background image

Use the following charging method whenever additional refrig-
erant is required for the system charge.

MEASUREMENT METHOD

A calibrated charging cylinder or accurate weighing device
must be used to add refrigerant. This is the only accurate
charging method for heat pumps in the heat pump mode.

Check flare caps on service ports to be sure they are leak tight.
DO NOT OVERTIGHTEN (between 40 and 60 inch-lbs. maxi-
mum).

SYSTEM OPERATION

See Figure 11 to trace the flow of refrigerant through the
system.

WITH POWER TO UNIT AND THERMOSTAT IN COOLING
POSITION.

1. Reversing valve is energized through thermostat system

switch to position refrigerant circuit for cooling operation. In
the cooling cycle, discharge gas is pumped to the outdoor
coil which is the condenser. The indoor coil is the evapora-
tor.

2. If fan switch is in “ON” position, a circuit is made through

blower relay to provide continuous blower operation.

3. When thermostat cooling contact closes, a circuit is made

to energize contactor and start the system, if the compres-

sor has been off for 5 minutes. With fan switch in “AUTO”
position, a circuit is made from thermostat cooling contact
through blower relay to provide blower operation.

4. System will cycle with thermostat demand to provide cool-

ing as needed.

WITH POWER TO UNIT AND THERMOSTAT IN HEATING
POSITION

1. Reversing valve is de-energized to position refrigerant

circuit for heating operation. In the heating cycle, discharge
gas is pumped to the indoor coil which is the condenser.
The outdoor coil is the evaporator.

2. If fan switch is in “ON” position, a circuit is made through

blower relay to provide continuous blower operation.

3. When first stage of thermostat heating contact closes, a

circuit is made through the control to energize contactor
and start the system, if the compressor has been off 5
minutes. With fan switch in “AUTO” position, a circuit is
made from thermostat heating contact through blower relay
to provide blower operation.

4. The system will cycle in response to thermostat signal to

provide heating as needed.

5. Supplemental electric heaters are energized by second

stage of heating thermostat.

FIGURE 11 - HEAT PUMP FLOW DIAGRAM 

FLOW
CONTROL
DEVICE
(COOLING)

INDOOR
COIL

FIELD INSTALLED BI-FLOW LIQUID STRAINER / DRYER

COMPRESSOR

4-WAY REVERSING VALVE*

SUCTION
ACCUM.

OUTDOOR
COIL

COOLING CYCLE FLOW

HEATING CYCLE FLOW

*SHOWN IN
 COOLING
 POSITION

FIELD CONNECTED LINE

FIELD CONNECTED LINE

FLOW CONTROL DEVICE (HEATING)

515.26-N5Y

10

Unitary Products Group

Summary of Contents for E9FD018 Series

Page 1: ...priate indoor unit air moving system and accessories Installer should pay particular attention to the words NOTE CAUTION and WARNING NOTES are intended to clarify or make the installation easier CAUTI...

Page 2: ...cause personal injury Remember that condensate will drip from the unit coils during heat and defrost cycles and that this condensate will freezewhen thetemperature ofthe outdoor air is below 32 F Ele...

Page 3: ...SQ FT 14 2 15 1 15 1 17 0 20 20 24 ROWS DEEP 1 1 1 1 1 1 2 FIN INCH 13 18 18 20 13 16 13 LIQUID LINE OD 3 8 3 8 3 8 3 8 3 8 3 8 3 8 VAPOR LINE OD 5 8 5 8 3 4 3 4 7 8 7 8 7 8 OPERATING WEIGHT LBS 140 1...

Page 4: ...ressor where theheater isinstalled The heater should be energized for at least 8 hours before the thermostat is set to operate the compressor CAUTION An attempt to start the compressor without at leas...

Page 5: ...or C L or X T E FIELD INSTALLED JUMPER 1 2 2 BLK YEL ORG WHT BRN X FIGURE 4 TYPICAL 1 FIELD WIRING Air Handler Electric Heat Y O W1 or 66 W GRD LUG DEFROST CONTROL CONTACTOR GRD SCREW M R C 53 or W3 R...

Page 6: ...es with as few bends as possible Care must be taken not to damage the couplings or kink the tubing Care must also be used to isolate the refrigerant lines to minimize noise transmission from the equip...

Page 7: ...e coil instruction for details to change the orifice in the coil QUICK CONNECT SYSTEMS Indoor coils and outdoor units are to be connected with pre charged interconnecting tubing specified for the spli...

Page 8: ...it as shown in Figure 9 Also protect all painted surfaces and insulation during brazing After brazing cool joint with wet rag WARNING Thisis not a backseating valve The service access port has a valv...

Page 9: ...ovided Connect the control wiring see Figure 4 or 5 for Typical Field Wiring EVACUATION It will be necessary to evacuate the system if the unit has developed a leak during shipment or was for any othe...

Page 10: ...t through blower relay to provide blower operation 4 System will cycle with thermostat demand to provide cool ing as needed WITH POWER TO UNIT AND THERMOSTAT IN HEATING POSITION 1 Reversing valve is d...

Page 11: ...l illumi nate on the thermostat To reset the lockout turn the indoor thermostat s system switch to OFF then back to the selected mode within 5 second OR disconnect the power to the trans former for at...

Page 12: ...ting discharging warm air from the ducts 3 The vapor line at the outdoor unitwill feel warm to the touch 4 The liquid line at the outdoor unit will feel cool to the touch NOTICE TO OWNER If lockout oc...

Reviews: