Unitary Products Group

3

GENERAL

Model D1EB units are factory assembled cooling only air con-
ditioners designed for outdoor installation on a rooftop or a
slab.

The units are completely assembled on rigid, but easily
removable base rails. All piping, refrigerant charge, and elec-
trical wiring is factory installed and tested. The units require
only electric power and duct connections at the point of instal-
lation.

INSPECTION

As soon as a unit is received, it should be inspected for possi-
ble damage during transit. If damage is evident, the extent of
the damage should be noted on the carrier's freight bill. A
separate request for inspection by the carrier's agent should

be made in writing. Refer to Form 50.15-NM for additional
information.

REFERENCE

Additional information on the design, installation, operation
and service of this equipment is available in the following ref-
erence forms:

173858 - General Installation

036-21686-001 - Technical Guide

REPLACEMENT PARTS

Refer to Replacement Parts Manual for complete listing of
replacement parts on this equipment.

INSTALLATION

LIMITATIONS

These units must be installed in accordance with the follow-
ing national and local safety codes.

1.

National Electrical Code ANSI/NFPS No. 70 or Canadian 
Electrical Code Part 1, C22.1 (latest editions).

2.

Local plumbing and waste water codes and other appli-
cable local codes.

Refer to Table 1 for unit application data.

If components are to be added to a unit to meet local codes,
they are to be installed at the dealer's and/or the customer's
expense.

Size of unit for proposed installation should be based on heat
loss/heat gain calculations made in accordance with industry
recognized procedures identified by the Air Conditioning
Contractors of America.

LOCATION

Use the following guidelines to select a suitable location for
these units.

1.

Unit is designed for outdoor installation only.

2.

Condenser must have an unlimited supply of air. Where 
a choice of location is possible, position unit on either 
north or east side of building.

3.

For ground level installation, a level pad or slab should 
be used. The thickness and size of the pad or slab used 

D

1

E

B

A

PRODUCT NOMENCLATURE

PRODUCT GENERATION

1 = NEW or Current Design 

PRODUCT CATEGORY

D = Single Package Air Conditioner 

(Air Cooled) 

PRODUCT IDENTIFIER

EB

3

0

6

5

0

FACTORY

INSTALLED ELECTRIC HEAT

A = No Electric Heat Installed 

VOLTAGE CODE 

50 = 380/415-3-50 

NOMINAL COOLING

CAPACITY (MBH)

036 = 36,000 BTUH 
048 = 48,000 BTUH 
060 = 60,000 BTUH 

TABLE 1:

UNIT APPLICATION DATA

Wet Bulb Temperature (°C) of Air on
Evaporator Coil,        Min. / Max.

14 / 22

Dry Bulb Temperature (°C) of Air on

Condenser Coil,        Min.

1

 / Max.

1.

A low ambient accessory is available for operation 
down to 0°F.

7 / 49

Summary of Contents for D1EB036

Page 1: ...T PARTS 3 SEQUENCE OF OPERATION 14 MAINTENANCE 14 See following pages for a complete Table of Contents NOTES CAUTIONS AND WARNINGS The installer should pay particular attention to the words NOTE CAUTI...

Page 2: ...4 2 TYPICAL FIELD WIRING DIAGRAM 7 3 UNIT DIMENSIONS 13 4 TYPICAL WIRING DIAGRAM 3 4 TON 380 415 3 50 POWER SUPPLY 15 5 TYPICAL WIRING DIAGRAM 5 TON 380 415 3 50 POWER SUPPLY 16 6 TYPICAL WIRING DIAGR...

Page 3: ...an Electrical Code Part 1 C22 1 latest editions 2 Local plumbing and waste water codes and other appli cable local codes Refer to Table 1 for unit application data If components are to be added to a u...

Page 4: ...nces for proper operation and service Refer to Figure 3 for the clearances required for combustion construction servicing and proper unit opera tion DUCT WORK These units are adaptable to downflow use...

Page 5: ...ating and cooling CONDENSATE DRAIN A condensate trap is required to be installed in the conden sate drain The plumbing must conform to local codes Use a sealing compound on male pipe threads Install t...

Page 6: ...croll 1 spd Scroll 1 spd Quantity 1 1 1 CONDENSER COIL DATA Face area m ft 0 77 8 3 1 47 15 8 1 47 15 8 Rows 1 1 2 Fins per cm in 7 88 20 6 30 16 7 88 20 Tube diameter mm in 10 0 375 10 0 375 10 0 375...

Page 7: ...diagram Electrical line must be sized properly to carry the load Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused Refer to Figure 2 for typic...

Page 8: ...termined from Table 5 After readings have been obtained remove the tubes and reinstall the two inch plugs removed in Step 1 TABLE 4 ELECTRICAL DATA SIZE TONS MODEL POWER COMPRESSOR EACH OD FAN MOTORS...

Page 9: ...02 7 47 0 03 9 96 0 04 12 45 0 05 14 95 0 06 17 44 0 07 19 93 0 08 22 42 0 09 24 91 0 1 7 47 0 03 7 47 0 03 9 96 0 04 9 96 0 04 9 96 0 04 12 45 0 05 12 45 0 05 12 45 0 05 14 95 0 06 060 5 0 DEB 0 71 1...

Page 10: ...0 7 11 2 11 8 12 3 15 0 17 6 18 9 20 2 105 6 7 7 1 7 4 7 7 8 1 8 4 8 8 12 4 16 0 17 8 19 6 110 5 0 5 2 9 7 14 3 16 6 18 9 115 7 1 12 6 15 4 18 2 TABLE 7 D1EB036 SUPERHEAT CHARGING METRIC OUTDOOR TEMPE...

Page 11: ...1 16 3 19 6 21 2 22 8 100 5 4 6 9 8 5 10 0 13 6 17 3 19 1 20 9 105 5 9 6 9 11 0 15 0 17 0 19 0 110 8 3 12 6 14 8 17 0 115 5 6 10 3 12 7 15 1 TABLE 9 D1EB048 SUPERHEAT CHARGING METRIC OUTDOOR TEMPERATU...

Page 12: ...5 5 9 8 3 10 7 13 1 16 7 20 4 22 2 24 0 100 6 4 8 2 10 1 13 2 16 3 17 9 19 5 105 5 8 7 0 9 6 12 3 13 6 14 9 110 6 1 8 2 9 3 10 4 115 5 8 TABLE 11 D1EB060 SUPERHEAT CHARGING METRIC OUTDOOR TEMPERATURE...

Page 13: ...92 7 211 12 287 5217 21 16 7 5 1 137 OO GLPHQVLRQV DUH LQ LQFKHV 7KH DUH VXEMHFW WR FKDQJH ZLWKRXW QRWLFH HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW 21 16 5 2 27720 6833 5 23 1 1 27720 5 7851...

Page 14: ...K1 relay will open and de energize the indoor blower motor SECURE OWNER S APPROVAL When the system is functioning properly secure the owner s approval Show the owner the location of all disconnect sw...

Page 15: ...173858 YIM A 0306 Unitary Products Group 15 FIGURE 3 TYPICAL WIRING DIAGRAM 3 4 TON 380 415 3 50 POWER SUPPLY...

Page 16: ...173858 YIM A 0306 16 Unitary Products Group FIGURE 4 TYPICAL WIRING DIAGRAM 5 TON 380 415 3 50 POWER SUPPLY...

Page 17: ...L CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT 2 CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SER VICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DAN GEROUS OPERATION IF ANY OF THE...

Page 18: ...173858 YIM A 0306 18 Unitary Products Group...

Page 19: ...173858 YIM A 0306 Unitary Products Group 19...

Page 20: ...ubject to change without notice Printed in U S A 173858 YIM A 0306 Copyright 2006 by Unitary Products Group All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive 7306...

Reviews: