FORM 160.54-M1(503)
97
YORK INTERNATIONAL
OIL HEATER OPERATION
On chillers equipped with the oil pump VSD, the oil
heat er is controlled by the Microboard via I/O Board
The connection to the I/O Board is determined by the
chiller style and compressor type as follows:
•
TB1-34 - Style D and E chillers with “G”, “H” or
“J” compressors
•
TB1-64 - Style E chillers with “P” compressors and
all Style F and later chillers.
When the oil pump is not operating, the heater is turned
on and off to maintain a target value of 50ºF above the
Condenser Saturation Temperature. If the calculated tar-
get value is > 160ºF, the target value de faults to 160ºF.
If the calculated target value is < 110ºF, it defaults to
110ºF. When the temperature de creas es to 4ºF below
the target value, the heater is turned on; it is turned off
at 3ºF above the target.
To prevent overheating the oil in the event of an
OptiView Control Center failure, thermostat 1HTR
opens at 180ºF.
FIG. 53 –
OIL PUMP VARIABLE SPEED DRIVE (VSD)
28782A
OIL PUMP VSD
15
Summary of Contents for MAXE OPTIVIEW YK
Page 28: ...YORK INTERNATIONAL 28 FORM 160 54 M1 503 Microboard FIG 7 MICROBOARD LD07776...
Page 60: ...YORK INTERNATIONAL 60 FORM 160 54 M1 503 Keypad FIG 32 KEYPAD CONNECTOR LD04074...
Page 61: ...FORM 160 54 M1 503 61 YORK INTERNATIONAL FIG 33 KEYPAD LD04075 LD04076 8...
Page 173: ...FORM 160 54 M1 503 173 YORK INTERNATIONAL 26 This page intentionally left blank...
Page 177: ...FORM 160 54 M1 503 177 YORK INTERNATIONAL 26 This page intentionally left blank...