![York MAXE OPTIVIEW YK Service Instructions Manual Download Page 86](http://html1.mh-extra.com/html/york/maxe-optiview-yk/maxe-optiview-yk_service-instructions-manual_3688009086.webp)
YORK INTERNATIONAL
86
FORM 160.54-M1(503)
FIG. 46 –
PROXIMITY PROBE - INTERFACE PROBE
PART NUMBER 025-XXXXX-000 (FUTURE)
LD05531
+24VDC
POWER
SUPPLY
NOTE 2
JX
2
MICRO
BOARD
+24VDC
NOTE 1
2
1
J1
J9
J8
12
2
1
15
12
PROXIMITY / TEMP PROBE
+5VDC (DRAIN LINE TEMP)
GND
DRAIN TEMP
PROXIMITY
GND
+5VDC
+24VDC
J31
P31
1
2
1
2
NOTES:
1. +24VDC Reference for “Proximity Probe - Low Supply Voltage” Cycling Shutdown.
2. CM-2 Board, Solid State Starter Logic Board or Adaptive Capacity Control Board as determined by the Starter Application.
LD04090
FIG. 45 –
PROXIMITY PROBE - INTERFACE PROBE PART NUM BER 025-30961-000
PROXIMITY
PROBE
+5VDC
GND
+12VDC (PROXIMITY)
PROXIMITY
MICRO
BOARD
+12VDC
GND
+5VDC
POWER
SUPPLY
7
3
2
1
12
12
2
4
15
+12VDC REFERENCE FOR "PROXIMITY PROBE - LOW SUPPLY
VOLTAGE" CYCLING SHUTDOWN
J8
J9
J1
Proximity Probe
Summary of Contents for MAXE OPTIVIEW YK
Page 28: ...YORK INTERNATIONAL 28 FORM 160 54 M1 503 Microboard FIG 7 MICROBOARD LD07776...
Page 60: ...YORK INTERNATIONAL 60 FORM 160 54 M1 503 Keypad FIG 32 KEYPAD CONNECTOR LD04074...
Page 61: ...FORM 160 54 M1 503 61 YORK INTERNATIONAL FIG 33 KEYPAD LD04075 LD04076 8...
Page 173: ...FORM 160 54 M1 503 173 YORK INTERNATIONAL 26 This page intentionally left blank...
Page 177: ...FORM 160 54 M1 503 177 YORK INTERNATIONAL 26 This page intentionally left blank...