TABLE 6:

D1EB036 SUPERHEAT CHARGING (IMPERIAL)

OUTDOOR

TEMPERATURE

(°F)

SUPERHEAT AT COMPRESSOR SUCTION (°F)

AIRFLOW = 1,300 CFM

INDOOR WB TEMPERATURE (°F)

55

57

59

61

63

65

67

69

71

73

75

65

21.1 

21.6 

22.1 22.7 23.2 23.8 24.3 25.3 26.4 26.9 27.4 

70

19.5 

20.0 

20.6 21.1 21.7 22.2 22.8 24.0 25.1 25.7 26.3 

75

17.9 

18.5 

19.0 19.6 20.2 20.7 21.3 22.6 23.9 24.6 25.2 

80

16.3 

16.9 

17.5 18.0 18.6 19.2 19.8 21.2 22.7 23.4 24.1 

85

14.7 

15.3 

15.9 16.5 17.1 17.7 18.3 19.9 21.4 22.2 23.0 

90

13.1 

13.8 

14.4 15.1 15.8 16.4 17.1 18.7 20.3 21.2 22.0 

95

11.5 

12.2 

12.9 13.7 14.4 15.2 15.9 17.6 19.3 20.1 20.9 

100

9.1 

9.6 

10.2 10.7 11.2 11.8 12.3 15.0 17.6 18.9 20.2 

105

6.7 

7.1 

7.4 7.7 8.1 8.4 8.8 12.4 

16.0 

17.8 

19.6 

110

-

-

-

-

-

5.0 5.2 9.7 14.3 

16.6 

18.9 

115

-

-

-

-

-

-

-

7.1 

12.6 

15.4 

18.2 

TABLE 7:

D1EB036 SUPERHEAT CHARGING (METRIC)

OUTDOOR

TEMPERATURE

(°C)

SUPERHEAT AT COMPRESSOR SUCTION (°C)

AIRFLOW = 0.61 M

3

/S

INDOOR WB TEMPERATURE (°C)

13

14

15

16

17

18

19

21

22

23

24

18

11.7 

12.0 

12.3 

12.6 

12.9 13.2 13.5 14.1 14.7 14.9 15.2 

21

10.8 

11.1 

11.4 

11.7 

12.1 12.4 12.7 13.3 14.0 14.3 14.6 

24

9.9 

10.3 

10.6 

10.9 

11.2 11.5 11.8 12.6 13.3 13.6 14.0 

27

9.1 

9.4 

9.7 

10.0 

10.4 10.7 11.0 11.8 12.6 13.0 13.4 

29

8.2 

8.5 

8.8 9.2 9.5  9.8  10.2 11.0 11.9 12.3 12.8 

32

7.3 

7.6 

8.0 8.4 8.8  9.1  9.5  10.4 11.3 11.8 12.2 

35

6.4 

6.8 

7.2 

7.6 

8.0 8.4 8.8 9.8 10.7 

11.2 

11.6 

38

5.0 

5.3 

5.6 

5.9 

6.2 6.5 6.8 8.3 9.8 10.5 

11.2 

41

3.7 

3.9 

4.1 

4.3 

4.5 4.7 4.9 6.9 8.9 9.9 10.9 

43

-

-

-

-

-

2.8 2.9 5.4 7.9 9.2 10.5 

46

-

-

-

-

-

-

-

4.0 7.0 8.6 10.1 

Summary of Contents for D1EB036

Page 1: ...T PARTS 3 SEQUENCE OF OPERATION 14 MAINTENANCE 14 See following pages for a complete Table of Contents NOTES CAUTIONS AND WARNINGS The installer should pay particular attention to the words NOTE CAUTI...

Page 2: ...4 2 TYPICAL FIELD WIRING DIAGRAM 7 3 UNIT DIMENSIONS 13 4 TYPICAL WIRING DIAGRAM 3 4 TON 380 415 3 50 POWER SUPPLY 15 5 TYPICAL WIRING DIAGRAM 5 TON 380 415 3 50 POWER SUPPLY 16 6 TYPICAL WIRING DIAGR...

Page 3: ...an Electrical Code Part 1 C22 1 latest editions 2 Local plumbing and waste water codes and other appli cable local codes Refer to Table 1 for unit application data If components are to be added to a u...

