background image

514067-UAD-A-0509

12

Johnson Controls Unitary Products

TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)

Read/

Write

BACnet 

Object 

Type

BACnet 

Object 

Inst

 

Descriptor

Default

Min

Max

Point Description

R/W

(2) AV

69

OP_STPT_DIF

1

1

5

Operating Setpoint Differential

R/W

(2) AV

70

SAT_ALM_COOL

0

0

80

Supply Air Temperature Alarm Setpoint for 
Cooling

R/W

(2) AV

71

SPCE_ALM_TMP

0

0

25

Space Sensor Alarm Temperature 
(degrees F, 0 = disabled)

R/W

(2) AV

72

SPCE_ALM_TIM

0

0

120

Space Sensor Alarm Time (minutes F, 
0 = disabled)

R/W

(2) AV

73

SP_OFF_RANGE

3

0

5

Space Temprature Sensor Offset Range 
(0-5 degrees)

R/W

(2) AV

74

OAT_COOL_L_O

45

0

100

Outdoor Air Temperature Cooling Lockout 
Temperature

R/W

(2) AV

75

UNOC_OVR_TP

60

0

240

Unoccupied Override Time Period

R

(2) AV

76

H1_ACCUM_HRS

Heating #1 Accumulated Run Time (in hours)

R

(2) AV

77

H2_ACCUM_HRS

Heating #2 Accumulated Run Time (in hours)

R

(2) AV

78

H3_ACCUM_HRS

Heating #3 Accumulated Run Time (in hours)

R/W

(2) AV

79

OAQ_STPT

1000

0

5000

Air Quality Setpoint Outside

R/W

(2) AV

80

IO_DVNT_STPT

700

0

2000

Indoor/Outdoor Demand Ventilation Setpoint

R/W

(2) AV

81

POP_HOURS

4

0

23

Pre-Occupancy Purge Time (hours)

R/W

(2) AV

82

POP_MINUTES

0

0

59

Pre-Occupancy Purge Time (minutes)

R/W

(2) AV

84

ECON_RAEN_SP

27

10

50

Economizer Return Air Enthalpy Setpoint

R/W

(5) BV

1

OCCUPIED_ENA

Occupied Enabled

R

(5) BV

2

HYDRONC_HEAT

Hydronic Heat Enabled

R

(5) BV

3

HH_REVER_VLV

Hydronic Heat Reverse Actuated Valve 
Installed

R

(5) BV

4

REM_CONT_ENA

Remote Control Enabled

R

(5) BV

5

VAV_OCC_HEAT

VAV Occupied Heating Enabled 

R

(5) BV

6

MORN_WARM-UP

Morning Warm-Up Enabled

R

(5) BV

7

ECONO_INST

Economizer Installed

R

(5) BV

8

PWR_EX_INST

Power Exhaust Installed

R

(5) BV

9

MOD_EX_INST

Modulating Exhaust Installed

R

(5) BV

10

EX_VFD_INST

Exhaust VFD Installed

R

(5) BV

11

MODBUS_ALARM

Modbus Communication Alarm 

R/W

(5) BV

12

REDLINE

Redline (0=clear redline, 1=set redline 
operation)

R/W

(5) BV

13

LOADSHED

Loadshed (0=clear loadshed, 1=set loadshed 
operation)

R

(5) BV

14

LOW_SUP_VOLT

Low Supply Voltage (0=comps not 
overridden by LSV, 1=comps overridden)

R

(5) BV

15

DIRT_FILT_SW

Dirty Filter Switch Status (0=open,1=closed/
fault)

R

(5) BV

16

AIR_PROOF_SW

Air Proving Switch Status (1=closed, 
0=open/no air flow)

R

(5) BV

17

PURGE_SWITCH

Purge Switch Status (0=open,1=closed)

R

(5) BV

18

HGR_STAT

Hot Gas Reheat Output Status (0=output is 
OFF, 1=output is ON)

Summary of Contents for LINC GATEWAY 514067-UAD-A-0509

Page 1: ...lli Comfort controllers The Simplicity LINC mounts inside the control panel of the UP unit and utilizes 24 VAC power from the unit s control transformer One port is connected to the UP controller The...

Page 2: ...is completed at the factory No further adjustment should be done If a problem arises with the Simplicity LINC or a parameter not exposed by the Simplicity LINC requires modification the UP controller...

Page 3: ...tion problems between the Simplicity LINC and the UP controller BI 84 MODBUS_ALARM is used to indicate Modbus communication problems between the Simplicity LINC Gateway and the UP controller When on t...

Page 4: ...essure Setpoint R W 2 AV 25 COM_V_LOW_SP 70 60 85 Comfort Ventilation LowerSetpoint degrees F R 5 BV 34 CVM_COOLING Comfort Ventilation Mode for Cooling Enabled R 5 BV 35 CVM_HEATING Comfort Ventilati...

Page 5: ...ult R 2 AV 42 E_C2_ACM_HRS Elite Compressor 2 Accumulated Run Time in hours R 5 BV 46 E_COMP2_STAT Elite Compressor 2 Output Status 0 out put is OFF 1 output is ON R 5 BV 49 E_C2_OVRLOAD Elite Compres...

Page 6: ...Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BV 52 E_LPS3 Elite Low Pressure Switch for Compressor 3 Input Status 1 closed 0 open fault R 5 BV 56 E_LPS4 Elite Low Pressure Switch fo...

Page 7: ...put is OFF 1 output is ON R 5 BV 79 I_CFAN_STAT Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5 BV 72 I_FAN_OVER Intelli Comfort Fan Overload Switch Input Status 0 open...

Page 8: ...or Communication Input Enabled R 2 AV 17 OP_COOL_STPT Operating Cooling Setpoint R 2 AV 49 OP_HEAT_STPT 68 45 99 Operating Heating Setpoint R W 2 AV 69 OP_STPT_DIF 1 1 5 Operating Setpoint Differenti...

Page 9: ...2 SAT_HEAT_SP 135 100 180 Supply Air Temperature Limit for Heating Setpoint degrees F R 2 AV 34 SFAN_VFD_OUT Supply Fan VFD Output Status 0 100 R 2 AV 36 ALARM_1 System Alarm 1 R 2 AV 37 ALARM_2 Syste...

Page 10: ...DEMVENT_STPT 1000 0 5000 Demand Ventilation Setpoint R W 2 AV 19 ECON_MIN_POS 20 0 100 Economizer Minimum Position R W 2 AV 20 ECO_1ST_STPT 55 40 65 Economizer First Stage Setpoint R W 2 AV 21 ECO_2N...

Page 11: ...0 Supply Air Temperature Limit for Heating Setpoint degrees F R W 2 AV 53 SAT_ALM_HEAT 0 0 120 Supply Air Temperature Alarm Setpoint for Heating R W 2 AV 54 OAT_HEAT_L_O 75 0 100 Outdoor Air Temperatu...

Page 12: ...n Setpoint R W 2 AV 81 POP_HOURS 4 0 23 Pre Occupancy Purge Time hours R W 2 AV 82 POP_MINUTES 0 0 59 Pre Occupancy Purge Time minutes R W 2 AV 84 ECON_RAEN_SP 27 10 50 Economizer Return Air Enthalpy...

Page 13: ...OOL_STAT Free Cooling Mode Status 0 comps not overridden by Econo 1 comps overridden R 5 BV 33 COM_VENT_STA Comfort Ventilation Mode Status 1 control is in Comfort Vent mode 0 it is not R 5 BV 34 CVM_...

Page 14: ...ressure Switch for Compressor 4 Input Status 1 closed 0 open fault R 5 BV 57 E_HPS4 Elite High Pressure Switch for Compressor 4 Input Status 1 closed 0 open fault R 5 BV 58 E_C4_OVRLOAD Elite Compress...

Page 15: ...8 I_HPS2 Intelli Comfort High Pressure Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BV 79 I_CFAN_STAT Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5...

Page 16: ...may also indicate incorrect polling parameters such as baud rate or parity If the TX and or RX LEDs do not flash it may represent a problem with the field wiring or confguration problems in the field...

Page 17: ...514067 UAD A 0509 Johnson Controls Unitary Products 17 FIGURE 3 SIMPLICITY LINC GATEWAY LED LOCATION PWR RS485 PWR BACnet GP105 BACnet LB BACnet RX RS485 TX RS485 LA BACnet TX BACnet RX BACnet...

Page 18: ...t to change without notice Printed in U S A 514067 UAD A 0509 Copyright 2009 by Johnson Controls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK...

Reviews: