TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor
Default
Min
Max
Point Description
R
(5) BV
71
I_IFAN_STAT
–
–
–
Intelli-Comfort Indoor Fan Output Status
(0=output is OFF, 1=output is ON)
R
(5) BV
72
I_FAN_OVER
–
–
–
Intelli-Comfort Fan Overload Switch Input
Status (0=open,1=closed)
R
(5) BV
73
I_COMP1_STAT
–
–
–
Intelli-Comfort Compressor #1 Input Status
(0=output is OFF, 1=output is ON)
R
(5) BV
74
I_LPS1
–
–
–
Intelli-Comfort Low Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)
R
(5) BV
75
I_HPS1
–
–
–
Intelli-Comfort High Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)
R
(5) BV
76
I_COMP2_STAT
–
–
–
Intelli-Comfort Compressor #2 Input Status
(0=output is OFF, 1=output is ON)
R
(5) BV
77
I_LPS2
–
–
–
Intelli-Comfort Low Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)
R
(5) BV
78
I_HPS2
–
–
–
Intelli-Comfort High Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)
R
(5) BV
79
I_CFAN_STAT
–
–
–
Intelli-Comfort Condenser Fan #1 Input
Status (0=output is OFF, 1=output is ON)
R
(5) BV
80
I_GAS_VLVE1
–
–
–
Intelli-Comfort Gas Valve #1 Input Status
R
(5) BV
81
I_LIMIT_1
–
–
–
Intelli-Comfort Limit Switch #1 Input Status
R
(5) BV
82
I_FREEZE_1
–
–
–
Intelli-Comfort Freeze Thermostat Switch #1
Input Status (0=open,1=closed)
R
(5) BV
83
I_FREEZE_2
–
–
–
Intelli-Comfort Freeze Thermostat Switch #2
Input Status (0=open,1=closed)
R
(5) BV
85
ALARM_1_ON
–
–
–
Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)
R
(5) BV
86
ALARM_2_ON
–
–
–
Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)
R
(5) BV
87
ALARM_3_ON
–
–
–
Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)
R
(5) BV
88
ALARM_4_ON
–
–
–
Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)
R
(5) BV
89
ALARM_5_ON
–
–
–
Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)
R
(5) BV
90
DF_SW_INST
–
–
–
Dirty Filter Switch Installed
R
(5) BV
93
OCC_COMS_ENA
–
–
–
Occupied Thermostat or Communication
Input Enabled
R/W
(5) BV
96
MANUAL_WRITE
–
–
–
Manual Write Command to ModlINC