background image

DUCTWORK

Ductwork should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors of
America (ACCA).
A closed return duct system shall be used. This shall not
preclude use of economizers or outdoor fresh air intake. The
supply and return air duct connections at the unit should be
made with flexible joints to minimize noise.
The supply and return air duct systems should be designed for
the CFM and static requirements of the job. They should NOT
be sized to match the dimensions of the duct connections on
the unit.
CAUTION: When fastening ductwork to side duct flanges on

unit, insert screws through duct flanges only. DO
NOT insert screws through casing.
Outdoor ductwor k must be insulated and
waterproofed.

Refer to Dimensions and Clearances Figure for information
concerning side and bottom supply and return air duct openings.

FIXED OUTDOOR AIR INTAKE DAMPER 

This damper is shipped inside the return air compartment. It is
completely assembled and ready for installation. A damper
baffle inside of the hood is adjustable to provide variable
amounts of outdoor air intake on units that are not provided
with an economizer or a motorized damper option. Refer to  the
Fixed Outdoor Damper figure.
Gasketing and mounting screws are provided in a parts bag
attached to the hood assembly. Apply gasketing to the three
flange surfaces on the hood prior to installing the hood. Extend
gasketing 1/4 inch beyond the top and bottom of the two side
flanges to insure adequate sealing.
Adjusting the damper to the desired air flow may be done before
mounting the hood into position or (after installation) by
removing the front hood panel or the screen on the bottom of
the hood. Damper baffle in position 1 will allow approximately
10% recirculated air flow, position 2 approximately 15% and, to
allow approximately 25%, remove the damper baffle.
On units with bottom return air applications, install the damper
assembly over the opening in the side return air access panel.
Remove and discard the opening cover and the covering over
the hood mounting holes (used for shipping) before installing.
Secure with the screws provided.
On units with side return air applications, install the damper
assembly on the return air ductwork as close to the unit as
possible. Cut an opening 16 inches high by 18 inches wide in
the ductwork to accommodate the damper. Using the holes in
the hood flanges as a template, drill 9/64 inch dia. (#26 drill)
holes into the ductwork and secure with the screws provided.
CAUTION: If outdoor air intake will not be required on units

with bottom return air applications, the damper
assembly should still be mounted on the side return
air access panel, per the instructions above, to
insure moisture is not drawn into the unit during
operation. The covering over the mounting holes
only need be removed. Do not remove the opening
cover.

CONDENSATE DRAIN

Plumbing must conform to local codes. Use a sealing
compound on male pipe threads. Install a condensate drain line

from the one-inch NPT female connection on the unit to an open
drain.

An alternate drain connection (one-inch NPT female coupling)
is provided inboard on the same centerline as the exterior
location.

NOTE:  The condensate drain operates in a negative pressure

in the cabinet. The condensate drain line MUST be
trapped to provide proper drainage. See figure below.

COMPRESSORS

Units are shipped with compressor mountings factory-adjusted
and ready for operation.

CAUTION: Do Not loosen compressor mounting bolts.

FILTERS

Two-inch filters are supplied with each unit. Filters must always
be installed ahead of the evaporator coil and must be kept clean
or replaced with same size and type. Dirty filters will reduce the
capacity of the unit and will result in frosted coils or safety
shutdown. Minimum filter area and required sizes are shown in
Physical Data Table.

SERVICE ACCESS

Access to all serviceable components is provided by the
following removable panels:

Compressor compartment

Gas Heat compartment (Two panels)

Side Supply & Return Air compartments (Two panels)

Blower compartment (Three panels)

Main control box

Filter compartment

Outdoor Air compartment (Two panels)

Refer to the Dimensions and Clearances Figure  for location of
these access panels.

CAUTION: Make sure that all screws and panel latches are

replaced and properly positioned on the unit to
maintain an air-tight seal.

FIG. 3 - FIXED OUTDOOR AIR DAMPER

FIG. 4 - RECOMMENDED DRAIN PIPING

It is recommended that, in Canada, the outlet duct be provided with
a removable access panel. It is recommended that this opening be
accessible when the unit is installed in service, and of a size such
that smoke or reflected light may be observed inside the casing to
indicate the presence of leaks in the heat exchanger. The cover
should be attached in a manner adequate to prevent leakage.

530.18-N6Y

4

Unitary Products Group

Summary of Contents for D2CG180

Page 1: ...rsion Accessory USA 530 18 N6 2V High Altitude Accessory Nat Gas 530 18 N6 3V High Altitude Accessory Propane 530 18 N13Y Coil Guard Installation Renewal Parts Refer to the Renewal Parts Manual for co...

Page 2: ...7 Four And Six Point Loads 12 8 Supply Air Blower Perf 15 Ton 13 9 Supply Air Blower Perf 20 Ton 14 10 Static Resistances 15 11 Power Exhaust Performance 15 12 Blower Motor and Drive Data 15 13 Limit...

Page 3: ...ame other than a YORK roof curb gasketing must be applied to all surfaces that come in contact with the unit underside 5 Maintain level tolerance to 1 2 inch maximum across the entire length or width...

Page 4: ...ductwork to accommodate the damper Using the holes in the hood flanges as a template drill 9 64 inch dia 26 drill holes into the ductwork and secure with the screws provided CAUTION If outdoor air in...

Page 5: ...ing to the unit waterproof type connectors MUST BE USED so that water or moisture cannot be drawn into the unit during normal operation The above waterproofing conditions will also apply when installi...

Page 6: ...or John Crane may be used 4 All piping should be cleaned of dirt and scale by hammering on the outside of the pipe and blowing out the loose dirt and scale Before initial start up be sure that all of...

Page 7: ...securing in place OPTIONAL ECONOMIZER MOTORIZED DAMPER RAIN HOOD The instruction for the optional economizer motorized damper rain hood can be found in form 44 320 2 Use these instructions when field...

Page 8: ...FIG 9 ENTHALPY SETPOINT ADJUSTMENT 530 18 N6Y 8 Unitary Products Group...

Page 9: ...6 0 43 3 COMPRESSOR Qty Per Unit 10 TON TANDEM 1 2 5 TON HERMETIC 1 AIR FILTERS QUANTITY PER UNIT 16 X 20 X 2 4 QUANTITY PER UNIT 16 X 25 X 2 4 QUANTITY PER UNIT 18 X 24 X 2 5 TOTAL FACE AREA sq ft 15...

Page 10: ...84 9 100 460 3 60 19 2 124 9 6 62 1 2 1 5 7 2 42 4 50 575 3 60 15 4 100 7 7 50 1 2 0 5 5 9 33 9 40 DCG240 208 230 3 60 38 4 248 38 4 248 1 4 1 4 2 7 5 21 0 19 4 115 1 111 6 125 460 3 60 19 2 124 19 2...

Page 11: ...ic meters gas meters regulators and relief equip R E T U R N A I R S U P P L Y A I R B O T T O M S U P P L Y A N D R E T U R N A I R O P E N I N G S S e e N o t e B P O W E R W I R I N G E N T R Y A C...

Page 12: ...NOTE These weights are with economizer and the largest blower motor available UNIT 6 POINT LOADS LBS TOTAL A B C D E F 180 2300 351 367 392 416 399 375 240 2500 334 350 426 502 481 407 NOTE These weig...

Page 13: ...7 3 0 2 7 0 4 3 5 3 1 915 5 0 1 1 2 6 2 4 0 8 3 1 2 8 0 5 3 6 3 2 0 2 4 1 3 7 965 4 0 1 2 2 7 2 5 0 9 3 2 2 9 0 6 3 7 3 3 0 4 4 4 3 9 0 2 5 0 4 5 980 3 5 1 3 2 9 2 6 1 0 3 4 3 0 0 7 3 8 3 4 0 5 4 5 4...

Page 14: ...4 1 1 5 0 4 2 0 6 5 9 5 0 0 1 6 7 5 7 950 3 5 1 7 4 2 3 6 1 3 5 1 4 3 0 8 6 0 5 1 0 2 6 9 5 8 965 2 5 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 0 1 8 5 7 1 995 2 0 2 1 4 6 3 9 1 6 5 5 4 7 1 1 6...

Page 15: ...65 1190 BK80 7 75 7 4 1 BX68 69 8 1 20 TON Stan dard 870 1025 7 5 213T 89 1VP68 6 75 5 5 6 52 1 3 8 BK120 11 75 11 4 1 3 16 BX83 84 8 1 High Speed Access 950 1120 BK110 10 75 10 4 1 3 16 BX81 81 8 1 1...

Page 16: ...rating efficiency ECONOMIZER SINGLE OR DUAL WITH POWER EXHAUST This system operates as specified above with one addition The power exhaust motor is energized whenever the economizer is chosen by the e...

Page 17: ...here are two separate gas valves in the furnace Each valve contains a main and a redundant valve The redundant valves are located upstream of the main gas valves Should either or both of the main gas...

Page 18: ...units If gas pressure is outside these limits contact the local gas utility for corrective action MANIFOLD GAS PRESSURE ADJUSTMENT Small adjustments to the high fire gas flow may be made by turning th...

Page 19: ...within the limitations shown in the Applications Data Table 2 Pulleys can be adjusted in half turn increments 3 The tension on the belt should be adjusted as shown in the Belt Adjustment figure Start...

Page 20: ...2 With the furnace turned on measure the time needed for one revolution of the hand on the smallest dial on the meter A typical gas meter usually has a 1 2 or a 1 cubic foot test dial 3 Using the numb...

Page 21: ...E Exercise care when cleaning the coil so that the coil fins are not damaged Do not permit the hot condenser air discharge to be obstructed by overhanging structures of shrubs BURNER PILOT Periodicall...

Page 22: ...tat fan switch set to AUTO a Set fan switch to ON If blower motor runs go to Step f If it does not check to see if line voltage is being supplied to the contacts of the contactor M3 and if the contact...

Page 23: ...T CHECKOUT b Check all wiring between the ignitor control and the gas valve Check to make sure the ground connections are intact c If the wiring is intact check for 24 volts across terminals PV and CO...

Page 24: ...and information from OUR current parts list for this unit are available to your servicing contractor through our local distributor The name and address of our nearest distributor may be obtained by co...

Reviews: