background image

173858-YIM-A-0306

Unitary Products Group

11

TABLE 8:

D1EB048 SUPERHEAT CHARGING (IMPERIAL)

OUTDOOR

TEMPERATURE

(°F)

SUPERHEAT AT COMPRESSOR SUCTION (°F)

AIRFLOW = 1,800 CFM

INDOOR WB TEMPERATURE (°F)

55

57

59

61

63

65

67

69

71

73

75

65

19.9 

21.0 22.1 23.3 24.4 25.6 26.7 28.0 29.3 30.0 30.7 

70

16.5 

17.9 19.2 20.6 22.0 23.4 24.8 26.3 27.8 28.6 29.4 

75

13.1 

14.7 16.3 18.0 19.6 21.3 22.9 24.6 26.3 27.2 28.1 

80

9.7 11.6 13.4 15.3 17.2 19.1 21.0 22.9 24.8 25.8 26.8 

85

6.3 8.4 10.5 12.7 14.8 17.0 19.1 21.2 23.3 24.4 25.5 

90

-

5.7  7.8  9.9  11.9 14.0 16.1 18.8 21.5 22.8 24.1 

95

-

-

5.0  7.0  9.1  11.1 13.1 16.3 19.6 21.2 22.8 

100

-

-

-

5.4  6.9  8.5  10.0 13.6 17.3 19.1 20.9 

105

-

-

-

-

-

5.9 6.9 11.0 

15.0 

17.0 

19.0 

110

-

-

-

-

-

-

-

8.3 12.6 14.8 17.0 

115

-

-

-

-

-

-

-

5.6 10.3 12.7 15.1 

TABLE 9:

D1EB048 SUPERHEAT CHARGING (METRIC)

OUTDOOR

TEMPERATURE

(°C)

SUPERHEAT AT COMPRESSOR SUCTION (°C)

AIRFLOW = 0.85 M

3

/S

INDOOR WB TEMPERATURE (°C)

13

14

15

16

17

18

19

21

22

23

24

18

11.0 

11.7 

12.3 12.9 13.6 14.2 14.8 15.6 16.3 16.7 17.0 

21

9.1 

9.9 

10.7 11.5 12.2 13.0 13.8 14.6 15.5 15.9 16.3 

24

7.3 

8.2 9.1 10.0 10.9 11.8 12.7 13.7 14.6 15.1 15.6 

27

5.4 

6.4 7.5  8.5  9.6  10.6 11.7 12.7 13.8 14.3 14.9 

29

3.5 

4.7 

5.9 7.0 8.2 9.4 10.6 

11.8 

13.0 

13.6 

14.1 

32

-

3.2 

4.3 5.5 6.6 7.8 8.9 10.4 

11.9 

12.7 

13.4 

35

-

-

2.8 3.9 5.0 6.2 7.3 9.1 10.9 

11.8 

12.7 

38

-

-

-

3.0 3.9 4.7 5.6 7.6 9.6 10.6 

11.6 

41

-

-

-

-

-

3.3 3.9 6.1 8.3 9.4 10.5 

43

-

-

-

-

-

-

-

4.6 

7.0 

8.2 

9.5 

46

-

-

-

-

-

-

-

3.1 

5.7 

7.1 

8.4 

Summary of Contents for D1EB036

Page 1: ...T PARTS 3 SEQUENCE OF OPERATION 14 MAINTENANCE 14 See following pages for a complete Table of Contents NOTES CAUTIONS AND WARNINGS The installer should pay particular attention to the words NOTE CAUTI...

Page 2: ...4 2 TYPICAL FIELD WIRING DIAGRAM 7 3 UNIT DIMENSIONS 13 4 TYPICAL WIRING DIAGRAM 3 4 TON 380 415 3 50 POWER SUPPLY 15 5 TYPICAL WIRING DIAGRAM 5 TON 380 415 3 50 POWER SUPPLY 16 6 TYPICAL WIRING DIAGR...

Page 3: ...an Electrical Code Part 1 C22 1 latest editions 2 Local plumbing and waste water codes and other appli cable local codes Refer to Table 1 for unit application data If components are to be added to a u...

Page 4: ...nces for proper operation and service Refer to Figure 3 for the clearances required for combustion construction servicing and proper unit opera tion DUCT WORK These units are adaptable to downflow use...

Page 5: ...ating and cooling CONDENSATE DRAIN A condensate trap is required to be installed in the conden sate drain The plumbing must conform to local codes Use a sealing compound on male pipe threads Install t...

Page 6: ...croll 1 spd Scroll 1 spd Quantity 1 1 1 CONDENSER COIL DATA Face area m ft 0 77 8 3 1 47 15 8 1 47 15 8 Rows 1 1 2 Fins per cm in 7 88 20 6 30 16 7 88 20 Tube diameter mm in 10 0 375 10 0 375 10 0 375...

Page 7: ...diagram Electrical line must be sized properly to carry the load Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused Refer to Figure 2 for typic...

Page 8: ...termined from Table 5 After readings have been obtained remove the tubes and reinstall the two inch plugs removed in Step 1 TABLE 4 ELECTRICAL DATA SIZE TONS MODEL POWER COMPRESSOR EACH OD FAN MOTORS...

Page 9: ...02 7 47 0 03 9 96 0 04 12 45 0 05 14 95 0 06 17 44 0 07 19 93 0 08 22 42 0 09 24 91 0 1 7 47 0 03 7 47 0 03 9 96 0 04 9 96 0 04 9 96 0 04 12 45 0 05 12 45 0 05 12 45 0 05 14 95 0 06 060 5 0 DEB 0 71 1...

Page 10: ...0 7 11 2 11 8 12 3 15 0 17 6 18 9 20 2 105 6 7 7 1 7 4 7 7 8 1 8 4 8 8 12 4 16 0 17 8 19 6 110 5 0 5 2 9 7 14 3 16 6 18 9 115 7 1 12 6 15 4 18 2 TABLE 7 D1EB036 SUPERHEAT CHARGING METRIC OUTDOOR TEMPE...

Page 11: ...1 16 3 19 6 21 2 22 8 100 5 4 6 9 8 5 10 0 13 6 17 3 19 1 20 9 105 5 9 6 9 11 0 15 0 17 0 19 0 110 8 3 12 6 14 8 17 0 115 5 6 10 3 12 7 15 1 TABLE 9 D1EB048 SUPERHEAT CHARGING METRIC OUTDOOR TEMPERATU...

Page 12: ...5 5 9 8 3 10 7 13 1 16 7 20 4 22 2 24 0 100 6 4 8 2 10 1 13 2 16 3 17 9 19 5 105 5 8 7 0 9 6 12 3 13 6 14 9 110 6 1 8 2 9 3 10 4 115 5 8 TABLE 11 D1EB060 SUPERHEAT CHARGING METRIC OUTDOOR TEMPERATURE...

Page 13: ...92 7 211 12 287 5217 21 16 7 5 1 137 OO GLPHQVLRQV DUH LQ LQFKHV 7KH DUH VXEMHFW WR FKDQJH ZLWKRXW QRWLFH HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW 21 16 5 2 27720 6833 5 23 1 1 27720 5 7851...

Page 14: ...K1 relay will open and de energize the indoor blower motor SECURE OWNER S APPROVAL When the system is functioning properly secure the owner s approval Show the owner the location of all disconnect sw...

Page 15: ...173858 YIM A 0306 Unitary Products Group 15 FIGURE 3 TYPICAL WIRING DIAGRAM 3 4 TON 380 415 3 50 POWER SUPPLY...

Page 16: ...173858 YIM A 0306 16 Unitary Products Group FIGURE 4 TYPICAL WIRING DIAGRAM 5 TON 380 415 3 50 POWER SUPPLY...

Page 17: ...L CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT 2 CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SER VICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DAN GEROUS OPERATION IF ANY OF THE...

Page 18: ...173858 YIM A 0306 18 Unitary Products Group...

Page 19: ...173858 YIM A 0306 Unitary Products Group 19...

Page 20: ...ubject to change without notice Printed in U S A 173858 YIM A 0306 Copyright 2006 by Unitary Products Group All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive 7306...

Reviews: