514067-UAD-A-0509

6

Johnson Controls Unitary Products

TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)

Read/

Write

BACnet 

Object 

Type

BACnet 

Object 

Inst

 

Descriptor

Default

Min

Max

Point Description

R

(5) BV

44

E_HPS1

Elite High Pressure Switch for Compressor 
#1 Input Status (1=closed, 0=open/fault)

R

(5) BV

48

E_HPS2

Elite High Pressure Switch for Compressor 
#2 Input Status (1=closed, 0=open/fault)

R

(5) BV

53

E_HPS3

Elite High Pressure Switch for Compressor 
#3 Input Status (1=closed, 0=open/fault)

R

(5) BV

57

E_HPS4

Elite High Pressure Switch for Compressor 
#4 Input Status (1=closed, 0=open/fault)

R

(5) BV

40

E_IFAN_STAT

Elite Indoor Fan Output Status (0=output is 
OFF, 1=output is ON)

R

(5) BV

61

E_LIMIT_ 1

Elite Limit Switch #1 Input Status (1=closed, 
0=open/fault)

R

(5) BV

63

E_LIMIT_ 2

Elite Limit Switch #2 Input Status (1=closed, 
0=open/fault)

R

(5) BV

65

E_LIMIT_ 3

Elite Limit Switch #3 Input Status (1=closed, 
0=open/fault)

R

(5) BV

43

E_LPS1

Elite Low Pressure Switch for Compressor 
#1 Input Status (1=closed, 0=open/fault)

R

(5) BV

47

E_LPS2

Elite Low Pressure Switch for Compressor 
#2 Input Status (1=closed, 0=open/fault)

R

(5) BV

52

E_LPS3

Elite Low Pressure Switch for Compressor 
#3 Input Status (1=closed, 0=open/fault)

R

(5) BV

56

E_LPS4

Elite Low Pressure Switch for Compressor 
#4 Input Status (1=closed, 0=open/fault)

R

(2) AV

32

EXH_DAMP_OUT

Exhaust Damper Output Status (0-100%)

R

(5) BV

30

EX_FAN_STAT

Exhaust Fan Output Status (0=output is 
OFF, 1=output is ON)

R

(5) BV

10

EX_VFD_INST

Exhaust VFD Installed

R

(5) BV

32

FRECOOL_STAT

Free Cooling Mode Status (0=comps not 
overridden by Econo, 1=comps overridden)

R

(5) BV

68

HEAT_1_STAT

H1 Heating Output #1 Status (0=output is 
OFF, 1=output is ON)

R

(5) BV

69

HEAT_2_STAT

H2 Heating Output #2 Status (0=output is 
OFF, 1=output is ON)

R

(5) BV

70

HEAT_3_STAT

H3 Heating Output #3 Status (0=output is 
OFF, 1=output is ON)

R

(2) AV

76

H1_ACCUM_HRS

Heating #1 Accumulated Run Time 
(in hours)

R

(2) AV

77

H2_ACCUM_HRS

Heating #2 Accumulated Run Time 
(in hours)

R

(2) AV

78

H3_ACCUM_HRS

Heating #3 Accumulated Run Time 
(in hours)

R

(5) BV

25

HEATING_ENA

Heating Mode Enabled

R/W

(2) AV

27

HGR_HUM_STPT

50

0

100

Hot Gas Reheat Humidity Setpoint (percent 
Humidity)

R

(5) BV

18

HGR_STAT

Hot Gas Reheat Output Status (0=output is 
OFF, 1=output is ON)

R

(2) AV

47

HGR_VLV_OUT

Hot Gas Reheat Valve Output Status 
(0-100%)

Summary of Contents for LINC GATEWAY 514067-UAD-A-0509

Page 1: ...lli Comfort controllers The Simplicity LINC mounts inside the control panel of the UP unit and utilizes 24 VAC power from the unit s control transformer One port is connected to the UP controller The...

Page 2: ...is completed at the factory No further adjustment should be done If a problem arises with the Simplicity LINC or a parameter not exposed by the Simplicity LINC requires modification the UP controller...

Page 3: ...tion problems between the Simplicity LINC and the UP controller BI 84 MODBUS_ALARM is used to indicate Modbus communication problems between the Simplicity LINC Gateway and the UP controller When on t...

Page 4: ...essure Setpoint R W 2 AV 25 COM_V_LOW_SP 70 60 85 Comfort Ventilation LowerSetpoint degrees F R 5 BV 34 CVM_COOLING Comfort Ventilation Mode for Cooling Enabled R 5 BV 35 CVM_HEATING Comfort Ventilati...

Page 5: ...ult R 2 AV 42 E_C2_ACM_HRS Elite Compressor 2 Accumulated Run Time in hours R 5 BV 46 E_COMP2_STAT Elite Compressor 2 Output Status 0 out put is OFF 1 output is ON R 5 BV 49 E_C2_OVRLOAD Elite Compres...

Page 6: ...Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BV 52 E_LPS3 Elite Low Pressure Switch for Compressor 3 Input Status 1 closed 0 open fault R 5 BV 56 E_LPS4 Elite Low Pressure Switch fo...

Page 7: ...put is OFF 1 output is ON R 5 BV 79 I_CFAN_STAT Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5 BV 72 I_FAN_OVER Intelli Comfort Fan Overload Switch Input Status 0 open...

Page 8: ...or Communication Input Enabled R 2 AV 17 OP_COOL_STPT Operating Cooling Setpoint R 2 AV 49 OP_HEAT_STPT 68 45 99 Operating Heating Setpoint R W 2 AV 69 OP_STPT_DIF 1 1 5 Operating Setpoint Differenti...

Page 9: ...2 SAT_HEAT_SP 135 100 180 Supply Air Temperature Limit for Heating Setpoint degrees F R 2 AV 34 SFAN_VFD_OUT Supply Fan VFD Output Status 0 100 R 2 AV 36 ALARM_1 System Alarm 1 R 2 AV 37 ALARM_2 Syste...

Page 10: ...DEMVENT_STPT 1000 0 5000 Demand Ventilation Setpoint R W 2 AV 19 ECON_MIN_POS 20 0 100 Economizer Minimum Position R W 2 AV 20 ECO_1ST_STPT 55 40 65 Economizer First Stage Setpoint R W 2 AV 21 ECO_2N...

Page 11: ...0 Supply Air Temperature Limit for Heating Setpoint degrees F R W 2 AV 53 SAT_ALM_HEAT 0 0 120 Supply Air Temperature Alarm Setpoint for Heating R W 2 AV 54 OAT_HEAT_L_O 75 0 100 Outdoor Air Temperatu...

Page 12: ...n Setpoint R W 2 AV 81 POP_HOURS 4 0 23 Pre Occupancy Purge Time hours R W 2 AV 82 POP_MINUTES 0 0 59 Pre Occupancy Purge Time minutes R W 2 AV 84 ECON_RAEN_SP 27 10 50 Economizer Return Air Enthalpy...

Page 13: ...OOL_STAT Free Cooling Mode Status 0 comps not overridden by Econo 1 comps overridden R 5 BV 33 COM_VENT_STA Comfort Ventilation Mode Status 1 control is in Comfort Vent mode 0 it is not R 5 BV 34 CVM_...

Page 14: ...ressure Switch for Compressor 4 Input Status 1 closed 0 open fault R 5 BV 57 E_HPS4 Elite High Pressure Switch for Compressor 4 Input Status 1 closed 0 open fault R 5 BV 58 E_C4_OVRLOAD Elite Compress...

Page 15: ...8 I_HPS2 Intelli Comfort High Pressure Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BV 79 I_CFAN_STAT Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5...

Page 16: ...may also indicate incorrect polling parameters such as baud rate or parity If the TX and or RX LEDs do not flash it may represent a problem with the field wiring or confguration problems in the field...

Page 17: ...514067 UAD A 0509 Johnson Controls Unitary Products 17 FIGURE 3 SIMPLICITY LINC GATEWAY LED LOCATION PWR RS485 PWR BACnet GP105 BACnet LB BACnet RX RS485 TX RS485 LA BACnet TX BACnet RX BACnet...

Page 18: ...t to change without notice Printed in U S A 514067 UAD A 0509 Copyright 2009 by Johnson Controls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK...

Reviews: