173858-YIM-A-0306

12

Unitary Products Group

TABLE 10: D1EB060 SUPERHEAT CHARGING (IMPERIAL)

OUTDOOR

TEMPERATURE

(°F)

SUPERHEAT AT COMPRESSOR SUCTION (°F)

AIRFLOW = 2,000 CFM

INDOOR WB TEMPERATURE (°F)

55

57

59

61

63

65

67

69

71

73

75

65

21.9 

23.8 

25.7 27.6 29.4 31.3 33.2 34.2 35.1 35.6 36.1 

70

16.0 

18.4 

20.7 23.0 25.3 27.6 30.0 31.3 32.7 33.4 34.0 

75

10.1 

12.9 

15.7 18.4 21.2 23.9 26.7 28.5 30.2 31.1 32.0 

80

-

7.5 10.7 13.9 17.1 20.3 23.5 25.6 27.8 28.9 29.9 

85

-

-

5.6  9.3  12.9 16.6 20.2 22.8 25.3 26.6 27.9 

90

-

-

-

7.6  10.6 13.6 16.7 19.8 22.9 24.4 26.0 

95

-

-

-

5.9  8.3  10.7 13.1 16.7 20.4 22.2 24.0 

100

-

-

-

-

6.4  8.2  10.1 13.2 16.3 17.9 19.5 

105

-

-

-

-

-

5.8 7.0 9.6 12.3 

13.6 

14.9 

110

-

-

-

-

-

-

-

6.1 8.2 9.3 10.4 

115

-

-

-

-

-

-

-

-

-

-

5.8 

TABLE 11: D1EB060 SUPERHEAT CHARGING (METRIC)

OUTDOOR

TEMPERATURE

(°C)

SUPERHEAT AT COMPRESSOR SUCTION (°C)

AIRFLOW = 0.94 M

3

/S

INDOOR WB TEMPERATURE (°C)

13

14

15

16

17

18

19

21

22

23

24

18

12.2 

13.2 

14.3 

15.3 

16.4 17.4 18.4 19.0 19.5 19.8 20.0 

21

8.9 

10.2 

11.5 

12.8 

14.1 15.4 16.6 17.4 18.2 18.5 18.9 

24

5.6 

7.2 8.7 

10.2 

11.8 13.3 14.8 15.8 16.8 17.3 17.8 

27

-

4.1 5.9 7.7 9.5 11.3 13.0 14.2 15.4 16.0 16.6 

29

-

-

3.1 5.2 7.2  9.2  11.2 12.6 14.1 14.8 15.5 

32

-

-

-

4.2 5.9  7.6  9.3  11.0 12.7 13.6 14.4 

35

-

-

-

3.3 

4.6 5.9 7.3 9.3 11.3 

12.3 

13.3 

38

-

-

-

-

3.6 4.6 5.6 7.3 9.1 9.9 10.8 

41

-

-

-

-

-

3.2 3.9 5.4 6.8 7.6 8.3 

43

-

-

-

-

-

-

-

3.4 4.6 5.2 5.8 

46

-

-

-

-

-

-

-

-

-

-

3.2 

Summary of Contents for D1EB036

Page 1: ...T PARTS 3 SEQUENCE OF OPERATION 14 MAINTENANCE 14 See following pages for a complete Table of Contents NOTES CAUTIONS AND WARNINGS The installer should pay particular attention to the words NOTE CAUTI...

Page 2: ...4 2 TYPICAL FIELD WIRING DIAGRAM 7 3 UNIT DIMENSIONS 13 4 TYPICAL WIRING DIAGRAM 3 4 TON 380 415 3 50 POWER SUPPLY 15 5 TYPICAL WIRING DIAGRAM 5 TON 380 415 3 50 POWER SUPPLY 16 6 TYPICAL WIRING DIAGR...

Page 3: ...an Electrical Code Part 1 C22 1 latest editions 2 Local plumbing and waste water codes and other appli cable local codes Refer to Table 1 for unit application data If components are to be added to a u...

Page 4: ...nces for proper operation and service Refer to Figure 3 for the clearances required for combustion construction servicing and proper unit opera tion DUCT WORK These units are adaptable to downflow use...

Page 5: ...ating and cooling CONDENSATE DRAIN A condensate trap is required to be installed in the conden sate drain The plumbing must conform to local codes Use a sealing compound on male pipe threads Install t...

Page 6: ...croll 1 spd Scroll 1 spd Quantity 1 1 1 CONDENSER COIL DATA Face area m ft 0 77 8 3 1 47 15 8 1 47 15 8 Rows 1 1 2 Fins per cm in 7 88 20 6 30 16 7 88 20 Tube diameter mm in 10 0 375 10 0 375 10 0 375...

Page 7: ...diagram Electrical line must be sized properly to carry the load Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused Refer to Figure 2 for typic...

Page 8: ...termined from Table 5 After readings have been obtained remove the tubes and reinstall the two inch plugs removed in Step 1 TABLE 4 ELECTRICAL DATA SIZE TONS MODEL POWER COMPRESSOR EACH OD FAN MOTORS...

Page 9: ...02 7 47 0 03 9 96 0 04 12 45 0 05 14 95 0 06 17 44 0 07 19 93 0 08 22 42 0 09 24 91 0 1 7 47 0 03 7 47 0 03 9 96 0 04 9 96 0 04 9 96 0 04 12 45 0 05 12 45 0 05 12 45 0 05 14 95 0 06 060 5 0 DEB 0 71 1...

Page 10: ...0 7 11 2 11 8 12 3 15 0 17 6 18 9 20 2 105 6 7 7 1 7 4 7 7 8 1 8 4 8 8 12 4 16 0 17 8 19 6 110 5 0 5 2 9 7 14 3 16 6 18 9 115 7 1 12 6 15 4 18 2 TABLE 7 D1EB036 SUPERHEAT CHARGING METRIC OUTDOOR TEMPE...

Page 11: ...1 16 3 19 6 21 2 22 8 100 5 4 6 9 8 5 10 0 13 6 17 3 19 1 20 9 105 5 9 6 9 11 0 15 0 17 0 19 0 110 8 3 12 6 14 8 17 0 115 5 6 10 3 12 7 15 1 TABLE 9 D1EB048 SUPERHEAT CHARGING METRIC OUTDOOR TEMPERATU...

Page 12: ...5 5 9 8 3 10 7 13 1 16 7 20 4 22 2 24 0 100 6 4 8 2 10 1 13 2 16 3 17 9 19 5 105 5 8 7 0 9 6 12 3 13 6 14 9 110 6 1 8 2 9 3 10 4 115 5 8 TABLE 11 D1EB060 SUPERHEAT CHARGING METRIC OUTDOOR TEMPERATURE...

Page 13: ...92 7 211 12 287 5217 21 16 7 5 1 137 OO GLPHQVLRQV DUH LQ LQFKHV 7KH DUH VXEMHFW WR FKDQJH ZLWKRXW QRWLFH HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW 21 16 5 2 27720 6833 5 23 1 1 27720 5 7851...

Page 14: ...K1 relay will open and de energize the indoor blower motor SECURE OWNER S APPROVAL When the system is functioning properly secure the owner s approval Show the owner the location of all disconnect sw...

Page 15: ...173858 YIM A 0306 Unitary Products Group 15 FIGURE 3 TYPICAL WIRING DIAGRAM 3 4 TON 380 415 3 50 POWER SUPPLY...

Page 16: ...173858 YIM A 0306 16 Unitary Products Group FIGURE 4 TYPICAL WIRING DIAGRAM 5 TON 380 415 3 50 POWER SUPPLY...

Page 17: ...L CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT 2 CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SER VICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DAN GEROUS OPERATION IF ANY OF THE...

Page 18: ...173858 YIM A 0306 18 Unitary Products Group...

Page 19: ...173858 YIM A 0306 Unitary Products Group 19...

Page 20: ...ubject to change without notice Printed in U S A 173858 YIM A 0306 Copyright 2006 by Unitary Products Group All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive 7306...

Reviews: