background image

ELECTRICAL CONNECTIONS

1. Check the electrical supply to be sure that it meets the

values specified on the unit nameplate and wiring label.

2. Remove proper low voltage knockout. Remove plastic snap

bushing from instruction packet and insert in low voltage
knockout hole.

3. The complete connection diagram and schematic wiring label

is located on the inside surface of the unit electrical box cover.
Typical Field Wiring is shown in Figures 4 and 5.

4. All field wiring to be in accordance with national electrical

code (NEC) and/or local city codes.

NOTE: Power wiring, disconnect switch, and overcurrent pro-

tection to be supplied by installer. See Physical and
Electrical Data Table for proper sizes. USE COPPER
CONDUCTORS ONLY. Unit must be grounded with a
separate ground conductor wire.

5. Install the proper size weatherproof disconnect switch out-

doors and within sight of the unit.

6. Run power wiring from the disconnect switch to the unit.

7. Install the proper size time-delay fuses or circuit breaker,

and make the power supply connections.

8. Energize the crankcase heater, if applicable, to save time

by preheating the compressor oil while the remaining instal-
lation is completed.

The crankcase heater, when furnished, is energized whenever
the compressor is not running. Check for proper operation by

feeling for heat on the compressor where the heater is installed.
The heater should be energized for at least 8 hours before the
thermostat is set to operate the compressor.

CAUTION: An attempt to start the compressor without at least

8 hours of crankcase heat will damage the com-
pressor.

A warning label with an adhesive back is supplied in the unit
installation instruction packet. This label should be attached to
the field supplied disconnect switch where it will be easily seen.
See below:

TUBING CONNECTIONS

Sweat-connect systems must use field supplied, clean, dehy-
drated refrigeration-grade copper tubing.

Quick-connect systems must use pre-charged refrigerant line
sets (quick-connect couplings) designated for the respective
unit size.  Pre-charged lines with excess tubing should be
coiled horizontally in an inconspicuous location to avoid oil
trapping.

IMPORTANT

035-03095A

IF POWER HAS BEEN OFF FOR 8 HOURS OR LONGER,
DISCONNECT SWITCH MUST BE TURNED ON 8 HOURS
BEFORE THERMOSTAT IS SET TO “HEAT”, “COOL” OR
“AUTO”.

24" SERVICE
ACCESS
CLEARANCE

WEATHERPROOF 
DISCONNECT SWITCH

NEC CLASS 1
WIRING

TO
BLOWER
MOTOR
RELAY

NEC CLASS 2
WIRING

TO
INDOOR
COIL

SEAL 
OPENING(S) 
WITH 
PERMAGUM OR
EQUIVALENT

THERMOSTAT

Sit unit on
rubber
elevator
grommets to
reduce noise
and allow for
proper
drainage.

Check local weather bureau for snow accumulation.

TO POWER
SUPPLY

NOTE:  ALL OUTDOOR WIRING
             MUST BE WEATHERPROOF

48" OVERHEAD
CLEARANCE

INSTALL BI-FLOW FILTER
DRIER IN LIQUID LINE

12" REAR
AND SIDES

FIGURE 3 - TYPICAL INSTALLATION

515.26-N5Y

4

Unitary Products Group

Summary of Contents for E9FD018 Series

Page 1: ...priate indoor unit air moving system and accessories Installer should pay particular attention to the words NOTE CAUTION and WARNING NOTES are intended to clarify or make the installation easier CAUTI...

Page 2: ...cause personal injury Remember that condensate will drip from the unit coils during heat and defrost cycles and that this condensate will freezewhen thetemperature ofthe outdoor air is below 32 F Ele...

Page 3: ...SQ FT 14 2 15 1 15 1 17 0 20 20 24 ROWS DEEP 1 1 1 1 1 1 2 FIN INCH 13 18 18 20 13 16 13 LIQUID LINE OD 3 8 3 8 3 8 3 8 3 8 3 8 3 8 VAPOR LINE OD 5 8 5 8 3 4 3 4 7 8 7 8 7 8 OPERATING WEIGHT LBS 140 1...

Page 4: ...ressor where theheater isinstalled The heater should be energized for at least 8 hours before the thermostat is set to operate the compressor CAUTION An attempt to start the compressor without at leas...

Page 5: ...or C L or X T E FIELD INSTALLED JUMPER 1 2 2 BLK YEL ORG WHT BRN X FIGURE 4 TYPICAL 1 FIELD WIRING Air Handler Electric Heat Y O W1 or 66 W GRD LUG DEFROST CONTROL CONTACTOR GRD SCREW M R C 53 or W3 R...

Page 6: ...es with as few bends as possible Care must be taken not to damage the couplings or kink the tubing Care must also be used to isolate the refrigerant lines to minimize noise transmission from the equip...

Page 7: ...e coil instruction for details to change the orifice in the coil QUICK CONNECT SYSTEMS Indoor coils and outdoor units are to be connected with pre charged interconnecting tubing specified for the spli...

Page 8: ...it as shown in Figure 9 Also protect all painted surfaces and insulation during brazing After brazing cool joint with wet rag WARNING Thisis not a backseating valve The service access port has a valv...

Page 9: ...ovided Connect the control wiring see Figure 4 or 5 for Typical Field Wiring EVACUATION It will be necessary to evacuate the system if the unit has developed a leak during shipment or was for any othe...

Page 10: ...t through blower relay to provide blower operation 4 System will cycle with thermostat demand to provide cool ing as needed WITH POWER TO UNIT AND THERMOSTAT IN HEATING POSITION 1 Reversing valve is d...

Page 11: ...l illumi nate on the thermostat To reset the lockout turn the indoor thermostat s system switch to OFF then back to the selected mode within 5 second OR disconnect the power to the trans former for at...

Page 12: ...ting discharging warm air from the ducts 3 The vapor line at the outdoor unitwill feel warm to the touch 4 The liquid line at the outdoor unit will feel cool to the touch NOTICE TO OWNER If lockout oc...

Reviews: