background image

If lock-out continues to occur, locate the source of the
problem and correct.

b. Check all 24 volt connections from the relay board to

and in the gas heat section. Check low voltage connec-
tions to the (ETD) located in the control box.

c. If the furnace is hot, it may be out on an over-tempera-

ture condition, wait for limit reset.

d. If the furnace is cold, check for 24 volts at wire 241

attached to the electrical time delay (ETD) located in the
main control box. If 24 volts is not found, replace the
ETD.

e. 24 volts is found at wire 241, remove the wires attached

to the (TDR) and with a VOM, check for continuity
across contacts 1 and 2. If none is found, the (TDR) is
open and must be replaced. If there is continuity, re-at-
tach the wires.With the draft motor running, check for
24 volts at terminal 4 of (RW1-2) and (RW2-1). If 24 volts
is not present, the centrifugal switch (CS) has not closed
or has gone bad. Check the line voltage to the unit -  if
it is correct, replace the draft motor. If line voltage is low,
call the power company.

f.

Check for 24V at terminal 2 of (RW1-2 and RW2-1). If
24V is not present, check for 24V at (RW1 and RW2)
relay coils. If these relays are pulled in, then check for
a loose connection at terminal 2 and terminal 4 of each
relay. If no problem is found, then replace (RW1 and/or
RW2) as required.

g. If 24 volts is present at the ignitor controls, check all

control wiring at the ignitor controls and the high tension
wire to the ignitors. Check that the ground wires from
the ignitor controls, the gas valves and pilot burners are
all intact and making good electrical connection. Check
to make sure that the ceramic insulator on the pilot
ignitors or sensors is not broken or cracked, if all are
intact, replace the ignition control IC1 or IC2.

5. The draft motor runs and the sparker sparks at the pilot

burner but the pilot does not ignite and a gas odor is not
detected at the draft motor outlet.

a. Check to make sure gas is being supplied to the unit.

Make sure that the gas pressure to the unit is within the
proper limits as described in the “POST START CHECK
LIST” and that the pilot adjust screw is allowing some
flow of gas as described in “PILOT CHECKOUT”.

b. Check all wiring between the ignitor control and the gas

valve. Check to make sure the ground connections are
intact.

c. If the wiring is intact, check for 24 volts across terminals

“PV” and “COMMON” on the ignitor control. If 24 volts
is not present, replace the ignitor control.

d. If 24 volts is present, remove the pilot burner and

remove the pilot orifice from the pilot burner. The orifice
is removed in the direction opposite the flow of gas.
Inspect the orifice for obstruction. If it is clear, replace
the main gas valve.

6. The sparker sparks at the pilot burner but the pilot does not

ignite and a gas odor is detected at the draft motor outlet.

a. Adjust the pilot adjust screw on the gas valve as de-

scribed in “PILOT CHECKOUT”.

b. Check the supply pressure as described in “POST

START CHECK LIST”. Make adjustments as necessary.

c. Check the pilot orifice for obstruction as described in

para. 5d. Clean as needed but the problem should not
be the gas valve.

7. The pilot burner ignites but the sparker continues to spark

and the main burners do not ignite.

a. Make the same checks and adjustment as described in

para. 6.

b. Make sure that the pilot burner is not bent or damaged.

c. Make sure that the ground connections at the pilot

burner, gas valve and ignitor control are intact. Check
the high tension wire for good electrical connection. If
all are intact, replace the ignitor module.

8. The pilot burner lights and the spark stops but the main

burners do not light.

a. Check electrical connections between the ignitor con-

trol and the gas valve. If intact, check for 24 volts across
terminals “MV” and “COMMON” terminals. If no voltage
detected, replace ignitor control. If voltage is present,
replace gas valve.

9. Furnace lights with roll-out or one burner has delayed

ignition.

a. Make sure that the pilot burner is aligned properly with

the carryover as described in “PILOT CHECKOUT”.

b. Make sure that the carryovers on adjoining burners are

screwed fast and are level with respect to one another.

10. Main burners light but exhibit erratic flame characteristics.

a. Adjust air shutters as described in “BURNER AIR

SHUTTER  ADJUSTMENT”.

b. Check the main burner orifices for obstruction and

alignment. Removal procedure is described in
“BURNER INSTRUCTIONS”. Clean or replace burner
orifices and burners as needed.

TROUBLESHOOTING

 - Cont’d.

530.18-N6Y

Unitary Products Group

23

Summary of Contents for D2CG180

Page 1: ...rsion Accessory USA 530 18 N6 2V High Altitude Accessory Nat Gas 530 18 N6 3V High Altitude Accessory Propane 530 18 N13Y Coil Guard Installation Renewal Parts Refer to the Renewal Parts Manual for co...

Page 2: ...7 Four And Six Point Loads 12 8 Supply Air Blower Perf 15 Ton 13 9 Supply Air Blower Perf 20 Ton 14 10 Static Resistances 15 11 Power Exhaust Performance 15 12 Blower Motor and Drive Data 15 13 Limit...

Page 3: ...ame other than a YORK roof curb gasketing must be applied to all surfaces that come in contact with the unit underside 5 Maintain level tolerance to 1 2 inch maximum across the entire length or width...

Page 4: ...ductwork to accommodate the damper Using the holes in the hood flanges as a template drill 9 64 inch dia 26 drill holes into the ductwork and secure with the screws provided CAUTION If outdoor air in...

Page 5: ...ing to the unit waterproof type connectors MUST BE USED so that water or moisture cannot be drawn into the unit during normal operation The above waterproofing conditions will also apply when installi...

Page 6: ...or John Crane may be used 4 All piping should be cleaned of dirt and scale by hammering on the outside of the pipe and blowing out the loose dirt and scale Before initial start up be sure that all of...

Page 7: ...securing in place OPTIONAL ECONOMIZER MOTORIZED DAMPER RAIN HOOD The instruction for the optional economizer motorized damper rain hood can be found in form 44 320 2 Use these instructions when field...

Page 8: ...FIG 9 ENTHALPY SETPOINT ADJUSTMENT 530 18 N6Y 8 Unitary Products Group...

Page 9: ...6 0 43 3 COMPRESSOR Qty Per Unit 10 TON TANDEM 1 2 5 TON HERMETIC 1 AIR FILTERS QUANTITY PER UNIT 16 X 20 X 2 4 QUANTITY PER UNIT 16 X 25 X 2 4 QUANTITY PER UNIT 18 X 24 X 2 5 TOTAL FACE AREA sq ft 15...

Page 10: ...84 9 100 460 3 60 19 2 124 9 6 62 1 2 1 5 7 2 42 4 50 575 3 60 15 4 100 7 7 50 1 2 0 5 5 9 33 9 40 DCG240 208 230 3 60 38 4 248 38 4 248 1 4 1 4 2 7 5 21 0 19 4 115 1 111 6 125 460 3 60 19 2 124 19 2...

Page 11: ...ic meters gas meters regulators and relief equip R E T U R N A I R S U P P L Y A I R B O T T O M S U P P L Y A N D R E T U R N A I R O P E N I N G S S e e N o t e B P O W E R W I R I N G E N T R Y A C...

Page 12: ...NOTE These weights are with economizer and the largest blower motor available UNIT 6 POINT LOADS LBS TOTAL A B C D E F 180 2300 351 367 392 416 399 375 240 2500 334 350 426 502 481 407 NOTE These weig...

Page 13: ...7 3 0 2 7 0 4 3 5 3 1 915 5 0 1 1 2 6 2 4 0 8 3 1 2 8 0 5 3 6 3 2 0 2 4 1 3 7 965 4 0 1 2 2 7 2 5 0 9 3 2 2 9 0 6 3 7 3 3 0 4 4 4 3 9 0 2 5 0 4 5 980 3 5 1 3 2 9 2 6 1 0 3 4 3 0 0 7 3 8 3 4 0 5 4 5 4...

Page 14: ...4 1 1 5 0 4 2 0 6 5 9 5 0 0 1 6 7 5 7 950 3 5 1 7 4 2 3 6 1 3 5 1 4 3 0 8 6 0 5 1 0 2 6 9 5 8 965 2 5 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 0 1 8 5 7 1 995 2 0 2 1 4 6 3 9 1 6 5 5 4 7 1 1 6...

Page 15: ...65 1190 BK80 7 75 7 4 1 BX68 69 8 1 20 TON Stan dard 870 1025 7 5 213T 89 1VP68 6 75 5 5 6 52 1 3 8 BK120 11 75 11 4 1 3 16 BX83 84 8 1 High Speed Access 950 1120 BK110 10 75 10 4 1 3 16 BX81 81 8 1 1...

Page 16: ...rating efficiency ECONOMIZER SINGLE OR DUAL WITH POWER EXHAUST This system operates as specified above with one addition The power exhaust motor is energized whenever the economizer is chosen by the e...

Page 17: ...here are two separate gas valves in the furnace Each valve contains a main and a redundant valve The redundant valves are located upstream of the main gas valves Should either or both of the main gas...

Page 18: ...units If gas pressure is outside these limits contact the local gas utility for corrective action MANIFOLD GAS PRESSURE ADJUSTMENT Small adjustments to the high fire gas flow may be made by turning th...

Page 19: ...within the limitations shown in the Applications Data Table 2 Pulleys can be adjusted in half turn increments 3 The tension on the belt should be adjusted as shown in the Belt Adjustment figure Start...

Page 20: ...2 With the furnace turned on measure the time needed for one revolution of the hand on the smallest dial on the meter A typical gas meter usually has a 1 2 or a 1 cubic foot test dial 3 Using the numb...

Page 21: ...E Exercise care when cleaning the coil so that the coil fins are not damaged Do not permit the hot condenser air discharge to be obstructed by overhanging structures of shrubs BURNER PILOT Periodicall...

Page 22: ...tat fan switch set to AUTO a Set fan switch to ON If blower motor runs go to Step f If it does not check to see if line voltage is being supplied to the contacts of the contactor M3 and if the contact...

Page 23: ...T CHECKOUT b Check all wiring between the ignitor control and the gas valve Check to make sure the ground connections are intact c If the wiring is intact check for 24 volts across terminals PV and CO...

Page 24: ...and information from OUR current parts list for this unit are available to your servicing contractor through our local distributor The name and address of our nearest distributor may be obtained by co...

Reviews: