORK P/N 031-00808-000
suppressor across the relay/
contactor coil which activates
the contacts.
CAUTION:
Control wiring connected to
the control panel should never
be run in the same conduit
with power wiring.
MAX
NON-
CONTROL
MIN
DUAL
FUSED
UNIT
POWER
CIRCUIT ELEMENT
DISC.
VOLTAGE
SUPPLY
AMP.
FUSE
SWITCH
SIZE
SIZE
ALL MODELS
115-1-50/60
20A
20A 250V
30A 240V
W/O TRANS.
MODELS
-17
200-1-60
15A
15A 250V
30A 240V
WITH
-28
230-1-60
15A
15A 250V
30A 240V
TRANS.
-46
400-1-60
8A
8A 600V
30A 480V
*
-58
575-1-60
8A
8A 600V
30A 600V
* All primary and secondary wiring between transformer and control panel included.
CONTROL POWER SUPPLY
LD02048