FORM 201.10-NM4
129
YORK INTERNATIONAL
PROBLEM
CAUSE
SOLUTION
“MOTOR CURRENT”
CONTACTOR DOES
FAULT
NOT ENERGIZE
Motor contactor may not
1. External high pressure
1. Check mechanical high
energize.
switch tripped.
pressure cut out, fan
operation, and discharge
stored in memory.
Forward running fans will
have air flow upward.
2. External motor
2. Check for defective
protector tripped.
motor protector, wiring,
and motor problems.
Assure the motor protector
is not tripped due to a
tripped mechanical high
pressure switch.
3. Defective Relay Output
3. Relay Output Board
Board
defective.
CONTACTOR ENERGIZES
1. Improper system high
1. Check system high
high voltage.
voltage supply.
2. Defective contactor
2. Check contactor and
contacts or contactor.
and contact.
3. Faulty high voltage wiring.
3. Check wiring.
4. High motor current stored
4. Loose J10 (SYS 1) or
in memory.
J11 (SYS 2) calibration
resistors on Power
Board.
5. Defective current
5. C.T. resistance =
transformer (C.T.)
42 - 44 ohms.