FORM 100.50-EG3 (802)
33
YORK INTERNATIONAL
TABLE 10 –
COOLING PERFORMANCE DATA* –
90 TON MODEL
(CONT’D)
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
288
227
286
197
285
174
284
152
282
129
–
–
33980
19
273
262
266
238
265
215
264
191
263
169
261
147
17
274
274
269
270
262
263
247
228
243
209
243
186
22
299
254
297
218
295
191
294
165
292
138
–
–
40776
19
291
295
278
267
276
239
275
210
273
184
271
158
17
296
296
288
291
280
288
261
257
254
232
253
204
22
305
272
302
231
301
201
299
172
297
143
–
–
45307
19
304
314
284
285
282
254
280
222
278
193
276
165
17
309
309
296
300
294
302
269
275
259
247
258
215
22
310
285
306
241
304
209
303
178
300
147
–
–
50970
19
314
328
289
298
286
265
284
231
282
201
280
170
17
319
319
303
307
304
312
276
288
264
258
262
223
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
276
223
274
192
273
170
272
148
270
125
–
–
33980
19
260
256
255
233
254
210
253
186
252
164
250
143
17
261
261
259
259
253
253
237
223
233
204
232
181
22
287
249
285
212
283
186
282
159
280
133
–
–
40776
19
277
287
267
260
265
233
263
204
261
179
260
153
17
282
282
276
279
271
278
250
252
243
226
242
198
22
293
266
290
225
288
196
287
167
284
138
–
–
45307
19
289
302
272
278
270
248
268
216
266
188
265
159
17
294
294
284
288
284
292
258
267
248
240
247
208
22
297
279
294
235
292
203
290
172
288
143
–
–
50970
19
299
312
277
291
274
260
272
225
270
195
268
164
17
304
304
291
295
293
302
264
276
252
251
251
216