background image

INSTRUCTING THE OWNER

Assist owner with processing warranty cards. Review User’s
Information Manual and provide a copy for the owner guidance
on proper operation and maintenance. Instruct the owner or the
operator how to start, stop and adjust temperature setting. The
owner should also be instructed about the 5 minute off cycle
timer and the defrost operation.

When applicable, instruct the owner that the compressor is
equipped with a crankcase heater to prevent the migration of
refrigerant to the compressor during the “OFF” cycle. The
heater is energized only when the unit is not running. If the main
switch is disconnected for long periods of shut down, do not
attempt to start the unit for 8 hours after the switch has been
connected. This will allow sufficient time for all liquid refrigerant
to be driven out of the compressor.

The installer should also instruct the owner on proper operation
and maintenance of all other system components.

INDICATIONS OF PROPER OPERATION

COOLING 

Cooling operation is the same as any conventional air condi-
tioning unit.

1. The outdoor fan should be running, with warm air being

discharged from the top of the unit.

2. The indoor blower (furnace or air handler) will be operating,

discharging cool air from the ducts.

3. The vapor line at the outdoor unit will feel cool to the touch.

4. The liquid line at the outdoor unit will feel warm to the touch.

HEATING

Indications of proper Heating operation is as follows:

1. The outdoor fan should be running, with cool air being

discharged from the top of the unit.

2. The indoor blower (furnace or air handler) will be operating,

discharging warm air from the ducts.

3. The vapor line at the outdoor unit will feel warm to the touch.

4. The liquid line at the outdoor unit will feel cool to the touch.

NOTICE TO OWNER:

If lockout occurs, check the following before calling a serviceman:

1. Indoor section for dirty filter.

2. Outdoor section for snow accumulation.

3. Outdoor section for leaf or debris blockage.

Eliminate problem, turn off the thermostat for 10 seconds and attempt
start. Wait 5 minutes. If system does not start, call serviceman.

MAINTENANCE

1. Dirt should not be allowed to accumulate on the outdoor

coils or other parts in the air circuit. Clean as often as
necessary to keep the unit clean. Use a brush, vacuum
cleaner attachment, or other suitable means.

2. The outdoor fan motor is permanently lubricated and does

not require periodic oiling.

3. If the coil needs to be cleaned, it should be washed with

Calgon Coilclean (mix one part Coilclean to seven parts
water). Allow solution to remain on coil for 30 minutes
before rinsing with clean water. Solution should not be
permitted to come in contact with painted surfaces.

4. Refer to the furnace or air handler instructions for filter and

blower motor maintenance.

5. The indoor coil drain pan should be inspected and cleaned

regularly to prevent odors and assure proper drainage.

CAUTION: IT IS UNLAWFUL TO KNOWINGLY VENT, RE-
LEASE OR DISCHARGE REFRIGERANT INTO THE OPEN
AIR DURING REPAIR, SERVICE, MAINTENANCE OR THE
FINAL DISPOSAL OF THIS UNIT.

WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND
THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE
THE OWNER’S APPROVAL.

Unitary Products Group
P.O. Box 1592, York, Pennsylvania USA 17405-1592
Subject to change without notice.   Printed in U.S.A.
Copyright

 

 by York International Corporation 1996.  All Rights Reserved.

SHU  12M  296  .66

Code: SBY

515.26-N5Y

Summary of Contents for E9FD018 Series

Page 1: ...priate indoor unit air moving system and accessories Installer should pay particular attention to the words NOTE CAUTION and WARNING NOTES are intended to clarify or make the installation easier CAUTI...

Page 2: ...cause personal injury Remember that condensate will drip from the unit coils during heat and defrost cycles and that this condensate will freezewhen thetemperature ofthe outdoor air is below 32 F Ele...

Page 3: ...SQ FT 14 2 15 1 15 1 17 0 20 20 24 ROWS DEEP 1 1 1 1 1 1 2 FIN INCH 13 18 18 20 13 16 13 LIQUID LINE OD 3 8 3 8 3 8 3 8 3 8 3 8 3 8 VAPOR LINE OD 5 8 5 8 3 4 3 4 7 8 7 8 7 8 OPERATING WEIGHT LBS 140 1...

Page 4: ...ressor where theheater isinstalled The heater should be energized for at least 8 hours before the thermostat is set to operate the compressor CAUTION An attempt to start the compressor without at leas...

Page 5: ...or C L or X T E FIELD INSTALLED JUMPER 1 2 2 BLK YEL ORG WHT BRN X FIGURE 4 TYPICAL 1 FIELD WIRING Air Handler Electric Heat Y O W1 or 66 W GRD LUG DEFROST CONTROL CONTACTOR GRD SCREW M R C 53 or W3 R...

Page 6: ...es with as few bends as possible Care must be taken not to damage the couplings or kink the tubing Care must also be used to isolate the refrigerant lines to minimize noise transmission from the equip...

Page 7: ...e coil instruction for details to change the orifice in the coil QUICK CONNECT SYSTEMS Indoor coils and outdoor units are to be connected with pre charged interconnecting tubing specified for the spli...

Page 8: ...it as shown in Figure 9 Also protect all painted surfaces and insulation during brazing After brazing cool joint with wet rag WARNING Thisis not a backseating valve The service access port has a valv...

Page 9: ...ovided Connect the control wiring see Figure 4 or 5 for Typical Field Wiring EVACUATION It will be necessary to evacuate the system if the unit has developed a leak during shipment or was for any othe...

Page 10: ...t through blower relay to provide blower operation 4 System will cycle with thermostat demand to provide cool ing as needed WITH POWER TO UNIT AND THERMOSTAT IN HEATING POSITION 1 Reversing valve is d...

Page 11: ...l illumi nate on the thermostat To reset the lockout turn the indoor thermostat s system switch to OFF then back to the selected mode within 5 second OR disconnect the power to the trans former for at...

Page 12: ...ting discharging warm air from the ducts 3 The vapor line at the outdoor unitwill feel warm to the touch 4 The liquid line at the outdoor unit will feel cool to the touch NOTICE TO OWNER If lockout oc...

Reviews: