YORK INTERNATIONAL
26
TABLE 7 –
COOLING PERFORMANCE DATA* –
75 TON MODEL
Cooling Performance Data –
75 Ton Model
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
35°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
29.4°C AIR ON CONDENSER COIL
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
244
183
233
159
233
141
232
123
230
104
–
–
27184
19
228
210
217
191
216
174
216
155
215
137
214
119
17
228
219
215
214
202
201
202
184
200
170
199
151
22
255
211
243
181
242
158
241
136
240
112
–
–
33980
19
244
237
231
220
227
198
226
174
224
153
223
131
17
248
238
234
237
217
224
216
209
211
193
209
170
22
259
224
247
191
245
166
244
141
243
116
–
–
37378
19
252
246
238
234
230
209
229
184
228
160
226
136
17
255
245
242
245
223
229
224
220
215
205
212
179
22
259
226
247
193
246
168
245
142
243
117
–
–
38228
19
254
247
239
237
231
212
230
186
228
161
227
136
17
256
246
243
246
224
230
225
222
216
207
213
180
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
235
183
233
159
233
141
232
123
230
104
–
–
27184
19
220
210
217
191
216
174
216
155
215
137
214
119
17
224
219
215
214
202
201
202
184
200
170
199
151
22
246
211
243
181
242
158
241
136
240
112
–
–
33980
19
236
237
231
220
227
198
226
174
224
153
223
131
17
243
238
234
237
217
224
216
209
211
193
209
170
22
250
224
247
191
245
166
244
141
243
116
–
–
37378
19
244
246
238
234
230
209
229
184
228
160
226
136
17
250
245
242
245
223
229
224
220
215
205
212
179
22
250
226
247
193
246
168
245
142
243
117
–
–
38228
19
245
247
239
237
231
212
230
186
228
161
227
136
17
251
246
243
246
224
230
225
222
216
207
213
180