YORK INTERNATIONAL
34
TABLE 11 –
COOLING PERFORMANCE DATA* –
95 TON MODEL
Cooling Performance Data –
95 Ton Model
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
35°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
29.4°C AIR ON CONDENSER COIL
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
324
250
323
222
322
197
321
171
319
143
–
–
33980
19
304
293
298
265
298
241
299
215
297
191
295
159
17
310
310
298
302
282
272
278
256
275
235
274
203
22
337
271
335
239
334
210
332
182
330
152
–
–
40776
19
324
317
311
287
311
259
310
231
308
204
306
169
17
330
330
313
317
299
292
293
280
287
254
285
218
22
343
289
341
253
339
221
338
190
336
158
–
–
45307
19
339
341
318
306
317
276
316
244
314
214
312
176
17
344
344
323
327
313
313
303
301
293
270
291
230
22
349
303
346
264
344
230
342
196
340
163
–
–
50970
19
349
360
323
321
322
289
320
254
319
222
316
181
17
355
355
330
334
324
330
310
317
298
282
295
238
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
312
250
312
217
311
192
309
166
307
139
–
–
33980
19
293
288
289
261
288
236
288
210
286
186
284
155
17
298
298
290
293
274
278
268
251
265
230
264
199
22
325
271
323
234
322
205
320
177
318
148
–
–
40776
19
313
312
301
282
300
254
299
225
297
199
295
164
17
318
318
304
308
290
293
283
274
277
248
275
213
22
332
289
329
248
327
216
326
185
324
153
–
–
45307
19
326
335
308
301
306
271
305
238
303
209
301
171
17
332
332
314
317
304
310
292
295
283
263
280
225
22
337
303
333
259
332
224
330
191
328
158
–
–
50970
19
337
352
313
316
311
283
309
248
307
216
305
176
17
342
342
321
325
315
324
299
311
287
275
285
233