CHECKING SUPPLY AIR CFM

To check the supply air CFM after the initial balancing has
been completed:

1.

Remove the two ¼ inch dot plugs in the duct panel. 

2.

Insert at least 8 inches of ¼ inch tubing into each of 
these holes for sufficient penetration into the airflow on 
both sides of the indoor coil.

3.

Using an inclined manometer, determine the pressure 
drop across the evaporator coil. 

4.

Knowing the pressure drop across the coil, the actual 
CFM through the unit can be determined from Table 5.

After readings have been obtained, remove the tubes and
reinstall the two ¼ inch plugs removed in Step 1.

TABLE 4: ELECTRICAL DATA

SIZE

(TONS)

MODEL

POWER

COMPRESSOR

(EACH)

OD FAN

MOTORS

(EACH)

SUPPLY

BLOWER

MOTOR

MCA

1

(AMPS)

MOCP

2

(AMPS)

MAX. FUSE

3

SIZE

(AMPS)

RLA

LRA

MCC

036

(3.0)

DEB

380/415-3-50

6.7

39.0

9.5

1.0

1.8

11.2

15

15

048

(4.0)

DEB

380/415-3-50

8.7

66.5

12.5

1.0

3.2

15.1

20

20

060

(5.0)

DEB

380/415-3-50

10.4

73.0

13.0

1.0

2.7

15.7

25

25

1.

Minimum Circuit Ampacity.

2.

Maximum Over Current Protection per standard UL 1995.

3.

Fuse or HACR circuit breaker size installed at factory or field installed.

Failure to properly adjust the total system air quan-
tity can result in extensive system damage.

Summary of Contents for D1EB036

Page 1: ...T PARTS 3 SEQUENCE OF OPERATION 14 MAINTENANCE 14 See following pages for a complete Table of Contents NOTES CAUTIONS AND WARNINGS The installer should pay particular attention to the words NOTE CAUTI...

Page 2: ...4 2 TYPICAL FIELD WIRING DIAGRAM 7 3 UNIT DIMENSIONS 13 4 TYPICAL WIRING DIAGRAM 3 4 TON 380 415 3 50 POWER SUPPLY 15 5 TYPICAL WIRING DIAGRAM 5 TON 380 415 3 50 POWER SUPPLY 16 6 TYPICAL WIRING DIAGR...

Page 3: ...an Electrical Code Part 1 C22 1 latest editions 2 Local plumbing and waste water codes and other appli cable local codes Refer to Table 1 for unit application data If components are to be added to a u...

Page 4: ...nces for proper operation and service Refer to Figure 3 for the clearances required for combustion construction servicing and proper unit opera tion DUCT WORK These units are adaptable to downflow use...

Page 5: ...ating and cooling CONDENSATE DRAIN A condensate trap is required to be installed in the conden sate drain The plumbing must conform to local codes Use a sealing compound on male pipe threads Install t...

Page 6: ...croll 1 spd Scroll 1 spd Quantity 1 1 1 CONDENSER COIL DATA Face area m ft 0 77 8 3 1 47 15 8 1 47 15 8 Rows 1 1 2 Fins per cm in 7 88 20 6 30 16 7 88 20 Tube diameter mm in 10 0 375 10 0 375 10 0 375...

Page 7: ...diagram Electrical line must be sized properly to carry the load Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused Refer to Figure 2 for typic...

Page 8: ...termined from Table 5 After readings have been obtained remove the tubes and reinstall the two inch plugs removed in Step 1 TABLE 4 ELECTRICAL DATA SIZE TONS MODEL POWER COMPRESSOR EACH OD FAN MOTORS...

Page 9: ...02 7 47 0 03 9 96 0 04 12 45 0 05 14 95 0 06 17 44 0 07 19 93 0 08 22 42 0 09 24 91 0 1 7 47 0 03 7 47 0 03 9 96 0 04 9 96 0 04 9 96 0 04 12 45 0 05 12 45 0 05 12 45 0 05 14 95 0 06 060 5 0 DEB 0 71 1...

Page 10: ...0 7 11 2 11 8 12 3 15 0 17 6 18 9 20 2 105 6 7 7 1 7 4 7 7 8 1 8 4 8 8 12 4 16 0 17 8 19 6 110 5 0 5 2 9 7 14 3 16 6 18 9 115 7 1 12 6 15 4 18 2 TABLE 7 D1EB036 SUPERHEAT CHARGING METRIC OUTDOOR TEMPE...

Page 11: ...1 16 3 19 6 21 2 22 8 100 5 4 6 9 8 5 10 0 13 6 17 3 19 1 20 9 105 5 9 6 9 11 0 15 0 17 0 19 0 110 8 3 12 6 14 8 17 0 115 5 6 10 3 12 7 15 1 TABLE 9 D1EB048 SUPERHEAT CHARGING METRIC OUTDOOR TEMPERATU...

Page 12: ...5 5 9 8 3 10 7 13 1 16 7 20 4 22 2 24 0 100 6 4 8 2 10 1 13 2 16 3 17 9 19 5 105 5 8 7 0 9 6 12 3 13 6 14 9 110 6 1 8 2 9 3 10 4 115 5 8 TABLE 11 D1EB060 SUPERHEAT CHARGING METRIC OUTDOOR TEMPERATURE...

Page 13: ...92 7 211 12 287 5217 21 16 7 5 1 137 OO GLPHQVLRQV DUH LQ LQFKHV 7KH DUH VXEMHFW WR FKDQJH ZLWKRXW QRWLFH HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW 21 16 5 2 27720 6833 5 23 1 1 27720 5 7851...

Page 14: ...K1 relay will open and de energize the indoor blower motor SECURE OWNER S APPROVAL When the system is functioning properly secure the owner s approval Show the owner the location of all disconnect sw...

Page 15: ...173858 YIM A 0306 Unitary Products Group 15 FIGURE 3 TYPICAL WIRING DIAGRAM 3 4 TON 380 415 3 50 POWER SUPPLY...

Page 16: ...173858 YIM A 0306 16 Unitary Products Group FIGURE 4 TYPICAL WIRING DIAGRAM 5 TON 380 415 3 50 POWER SUPPLY...

Page 17: ...L CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT 2 CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SER VICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DAN GEROUS OPERATION IF ANY OF THE...

Page 18: ...173858 YIM A 0306 18 Unitary Products Group...

Page 19: ...173858 YIM A 0306 Unitary Products Group 19...

Page 20: ...ubject to change without notice Printed in U S A 173858 YIM A 0306 Copyright 2006 by Unitary Products Group All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive 7306...

Reviews: