![background image](http://html1.mh-extra.com/html/york/eadc-09-fsaar/eadc-09-fsaar_installation-instructions-manual_3797484010.webp)
550
by johnson controls
8
GB
-
R-410A refrigerant is not flammable at
atmospheric pressure. Nevertheless, as it
contains 50% HFC-32, it should never be
pressurised with air or any gas other than
nitrogen (the same as R-22).
POE oil
-
POE oil is highly hygroscopic. Its water
absorbing capacity is 15 times greater
than mineral oil.
-
POE oil containers should be metallic
and should be kept open the least time
possible. They should be hermetically
sealed after use.
-
Never open a circuit or compressor charged
with POE oil while under vacuum. Should
either one be under atmospheric pressure,
it should not remain open for more than
15 minutes. Should this not be possible, a
flow of dry nitrogen should be established.
-
POE oil cannot be mixed with mineral oil.
Amounts of over 5% of mineral oil mixed
with POE will cause transitory obstructions
within the expansion systems..
-
It is recommendable to use filter-dryers on
systems using POE oil.
-
Should the POE oil become contaminated
with water, a vacuum pump is no longer
sufficient. Excessive presence of humidity
causes sludge and acids that damage the
compressor. Therefore, any contaminated
oil should be changed or recovered by
means of filters.
-
Due to its high hygroscopic nature, POE
oil can cause burns on the skin. The use of
gloves during handling is recommended.
-
The POE oils that are adequate for R-410A
systems are as follows:
MOBIL EAL ARCTIC 22 CC (ICI)
EMKARATE RL32CF (ICI)
Specific tools
For installing equipment charged with
R-410A refrigerant and POE oil, the following
tools are required:
-
Pressure gauges
. Specific for R-410A.
High pressure (red) with a range of -1 to
53 bar. Low pressure (blue) with a range
of -1 to 38 bar. With ½” threaded UNF-20
connections.
-
Hoses
. Of HNBR rubber and with nylon
internal lining. Operating pressure 5.1
Mpa, bursting pressure 27.4 Mpa. ½”
UNF-20 thread.
-
Vacuum pump
. High vacuum (two stages)
and with adapter to avoid part of the mineral
oil in the pump from flowing towards the
circuit charged with POE oil. With adapter
for ½” UNF-20 thread.
-
Electronic scale
. Needed because it is
impossible to charge R-410A by using a
charge cylinder due to the bubbles caused
by the high pressure and speed of gas
evaporation.
-
Refrigerant tank
. Adequate for a pressure
of 47 bar and for containing R-410A only
(painted pink). With adapter for ½” UNF-
20 thread.
-
Leak detector
. Specific for HFC. Sensitivity
of approximately 23 gr. year.
-
Recovery equipment
. Specific unit for
recovery of R-410A.
Minimum thickness of tubing
Due to the greater operating pressures
of R-410A refrigerant, the interconnection
of the split units requires seamless DHP
copper tubing with thicker walls.
Tubing diameter
mm (inches
Minimum thickness
mm
6,35 (1/4")
0,76
9,52 (3/8")
0,812
12,70 (1/2")
0,812
Limits of use
Voltage limits
Air intake temperature to outdoor coil DB
Air intake temperature to indoor coil
Nom. 230 V
Operating cycle
Operating cycle
Minimum °C
Maximum °C
Minimum °C
Maximum °C
Minimum
Maximum
Cool
Heat
Cool
Heat
Cool WB
Heat DB
Cool WB
Heat DB
198
254
18
-7
46
24
15
10(1)
23 (1)
32
Notes: WB = Wet bulb. DB = Dry bulb.
(1) This equipment can operate, for a short interval of time, at a temperature beyond limits until the occupied space is conditioned.
Summary of Contents for EADC - 09 FSAAR
Page 2: ...542 542...
Page 30: ...570...
Page 32: ...572 www johnsoncontrols com...
Page 34: ...574 by johnson controls 2...
Page 46: ...586...
Page 48: ...588 www johnsoncontrols com...
Page 69: ...609 7 1 Exploded View of Components and Parts of Indoor unit...
Page 71: ...611 7 2 Exploded View of Components and Parts of Indoor unit...
Page 73: ...613 7 3 Exploded View of Components and Parts of Indoor unit...
Page 75: ...615 7 4 Exploded View of Components and Parts of Indoor unit...
Page 77: ...617 7 5 Exploded View of Components and Parts of Outdoor unit...
Page 79: ...619 7 6 Exploded View of Components and Parts of Outdoor unit...
Page 81: ...621 7 7 Exploded View of Components and Parts of Outdoor unit...
Page 83: ...623 Bee Series Trouble Shooting Trouble Shooting 8...
Page 84: ...624...
Page 85: ...625...
Page 86: ...626 B 9 8 B 0 7 B0 B0 tor 0 0 9 9 0 0 or 0 0 0 0 9 C...
Page 87: ...627...
Page 88: ...628 www johnsoncontrols com...