Page 4: ...nces for proper operation and service Refer to Figure 3 for the clearances required for combustion construction servicing and proper unit opera tion DUCT WORK These units are adaptable to downflow use...

Page 5: ...ating and cooling CONDENSATE DRAIN A condensate trap is required to be installed in the conden sate drain The plumbing must conform to local codes Use a sealing compound on male pipe threads Install t...

Page 6: ...croll 1 spd Scroll 1 spd Quantity 1 1 1 CONDENSER COIL DATA Face area m ft 0 77 8 3 1 47 15 8 1 47 15 8 Rows 1 1 2 Fins per cm in 7 88 20 6 30 16 7 88 20 Tube diameter mm in 10 0 375 10 0 375 10 0 375...

Page 7: ...diagram Electrical line must be sized properly to carry the load Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused Refer to Figure 2 for typic...

Page 8: ...termined from Table 5 After readings have been obtained remove the tubes and reinstall the two inch plugs removed in Step 1 TABLE 4 ELECTRICAL DATA SIZE TONS MODEL POWER COMPRESSOR EACH OD FAN MOTORS...

Page 9: ...02 7 47 0 03 9 96 0 04 12 45 0 05 14 95 0 06 17 44 0 07 19 93 0 08 22 42 0 09 24 91 0 1 7 47 0 03 7 47 0 03 9 96 0 04 9 96 0 04 9 96 0 04 12 45 0 05 12 45 0 05 12 45 0 05 14 95 0 06 060 5 0 DEB 0 71 1...

Page 10: ...0 7 11 2 11 8 12 3 15 0 17 6 18 9 20 2 105 6 7 7 1 7 4 7 7 8 1 8 4 8 8 12 4 16 0 17 8 19 6 110 5 0 5 2 9 7 14 3 16 6 18 9 115 7 1 12 6 15 4 18 2 TABLE 7 D1EB036 SUPERHEAT CHARGING METRIC OUTDOOR TEMPE...

Page 11: ...1 16 3 19 6 21 2 22 8 100 5 4 6 9 8 5 10 0 13 6 17 3 19 1 20 9 105 5 9 6 9 11 0 15 0 17 0 19 0 110 8 3 12 6 14 8 17 0 115 5 6 10 3 12 7 15 1 TABLE 9 D1EB048 SUPERHEAT CHARGING METRIC OUTDOOR TEMPERATU...

Page 12: ...5 5 9 8 3 10 7 13 1 16 7 20 4 22 2 24 0 100 6 4 8 2 10 1 13 2 16 3 17 9 19 5 105 5 8 7 0 9 6 12 3 13 6 14 9 110 6 1 8 2 9 3 10 4 115 5 8 TABLE 11 D1EB060 SUPERHEAT CHARGING METRIC OUTDOOR TEMPERATURE...

Page 13: ...92 7 211 12 287 5217 21 16 7 5 1 137 OO GLPHQVLRQV DUH LQ LQFKHV 7KH DUH VXEMHFW WR FKDQJH ZLWKRXW QRWLFH HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW 21 16 5 2 27720 6833 5 23 1 1 27720 5 7851...

Page 14: ...K1 relay will open and de energize the indoor blower motor SECURE OWNER S APPROVAL When the system is functioning properly secure the owner s approval Show the owner the location of all disconnect sw...

Page 15: ...173858 YIM A 0306 Unitary Products Group 15 FIGURE 3 TYPICAL WIRING DIAGRAM 3 4 TON 380 415 3 50 POWER SUPPLY...

Page 16: ...173858 YIM A 0306 16 Unitary Products Group FIGURE 4 TYPICAL WIRING DIAGRAM 5 TON 380 415 3 50 POWER SUPPLY...

Page 17: ...L CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT 2 CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SER VICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DAN GEROUS OPERATION IF ANY OF THE...

Page 18: ...173858 YIM A 0306 18 Unitary Products Group...

Page 19: ...173858 YIM A 0306 Unitary Products Group 19...

Page 20: ...ubject to change without notice Printed in U S A 173858 YIM A 0306 Copyright 2006 by Unitary Products Group All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive 7306...

Reviews: