FORM 100.50-EG3 (802)
21
YORK INTERNATIONAL
TABLE 4 –
COOLING PERFORMANCE DATA* –
60 TON MODEL
(CONT’D)
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
208
165
206
143
205
126
205
110
204
94
–
–
23786
19
200
187
190
171
190
154
190
137
189
122
188
106
17
197
197
189
191
179
179
177
163
175
150
175
133
22
213
182
212
158
211
139
210
119
209
99
–
–
30582
19
210
208
198
188
197
172
197
152
195
133
194
114
17
211
211
202
205
193
197
185
183
180
166
181
147
22
217
195
217
168
216
148
214
125
213
103
–
–
35679
19
218
227
204
209
203
185
201
163
199
141
198
119
17
222
222
212
214
204
209
190
197
183
178
185
157
22
218
198
218
171
217
150
215
127
214
104
–
–
38228
19
220
229
206
217
204
189
202
166
200
144
199
121
17
224
224
214
217
206
212
192
200
184
181
186
159
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
199
160
197
138
195
121
194
106
192
91
–
–
23786
19
187
187
182
169
182
150
181
134
179
118
178
103
17
190
190
181
183
172
174
167
160
165
147
165
131
22
203
177
203
154
202
134
200
115
199
96
–
–
30582
19
200
206
190
187
188
168
188
149
186
130
185
110
17
204
204
192
194
186
190
179
182
173
162
173
144
22
206
190
207
166
206
143
205
121
204
100
–
–
35679
19
210
219
195
200
193
180
193
159
191
138
190
115
17
214
214
200
202
197
202
188
196
178
173
178
154
22
207
193
208
169
208
145
206
123
205
100
–
–
38228
19
213
222
197
204
194
184
194
162
192
140
191
117
17
216
216
202
204
199
205
190
199
179
176
180
156