background image

514067-UAD-A-0509

16

Johnson Controls Unitary Products

TROUBLESHOOTING

The 

Simplicity

®

LINC Gateway consists of two printed circuit 

boards.

TABLE 4:

SIMPLICITY

®

LINC GATEWAY

RS485 BOARD (Bottom)

BacNET Board (Top)

Normal Board Operation

Normal Board Operation

The PWR LED should be on during operation. The RX and TX 
LEDs should flash when a signal is either received or sent.

LEDs LA and LB flash about once per second. LED GP105 will 
remain on within 45-60 seconds after power up, signifying normal 
operation. The PWR LED should be on during operation. The RX 
and TX LEDs should flash when a signal is either received or 
sent.

Faulty Board Operation

Faulty Board Operation

If the PWR LED does not come on but the RX and TX flash, then 
the PWR LED is broken.

If the PWR LED does not come on but the RX and TX flash, then 
the PWR LED is broken.

If the TX and / or RX LEDs do not flash, it may represent a problem 
with the field wiring or configuration problems in the field side of 
the BacNET board. It may also indicate incorrect polling 
parameters such as baud rate or parity.

If the TX and / or RX LEDs do not flash, it may represent a 
problem with the field wiring or confguration problems in the field 
side  of the BacNet board. It may also indicate incorrect polling 
parameters such as baud rate or parity.

If the PWR LED does not come on and LA and LB do not flash, 
call UP Tech Services at 1-877-874-7378.

If GP105 never comes on, call UP Tech Services at
1-877-874-7378.

General

Power Source

24 ± 15% VAC (Obtained from the Roof Top Unit)

Frequency

45 to 65 HZ

Power Consumption

Nominal >2 VA

Operating Environment

-40 to 160° F (-40 to 70° C) 10 to 95% non-condensing

Size (H x W x D)

5.0 x 2.4 x 1.8 in. (128 x 61 x 45.75 cm)

Weight

0.2 lb. (0.09 kg)

Processor

Type

Microchip

SDRAM Memory

2048 bytes

FLASH Memory

1024 bytes w/1,000,000 write cycle capability

Interface

Port 1 Type

BACnet MS/TP

Port 1 Speeds

9.6, 19.2, 38.4, 76.8 kbaud

Port 1 Connector

3-pin screw terminals

Port 2 Type

Modbus RTU (RS485)

Port 2 Speeds

9.6, 19,2 kbaud

Port 2 Connector

6-pin screw terminals

LAN Cable

Screened Twisted-Pair (Belden 9272 or 89272)

LEDs

Controller Status; BACnet; Modbus

Switch Selections

MAC Address (1-99), Baud Rate

Summary of Contents for LINC GATEWAY 514067-UAD-A-0509

Page 1: ...lli Comfort controllers The Simplicity LINC mounts inside the control panel of the UP unit and utilizes 24 VAC power from the unit s control transformer One port is connected to the UP controller The...

Page 2: ...is completed at the factory No further adjustment should be done If a problem arises with the Simplicity LINC or a parameter not exposed by the Simplicity LINC requires modification the UP controller...

Page 3: ...tion problems between the Simplicity LINC and the UP controller BI 84 MODBUS_ALARM is used to indicate Modbus communication problems between the Simplicity LINC Gateway and the UP controller When on t...

Page 4: ...essure Setpoint R W 2 AV 25 COM_V_LOW_SP 70 60 85 Comfort Ventilation LowerSetpoint degrees F R 5 BV 34 CVM_COOLING Comfort Ventilation Mode for Cooling Enabled R 5 BV 35 CVM_HEATING Comfort Ventilati...

Page 5: ...ult R 2 AV 42 E_C2_ACM_HRS Elite Compressor 2 Accumulated Run Time in hours R 5 BV 46 E_COMP2_STAT Elite Compressor 2 Output Status 0 out put is OFF 1 output is ON R 5 BV 49 E_C2_OVRLOAD Elite Compres...

Page 6: ...Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BV 52 E_LPS3 Elite Low Pressure Switch for Compressor 3 Input Status 1 closed 0 open fault R 5 BV 56 E_LPS4 Elite Low Pressure Switch fo...

Page 7: ...put is OFF 1 output is ON R 5 BV 79 I_CFAN_STAT Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5 BV 72 I_FAN_OVER Intelli Comfort Fan Overload Switch Input Status 0 open...

Page 8: ...or Communication Input Enabled R 2 AV 17 OP_COOL_STPT Operating Cooling Setpoint R 2 AV 49 OP_HEAT_STPT 68 45 99 Operating Heating Setpoint R W 2 AV 69 OP_STPT_DIF 1 1 5 Operating Setpoint Differenti...

Page 9: ...2 SAT_HEAT_SP 135 100 180 Supply Air Temperature Limit for Heating Setpoint degrees F R 2 AV 34 SFAN_VFD_OUT Supply Fan VFD Output Status 0 100 R 2 AV 36 ALARM_1 System Alarm 1 R 2 AV 37 ALARM_2 Syste...

Page 10: ...DEMVENT_STPT 1000 0 5000 Demand Ventilation Setpoint R W 2 AV 19 ECON_MIN_POS 20 0 100 Economizer Minimum Position R W 2 AV 20 ECO_1ST_STPT 55 40 65 Economizer First Stage Setpoint R W 2 AV 21 ECO_2N...

Page 11: ...0 Supply Air Temperature Limit for Heating Setpoint degrees F R W 2 AV 53 SAT_ALM_HEAT 0 0 120 Supply Air Temperature Alarm Setpoint for Heating R W 2 AV 54 OAT_HEAT_L_O 75 0 100 Outdoor Air Temperatu...

Page 12: ...n Setpoint R W 2 AV 81 POP_HOURS 4 0 23 Pre Occupancy Purge Time hours R W 2 AV 82 POP_MINUTES 0 0 59 Pre Occupancy Purge Time minutes R W 2 AV 84 ECON_RAEN_SP 27 10 50 Economizer Return Air Enthalpy...

Page 13: ...OOL_STAT Free Cooling Mode Status 0 comps not overridden by Econo 1 comps overridden R 5 BV 33 COM_VENT_STA Comfort Ventilation Mode Status 1 control is in Comfort Vent mode 0 it is not R 5 BV 34 CVM_...

Page 14: ...ressure Switch for Compressor 4 Input Status 1 closed 0 open fault R 5 BV 57 E_HPS4 Elite High Pressure Switch for Compressor 4 Input Status 1 closed 0 open fault R 5 BV 58 E_C4_OVRLOAD Elite Compress...

Page 15: ...8 I_HPS2 Intelli Comfort High Pressure Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BV 79 I_CFAN_STAT Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5...

Page 16: ...may also indicate incorrect polling parameters such as baud rate or parity If the TX and or RX LEDs do not flash it may represent a problem with the field wiring or confguration problems in the field...

Page 17: ...514067 UAD A 0509 Johnson Controls Unitary Products 17 FIGURE 3 SIMPLICITY LINC GATEWAY LED LOCATION PWR RS485 PWR BACnet GP105 BACnet LB BACnet RX RS485 TX RS485 LA BACnet TX BACnet RX BACnet...

Page 18: ...t to change without notice Printed in U S A 514067 UAD A 0509 Copyright 2009 by Johnson Controls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK...

Reviews: