background image

CAUTION: Do not connect manifold gauges unless trouble is

suspected. Approximately 3/4 ounce of refrigerant
will be lost each time a standard manifold gauge is
connected.

7. The quick connect outdoor unit contains enough refrigerant

charge for a matched indoor coil. Refer to Table 4 for the
amount of additional charge required for some mix-
matched indoor coils. If additional charge is required, see
recommended charging methods.

SWEAT-CONNECT SYSTEMS

The outdoor units have re-usable service valves on both the
liquid and vapor connections.  The total system refrigerant
charge is retained within the outdoor unit during shipping and
installation. The re-usable service valves are provided to
evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate
precautions to assure an internally clean and dry system.

Always use refrigeration-grade copper tubing that is internally
clean and dry for refrigerant lines. Use clean hard drawn copper
tubing where no appreciable amount of bending around ob-
struction is necessary. If soft copper must be used, care must
be taken to avoid sharp bends which may cause a restriction.
The vapor line must be insulated with a minimum of 1/2 inch
insulation (Arm-A-Flex or equivalent).

CAUTION: Dry nitrogen should always be supplied through

the tubing while it is being brazed, because  the
temperature required is high enough to cause oxi-
dation of the copper unless an inert atmosphere is
provided. The flow of dry nitrogen should continue
until the joint has cooled. Always use a pressure
regulator and safety valve to insure that only low
pressure dry nitrogen is introduced into the tubing.
Only a small flow is necessary to displace air and
prevent oxidation.

All outdoor unit and indoor coil connections are copper-to-cop-
per and should be brazed with a phosphorous-copper alloy
material such as Silfos-5 or equivalent. DO NOT use soft
solder.

BASE VALVE CONNECTION PRECAUTIONS

Precautions should be taken to prevent heat damage to the
fitting by wrapping a wet rag around it as shown in Figure 9.
Also, protect all painted surfaces and insulation during brazing.
After brazing - cool joint with wet rag.

WARNING: This is not a backseating valve. The service access

port has a valve core. Opening or closing valve
does not close service access port . See Figure 10.

Valve can be opened by removing the plunger cap and fully
inserting a hex wrench into the stem and backing out counter-
clockwise until valve stem just touches retaining ring.

CAUTION:  If visual verification ot the valve stem reaching the

retaining ring is impossible, stop backing out the
valve stem when the slightest increase in resis-
tance is felt. Because of the small size and there-
fore the reduced resistance, back out the liquid
valve 5 turns maximum to prevent going past the
retaining ring.

WARNING:  If the valve stem is backed out past the retaining

ring, the O’ring can be damaged causing leakage
or system pressure could force the valve stem out
of the valve body possibly causing personal injury.
In the event the retaining ring is missing, do not
attempt to open the valve.

Replace plunger cap finger tight, then tighten an additional 1/12
turn (1/2 hex flat). Cap must be replaced to prevent leaks.

LINE INSTALLATION

Install the refrigerant lines using the following procedure:

1. Remove the cap and Schrader core from both the liquid and

vapor fitting service ports at the outdoor unit. Connect low
pressure nitrogen to the liquid line service port.

2. Braze the liquid line to the liquid fitting at the outdoor unit.

Be sure to wrap the fitting body with a wet rag. Allow the
nitrogen to continue flowing.

3. Carefully remove the rubber plugs from the indoor coil

liquid and vapor connections. Use caution, since the coil is
pressurized. Release the gas through the schrader fitting
at the liquid connection before removing cap on vapor line.

4. Braze the liquid line to the indoor coil  liquid connection.

The nitrogen should now be flowing through the coil.

5. Remove the grommet from the vapor connection at the coil.

Braze the vapor line to the indoor coil vapor connection.
After the connection has cooled, replace the grommet.

FIGURE 9 - HEAT PROTECTION

FIGURE 10 -  SHUT-OFF VALVE

SERVICE ACCESS
PORT WITH
SCHRADER

PLUNGER CAP

515.26-N5Y

8

Unitary Products Group

Summary of Contents for E9FD018 Series

Page 1: ...priate indoor unit air moving system and accessories Installer should pay particular attention to the words NOTE CAUTION and WARNING NOTES are intended to clarify or make the installation easier CAUTI...

Page 2: ...cause personal injury Remember that condensate will drip from the unit coils during heat and defrost cycles and that this condensate will freezewhen thetemperature ofthe outdoor air is below 32 F Ele...

Page 3: ...SQ FT 14 2 15 1 15 1 17 0 20 20 24 ROWS DEEP 1 1 1 1 1 1 2 FIN INCH 13 18 18 20 13 16 13 LIQUID LINE OD 3 8 3 8 3 8 3 8 3 8 3 8 3 8 VAPOR LINE OD 5 8 5 8 3 4 3 4 7 8 7 8 7 8 OPERATING WEIGHT LBS 140 1...

Page 4: ...ressor where theheater isinstalled The heater should be energized for at least 8 hours before the thermostat is set to operate the compressor CAUTION An attempt to start the compressor without at leas...

Page 5: ...or C L or X T E FIELD INSTALLED JUMPER 1 2 2 BLK YEL ORG WHT BRN X FIGURE 4 TYPICAL 1 FIELD WIRING Air Handler Electric Heat Y O W1 or 66 W GRD LUG DEFROST CONTROL CONTACTOR GRD SCREW M R C 53 or W3 R...

Page 6: ...es with as few bends as possible Care must be taken not to damage the couplings or kink the tubing Care must also be used to isolate the refrigerant lines to minimize noise transmission from the equip...

Page 7: ...e coil instruction for details to change the orifice in the coil QUICK CONNECT SYSTEMS Indoor coils and outdoor units are to be connected with pre charged interconnecting tubing specified for the spli...

Page 8: ...it as shown in Figure 9 Also protect all painted surfaces and insulation during brazing After brazing cool joint with wet rag WARNING Thisis not a backseating valve The service access port has a valv...

Page 9: ...ovided Connect the control wiring see Figure 4 or 5 for Typical Field Wiring EVACUATION It will be necessary to evacuate the system if the unit has developed a leak during shipment or was for any othe...

Page 10: ...t through blower relay to provide blower operation 4 System will cycle with thermostat demand to provide cool ing as needed WITH POWER TO UNIT AND THERMOSTAT IN HEATING POSITION 1 Reversing valve is d...

Page 11: ...l illumi nate on the thermostat To reset the lockout turn the indoor thermostat s system switch to OFF then back to the selected mode within 5 second OR disconnect the power to the trans former for at...

Page 12: ...ting discharging warm air from the ducts 3 The vapor line at the outdoor unitwill feel warm to the touch 4 The liquid line at the outdoor unit will feel cool to the touch NOTICE TO OWNER If lockout oc...

Reviews: