background image

835965-UIM-C-0814

Johnson Controls Unitary Products

7

DEHUMIDIFICATION CONTROL

A dehumidification control accessory 2HU06700124 may be used with
variable speed air handlers or furnaces in high humidity areas. This
control works with the variable speed indoor unit to provide cooling at a
reduced air flow, lowering evaporator temperature and increasing latent
capacity. The humidistat in this control opens the humidistat contacts on
humidity rise. To install, refer to instructions packaged with the acces-
sory and Figures 7-8. Prior to the installation of the dehumidification
control, the jumper across the HUMIDISTAT terminals on the indoor
variable speed air handler or furnace CFM selection board must be
removed.

During cooling, if the relative humidity in the space is higher than the
desired set point of the dehumidification control, the variable speed
blower motor will operate at lower speed until the dehumidification con-
trol is satisfied. A 40-60% relative humidity level is recommended to
achieve optimum comfort.

If a dehumidification control is installed, it is recommended that a mini-
mum air flow of 325 cfm/ton be supplied at all times.

INDOOR CFM CONFIGURATION

For proper system operation the indoor CFM must be set properly. 

Refer to the Technical Guide for the outdoor unit for the recommended
air flow settings for each size condensing unit and matching indoor unit.

Set the cooling speed per the instructions for the air handler or furnace.
Verify the airflow. 

If installed as a communicating system (outdoor, indoor, and thermo-
stat), the system will automatically adjust to the optimal airflow settings.
These parameters can also be modified using the Touch Screen Com-
municating Control. Refer to the Touch Screen Communicating Control
owner’s manual for this procedure. Manual setting of the airflow on the
ID equipment is not necessary with the Touch Screen Communicating
Control.

 FIGURE 7:  

Communicating AC with Communicating Air Handler or 

Furnace

R

C

Y1

Y2

Touch Screen

Communicating

Control

Air Handler/Furnace

Communicating

Control

Air Conditioner

Communicating

Control

GND
or C

GND
or C

B-

R

A+

GND
or C

GND
or C

B-

R

A+

GND
or C

GND
or C

B-

R

A+

A0205-001

 FIGURE 8:  

Communicating AC with Non-Communicating Air Handler 

or Furnace using Communicating Interface Control

R

C

Y1

Y2

HUM

W2

DHUM

W

G

C

R

O

Y

Y2

HUM

W2

DHUM

W

G

C

R

O

Y

Y2

Touch Screen

Communicating

Control

Communicating

Indoor

Interface Control

Non-Communicating

Indoor Unit

Air Conditioner

Communicating

Control

Wire per

non-comm.

installation

manual

Assume that

connections

are from

thermostat

GND
or C

GND
or C

B-

R

A+

GND
or C

GND
or C

B-

R

A+

GND
or C

GND
or C

B-

R

A+

A0206-001

Summary of Contents for CZH

Page 1: ...tage Wiring Diagram 5 Ton 23 Two Stage Wiring Diagram 24 LIST OF TABLES R 410A Saturation Properties 18 TEST Input Functionality 19 Operational Mode Display 19 Status Code Display 19 Status Code Displ...

Page 2: ...taking the accumulated layer of hot air into the outdoor unit Provide adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 22 unit it is requi...

Page 3: ...tightened 4 Position the unit on the base provided LIQUID LINE FILTER DRIER The air conditioning unit s copper spun filter dryer is located on the liq uid line TXV INSTALLATIONS The following are the...

Page 4: ...d dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valves by wrapping a wet rag around it as shown in Figure 4 Heat Protection Also pro...

Page 5: ...liquid and vapor valves 10 Leak test all refrigerant piping connections SECTION IV EVACUATION 1 It will be necessary to evacuate the system to 500 microns or less If a leak is suspected leak test with...

Page 6: ...rol 2 Route low voltage four conductor shielded thermostat communica tions harness into junction box and connect to communications port on control board See Figure 6 Communications Harness Connec tion...

Page 7: ...set properly Refer to the Technical Guide for the outdoor unit for the recommended air flow settings for each size condensing unit and matching indoor unit Set the cooling speed per the instructions f...

Page 8: ...ELEC SINGLE STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor SINGLE STAGE AIR CONDITIONER External Humidistat Optional Open on Humidity Rise Y...

Page 9: ...mpressor Y2 Second Stage Compressor SINGLE STAGE AIR CONDITIONER External Humidistat Optional Open on Humidity Rise Optional 24VAC Electronic Air Cleaner Optional Y1 First Stage Compressor COM 24 Volt...

Page 10: ...must be set to GAS SINGLE STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor SINGLE STAGE AIR CONDITIONER External Humidistat Optional Open on Hu...

Page 11: ...of the C terminal 24 Volt common is optional when used with batteries Thermostat Installer Setup 0170 System Type must be set to 8 2 Heat 2 Cool Multistage Conventional Connection of the C terminal 24...

Page 12: ...umper to YES if humidistat is to be used ID MODELS TWO STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor 24VAC Humidifier Optional External Humi...

Page 13: ...lt Hot Y1 Single Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FURNACE Y Y2 Second or Full Stage Compressor HUM Dehumidification Open on Humidity Rise W Mo...

Page 14: ...YES if humidistat is to be used 24VAC Humidifier Optional External Humidistat Optional Open on Humidity Rise C 24 Volt Common R 24 Volt Hot Y First Stage Compressor Y2 Second Stage Compressor G Fan D...

Page 15: ...optional when used with batteries Thermostat Installer Setup 1 System Type must be set to 6 2 Heat 2 Cool Multistage Conventional COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage H...

Page 16: ...on of the C Terminal 24 Volt Common is optional when used with batteries COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage...

Page 17: ...n Properties 6 Subcooling temperature TC Saturated Temperature ST Liquid Temp T Add charge if the calculated subcooling temperature TC in Step 6 is lower than the recommended level Remove and recover...

Page 18: ...control includes a TEST input connector that can be used for vari ous testing functions during installation and service Table 2 summa rizes the behavior of the control when the two TEST pins are conne...

Page 19: ...ster signals present Control behavior with system master signals present 2 No response No response 2 Display compressor type TS Ultratech or single stage compressor Ignore LPS Bypass ASCD Reduce timer...

Page 20: ...o be reset when the thermostat is satisfied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seconds When the soft lockout c...

Page 21: ...s started following a high pressure switch fault the control will start a six hour timer based on accumulated compressor run time If the control senses another opening of the high pressure switch befo...

Page 22: ...ITCH OFM OUTDOOR FAN MOTOR 562158 UWD B 0313 WIRING DIAGRAM S C R FAN MOTOR GND 6 3 5 PLUG 4 2 1 S C R COMPRESSOR USE COPPER CONDUCTORS ONLY 208 230VAC 60 Hz 1 PHASE SUPPLY GRN BRN RED BLK RED BRN BLK...

Page 23: ...UNICATION CONNECTIONS BLU PNK C M M1 M2 R C Y1 Y2 BLU PNK BRN PNK BRN PNK YEL BLK RED GRY AMB SENS HPS LPS WHT WHT CC RED SEE INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE CONNECTIONS BLK RED GRN YEL 3 BL...

Page 24: ...CATION CONNECTIONS BLU PNK C M M1 M2 R C Y1 Y2 BLU PNK BRN PNK BRN PNK YEL BLU YEL BLK RED GRY AMB SENS HPS LPS WHT WHT CC BLU RED SEE INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE CONNECTIONS 2 STAGE SOL...

Page 25: ...f applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is conn...

Page 26: ...th the owner s manual Explain thermostat use and programming if applicable to owner Cycle Test Operate the unit through several heating cycles if applicable from the thermostat noting and correcting a...

Reviews: