FORM 100.50-EG3 (802)
35
YORK INTERNATIONAL
TABLE 11 –
COOLING PERFORMANCE DATA* –
95 TON MODEL
(CONT’D)
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
305
247
304
214
303
189
301
164
300
137
–
–
33980
19
288
285
282
258
282
233
281
207
279
183
277
152
17
293
293
285
288
272
277
262
248
259
227
258
196
22
308
249
307
216
305
191
304
165
302
138
–
–
40776
19
290
288
285
260
285
236
284
209
282
185
280
154
17
297
297
289
292
275
281
266
251
263
230
261
198
22
309
250
308
217
307
192
305
166
303
139
–
–
45307
19
292
289
287
262
286
237
285
210
284
186
282
155
17
300
300
291
295
278
283
268
254
265
232
264
200
22
310
251
309
218
308
192
306
166
304
139
–
–
50970
19
293
291
288
263
288
238
287
211
285
187
283
155
17
302
302
294
297
280
286
271
256
267
234
266
202
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
293
241
291
209
290
184
289
159
287
132
–
–
33980
19
275
279
271
252
270
227
269
202
267
177
266
147
17
280
280
275
278
264
272
251
242
248
221
247
190
22
296
243
294
211
292
185
291
160
289
133
–
–
40776
19
278
282
274
255
273
230
272
204
270
179
268
149
17
284
284
279
282
268
275
254
245
252
224
250
193
22
297
244
295
212
294
186
292
161
291
134
–
–
45307
19
280
283
275
256
274
231
273
205
272
180
270
150
17
287
287
281
285
271
278
257
248
254
226
253
195
22
298
244
296
213
295
187
293
162
292
134
–
–
50970
19
281
285
277
257
275
232
275
206
273
181
271
150
17
289
289
284
287
273
280
259
249
256
228
254
196