CONNECTION

The 

Simplicity

®

LINC has 2 ports, one for connection to the BAS 

network (BACnet) and one to the 

Simplicity

®

 board (Modbus).

BACNET NETWORK

The only connection required in the field is to the BACnet (BAS) 
network.

NOTE: 

Proper termination and grounding of the shields must
be observed.

DIP switches A0-A7 on the 

Simplicity

®

LINC board allow 

selection of the MAC Address. The MAC Address identifies the 

Simplicity

®

LINC to other devices and must be between 1 and 

99. The default DIP switch setting is 1.

A Device Instance (DE) Modifier is used by the 

Simplicity

®

LINC 

and defaulted to 230. The combination of the DE Modifier and 
the default DIP switch setting creates a default DE of 23001. 
The default Unit Name is YORK_RTU.

FIGURE 2: MAC ADDRESS EXAMPLES

DIP switches B0-B3 on the 

Simplicity

®

LINC board allow for 

selection of the BACnet transfer speed.The default speed is set 
at 38.4k baud. Other speeds can be chosen as shown in Table 
1.

MODBUS CONNECTION

The UP device communicates with the 

Simplicity

®

LINC using 

the Modbus RTU protocol on an RS485 connection. Connection 
and addressing of the UP product is completed at the factory. 
No further adjustment should be done.

If a problem arises with the 

Simplicity

®

LINC or a parameter not 

exposed by the 

Simplicity

®

LINC requires modification, the UP 

controller software can be manipulated using a Microsoft

©

 

Windows-based PC with the 

Simplicity

®

 PC software 

(downloadable from the UP website). To connect the PC to the 
UP controller, a FREEnet USB adaptor (Part No. 
S103101967000), which is an RS232 to RS485 adapter, and 
FREEnet adapter cable (S102538682000) are required and 
available through SOURCE1 (Toll-free at 1-800-536-6112).

SOFTWARE SETUP

The control sequence is managed by the 

Simplicity

®

 controller. 

The data points on these systems are mapped to standard AV 
and BV BACnet Objects. As a preconfigured application, no 
configuration is necessary in the 

Simplicity

®

LINC Gateway.

MAC Address of 21 





16 



21 






32 
64 

99 

MAC Address of 99 




16 
32 
64 

128 

ON
 

1    2    3    4    5    6

    7    8

  




16 
32 
64 

128 

ON
 

1    2    3    4    5    6    7    8

  

A0 
A1 
A2 
A3 
A4 
A5 
A6 
A7 

A0 
A1 
A2 
A3 
A4 
A5 
A6 
A7 

TABLE 1: BAUD RATE SELECTION SETTINGS

DIP Setting

Baud Rate

1

110

2

300

3

600

4

1200

5

2400

6

4800

7

9600

8

19200

9

20833

10

28800

11

38400

12

57600

13

76800

14

115200

The default 

Simplicity

®

 board address is 1. Do not 

engage the Address button on the 

Simplicity

®

 board. 

This changes the address and causes a Modbus 
communication failure.

Summary of Contents for LINC GATEWAY 514067-UAD-A-0509

Page 1: ...lli Comfort controllers The Simplicity LINC mounts inside the control panel of the UP unit and utilizes 24 VAC power from the unit s control transformer One port is connected to the UP controller The...

Page 2: ...is completed at the factory No further adjustment should be done If a problem arises with the Simplicity LINC or a parameter not exposed by the Simplicity LINC requires modification the UP controller...

Page 3: ...tion problems between the Simplicity LINC and the UP controller BI 84 MODBUS_ALARM is used to indicate Modbus communication problems between the Simplicity LINC Gateway and the UP controller When on t...

Page 4: ...essure Setpoint R W 2 AV 25 COM_V_LOW_SP 70 60 85 Comfort Ventilation LowerSetpoint degrees F R 5 BV 34 CVM_COOLING Comfort Ventilation Mode for Cooling Enabled R 5 BV 35 CVM_HEATING Comfort Ventilati...

Page 5: ...ult R 2 AV 42 E_C2_ACM_HRS Elite Compressor 2 Accumulated Run Time in hours R 5 BV 46 E_COMP2_STAT Elite Compressor 2 Output Status 0 out put is OFF 1 output is ON R 5 BV 49 E_C2_OVRLOAD Elite Compres...

Page 6: ...Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BV 52 E_LPS3 Elite Low Pressure Switch for Compressor 3 Input Status 1 closed 0 open fault R 5 BV 56 E_LPS4 Elite Low Pressure Switch fo...

Page 7: ...put is OFF 1 output is ON R 5 BV 79 I_CFAN_STAT Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5 BV 72 I_FAN_OVER Intelli Comfort Fan Overload Switch Input Status 0 open...

Page 8: ...or Communication Input Enabled R 2 AV 17 OP_COOL_STPT Operating Cooling Setpoint R 2 AV 49 OP_HEAT_STPT 68 45 99 Operating Heating Setpoint R W 2 AV 69 OP_STPT_DIF 1 1 5 Operating Setpoint Differenti...

Page 9: ...2 SAT_HEAT_SP 135 100 180 Supply Air Temperature Limit for Heating Setpoint degrees F R 2 AV 34 SFAN_VFD_OUT Supply Fan VFD Output Status 0 100 R 2 AV 36 ALARM_1 System Alarm 1 R 2 AV 37 ALARM_2 Syste...

Page 10: ...DEMVENT_STPT 1000 0 5000 Demand Ventilation Setpoint R W 2 AV 19 ECON_MIN_POS 20 0 100 Economizer Minimum Position R W 2 AV 20 ECO_1ST_STPT 55 40 65 Economizer First Stage Setpoint R W 2 AV 21 ECO_2N...

Page 11: ...0 Supply Air Temperature Limit for Heating Setpoint degrees F R W 2 AV 53 SAT_ALM_HEAT 0 0 120 Supply Air Temperature Alarm Setpoint for Heating R W 2 AV 54 OAT_HEAT_L_O 75 0 100 Outdoor Air Temperatu...

Page 12: ...n Setpoint R W 2 AV 81 POP_HOURS 4 0 23 Pre Occupancy Purge Time hours R W 2 AV 82 POP_MINUTES 0 0 59 Pre Occupancy Purge Time minutes R W 2 AV 84 ECON_RAEN_SP 27 10 50 Economizer Return Air Enthalpy...

Page 13: ...OOL_STAT Free Cooling Mode Status 0 comps not overridden by Econo 1 comps overridden R 5 BV 33 COM_VENT_STA Comfort Ventilation Mode Status 1 control is in Comfort Vent mode 0 it is not R 5 BV 34 CVM_...

Page 14: ...ressure Switch for Compressor 4 Input Status 1 closed 0 open fault R 5 BV 57 E_HPS4 Elite High Pressure Switch for Compressor 4 Input Status 1 closed 0 open fault R 5 BV 58 E_C4_OVRLOAD Elite Compress...

Page 15: ...8 I_HPS2 Intelli Comfort High Pressure Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BV 79 I_CFAN_STAT Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5...

Page 16: ...may also indicate incorrect polling parameters such as baud rate or parity If the TX and or RX LEDs do not flash it may represent a problem with the field wiring or confguration problems in the field...

Page 17: ...514067 UAD A 0509 Johnson Controls Unitary Products 17 FIGURE 3 SIMPLICITY LINC GATEWAY LED LOCATION PWR RS485 PWR BACnet GP105 BACnet LB BACnet RX RS485 TX RS485 LA BACnet TX BACnet RX BACnet...

Page 18: ...t to change without notice Printed in U S A 514067 UAD A 0509 Copyright 2009 by Johnson Controls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK...

Reviews: