TABLE 6 - ELECTRICAL DATA
MODEL
POWER
SUPPLY
COMPRESSORS
COND. FAN
MOTORS
(#1 & #2)
SUPPLY AIR
BLOWER
MOTOR
MINIMUM
CIRCUIT
AMPACITY
(AMPS)
MAXIMUM
TIME DELAY
FUSE SIZE
(AMPS)
#1
#2
RLA LRA RLA LRA
HP
EACH
FLA
EACH
HP
FLA
DCG180
208/230-3-60
38.4 248 19.2
124
1
4.1 / 4.2
5
15.4 / 14.4
87.1 / 84.9
100
460-3-60
19.2 124
9.6
62
1
2.1
5
7.2
42.4
50
575-3-60
15.4 100
7.7
50
1
2.0
5
5.9
33.9
40
DCG240
208/230-3-60
38.4 248 38.4
248
1
4.1 / 4.2
7.5
21.0 / 19.4
115.1 / 111.6
125
460-3-60
19.2 124 19.2
124
1
2.1
7.5
9.7
55.8
60
575-3-60
15.4 100 15.4
100
1
2.0
7.5
7.8
44.8
50
VOLTAGE
LIMITATIONS**
POWER SUPPLY
VOLTAGE
MIN.
MAX.
208/230-3-60
187
253
460-3-60
414
506
575-3-60
518
630
**Utilization Range “A” in accordance with ARI Standard 110.