514067-UAD-A-0509
4
Johnson Controls Unitary Products
TABLE 2: POINTS LIST IN DESCRIPTION ORDER
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor
Default
Min
Max
Point Description
R
(2) AV
14
ACC_OVER_TME
–
–
–
Accumulated Unoccupied Override Time
(in hours)
R
(2) AV
15
ACTIVE_ALARM
–
–
–
Active Alarm
R
(5) BV
16
AIR_PROOF_SW
–
–
–
Air Proving Switch Status (1=closed,
0=open/no air flow)
R/W
(2) AV
79
OAQ_STPT
1000
0
5000
Air Quality Setpoint Outside
R
(5) BV
85
ALARM_1_ON
–
–
–
Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)
R
(5) BV
86
ALARM_2_ON
–
–
–
Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)
R
(5) BV
87
ALARM_3_ON
–
–
–
Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)
R
(5) BV
88
ALARM_4_ON
–
–
–
Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)
R
(5) BV
89
ALARM_5_ON
–
–
–
Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)
R
(2) AV
33
BLDG_STATIC
–
–
–
Building Static Pressure
R
(5) BV
29
BP_SENS_INST
–
–
–
Building Static Pressure Sensor Installed
R/W
(2) AV
57
BLDG_SP_STPT
0.1
-0.25
0.25
Building Static Pressure Setpoint
R/W
(2) AV
25
COM_V_LOW_SP
70
60
85
Comfort Ventilation LowerSetpoint
(degrees F)
R
(5) BV
34
CVM_COOLING
–
–
–
Comfort Ventilation Mode for Cooling
Enabled
R
(5) BV
35
CVM_HEATING
–
–
–
Comfort Ventilation Mode for Heating
Enabled
R
(5) BV
33
COM_VENT_STA
–
–
–
Comfort Ventilation Mode Status (1=control
is in Comfort Vent mode, 0= it is not)
R/W
(2) AV
24
COM_V_HI_SP
80
60
85
Comfort Ventilation Upper Setpoint
(degrees F)
R
(5) BV
23
COOLING_ENA
–
–
–
Cooling Mode Enabled
R
(5) BV
21
FAN_ON_W_SEN
–
–
–
CV - Indoor Fan Operates with Space
Sensor Present Option Enabled
R
(2) AV
56
CV_VAV_SELEC
–
–
–
CV/VAV Selected (0= Valid CV, 1=Valid
VAV, 2= Invalid Value)
R
(2) AV
8
IAQ_VALUE
–
–
–
Demand Ventilation (IAQ) Value (PPM)
R
(5) BV
39
DEMAND_VENT
–
–
–
Demand Ventilation (using Inside Sensor)
Enabled
R/W
(2) AV
18
DEMVENT_STPT
1000
0
5000
Demand Ventilation Setpoint
R
(2) AV
67
REVISION
–
–
xx
Device Revision
R
(5) BV
90
DF_SW_INST
–
–
–
Dirty Filter Switch Installed
R
(5) BV
15
DIRT_FILT_SW
–
–
–
Dirty Filter Switch Status (0=open,1=closed/
fault)
R
(2) AV
35
DUCT_STATIC
–
–
–
Duct Static Pressure
R/W
(2) AV
58
DUCT_SP_STPT
1.5
0
5
Duct Static Pressure Setpoint
R/W
(2) AV
59
DUCT_SD_STPT
4.5
0
5
Duct Static Pressure Shutdown Setpoint
R
(2) AV
31
ECO_DAMP_OUT
–
–
–
Economizer Damper Output Status
(0-100%)