514067-UAD-A-0509
14
Johnson Controls Unitary Products
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor
Default
Min
Max
Point Description
R
(5) BV
47
E_LPS2
–
–
–
Elite Low Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R
(5) BV
48
E_HPS2
–
–
–
Elite High Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R
(5) BV
49
E_C2_OVRLOAD
–
–
–
Elite Compressor #2 Overload Switch Input
Status (1=closed, 0=open/fault)
R
(5) BV
50
E_CFAN1_STAT
–
–
–
Elite Condenser Fan #1 Output Status
(0=output is OFF, 1=output is ON)
R
(5) BV
51
E_COMP3_STAT
–
–
–
Elite Compressor #3 Output Status (0=output
is OFF, 1=output is ON)
R
(5) BV
52
E_LPS3
–
–
–
Elite Low Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R
(5) BV
53
E_HPS3
–
–
–
Elite High Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R
(5) BV
54
E_C3_OVRLOAD
–
–
–
Elite Compressor #3 Overload Switch Input
Status (1=closed, 0=open/fault)
R
(5) BV
55
E_COMP4_STAT
–
–
–
Elite Compressor #4 Output Status (0=output
is OFF, 1=output is ON)
R
(5) BV
56
E_LPS4
–
–
–
Elite Low Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R
(5) BV
57
E_HPS4
–
–
–
Elite High Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R
(5) BV
58
E_C4_OVRLOAD
–
–
–
Elite Compressor #4 Overload Switch Input
Status (1=closed, 0=open/fault)
R
(5) BV
59
E_CFAN2_STAT
–
–
–
Elite Condenser Fan #2 Output Status Input
Status (0=output is OFF, 1=output is ON)
R
(5) BV
60
E_GAS_VLVE1
–
–
–
Elite Gas Valve #1 Input Status
(1=energized, 0=not energized)
R
(5) BV
61
E_LIMIT_ 1
–
–
–
Elite Limit Switch #1 Input Status (1=closed,
0=open/fault)
R
(5) BV
62
E_GAS_VLVE2
–
–
–
Elite Gas Valve #2 Input Status
(1=energized, 0=not energized)
R
(5) BV
63
E_LIMIT_ 2
–
–
–
Elite Limit Switch #2 Input Status (1=closed,
0=open/fault)
R
(5) BV
64
E_GAS_VLVE3
–
–
–
Elite Gas Valve #3 Input Status
(1=energized, 0=not energized)
R
(5) BV
65
E_LIMIT_ 3
–
–
–
Elite Limit Switch #3 Input Status (1=closed,
0=open/fault)
R
(5) BV
66
E_FREEZE_ST
–
–
–
Hot H2O Freeze Thermostat Switch #1 Input
Status (1=closed, 0=open/fault)
R
(5) BV
67
FAN_HEAT
–
–
–
Turn OFF Continuous Fan when Starting
Heat Enabled (0=Continuous Fan ON)
R
(5) BV
68
HEAT_1_STAT
–
–
–
H1 Heating Output #1 Status (0=output is
OFF, 1=output is ON)
R
(5) BV
69
HEAT_2_STAT
–
–
–
H2 Heating Output #2 Status (0=output is
OFF, 1=output is ON)
R
(5) BV
70
HEAT_3_STAT
–
–
–
H3 Heating Output #3 Status (0=output is
OFF, 1=output is ON)