background image

835965-UIM-C-0814

4

Johnson Controls Unitary Products

PIPING CONNECTIONS

The outdoor condensing unit must be connected to the indoor evapora-
tor coil using field supplied refrigerant grade copper tubing that is inter-
nally clean and dry. Units should be installed only with the tubing sizes
for approved system combinations as specified in tabular data sheet.
The charge given is applicable for total tubing lengths up to 15 feet. See
Application Data Part Number 247077 for installing tubing of longer
lengths and elevation differences.

PRECAUTIONS DURING LINE INSTALLATION

1. Install the lines with as few bends as possible. Care must be taken

not to damage the couplings or kink the tubing. Use clean hard
drawn copper tubing where no appreciable amount of bending
around obstruction is necessary. If soft copper must be used, care
must be taken to avoid sharp bends which may cause a restriction.

2. The lines should be installed so that they will not obstruct service

access to the coil, air handling system, or filter.

3. Care must also be taken to isolate the refrigerant lines to minimize

noise transmission from the equipment to the structure.

4. The vapor line must be insulated with a minimum of 1/2" foam rubber

insulation (Armaflex or equivalent). Liquid lines that will be exposed
to direct sunlight and/or high temperatures must also be insulated.

5. Tape and suspend the refrigerant lines as shown. DO NOT allow

tube metal-to-metal contact. See Figure 2 "Tubing Hanger".

6. Use PVC piping as a conduit for all underground installations as

shown in Figure 3 "Underground Installation". Buried lines should be
kept as short as possible to minimize the build up of liquid refrigerant
in the vapor line during long periods of shutdown

7. Pack fiberglass insulation and a sealing material such as permagum

around refrigerant lines where they penetrate a wall to reduce vibra-
tion and to retain some flexibility.

8. See application part number 247077 for additional piping informa-

tion.

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-to-copper
and should be brazed with a phosphorous-copper alloy material such
as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units
have reusable service valves on both the liquid and vapor connections.
The total system refrigerant charge is retained within the outdoor unit
during shipping and installation. The reusable service valves are pro-
vided to evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate precau-
tions to ensure an internally clean and dry system.

PRECAUTIONS DURING BRAZING SERVICE VALVE

Precautions should be taken to prevent heat damage to service valves
by wrapping a wet rag around it as shown in Figure 4 "Heat Protection".
Also, protect all painted surfaces, insulation, and plastic base during
brazing. After brazing, cool joint with wet rag.

The valve can be opened by removing the plunger cap and fully insert-
ing a hex wrench into the stem and backing out counter-clockwise until
valve stem just touches the chamfered retaining wall.

Connect the refrigerant lines using the following procedure:

1. Refer to the Tabular Data Sheet for proper vapor and liquid line siz-

ing.

2. Remove the cap and Schrader core from both the liquid and vapor

service valve service ports at the outdoor unit. Connect low pressure
nitrogen to the liquid line service port.

This system uses R-410A refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.
Gauge sets, hoses, refrigerant containers, and recovery systems
must be designed to handle R-410A. If you are unsure, consult the
equipment manufacturer.

Never install a suction-line filter drier in the liquid line of an R-410A
system. Failure to follow this warning can cause a fire, injury or
death.

Using a larger than specified line size could result in oil return prob-
lems. Using too small a line will result in loss of capacity and other
problems caused by insufficient refrigerant flow. Slope horizontal
vapor lines at least 1" every 20 feet toward the outdoor unit to facili-
tate proper oil return.

 FIGURE 2:  

Tubing Hanger

NOTICE

A0151-001

SHEET METAL HANGER

LIQUID
LINE

INCORRECT

CORRECT

INSULATED VAPOR LINE

TAPE

 FIGURE 3:  

Underground Installation

 Dry nitrogen should always be supplied through the tubing while it
is being brazed, because the temperature is high enough to cause
oxidation of the copper unless an inert atmosphere is provided. The
flow of dry nitrogen should continue until the joint has cooled.
Always use a pressure regulator and safety valve to insure that only
low pressure dry nitrogen is introduced into the tubing. Only a small
flow is necessary to displace air and prevent oxidation.

This is not a backseating valve. The service access port has a
valve core. Opening or closing valve does not close service access
port.
 If the valve stem is backed out past the chamfered retaining wall,
the O-ring can be damaged causing leakage or system pressure
could force the valve stem out of the valve body possibly causing
personal injury.

Do not leave the system open to the atmosphere.  Unit damage
could occur due to moisture being absorbed by the POE oil in the
system.  This type of oil is highly susceptible to moisture absorp-
tion.

TO INDOOR COIL

TO OUTDOOR UNIT

LIQUID LINE

CAP

PVC
CONDUIT

INSULATED

VAPOR LINE

A0152-001

Summary of Contents for CZH

Page 1: ...tage Wiring Diagram 5 Ton 23 Two Stage Wiring Diagram 24 LIST OF TABLES R 410A Saturation Properties 18 TEST Input Functionality 19 Operational Mode Display 19 Status Code Display 19 Status Code Displ...

Page 2: ...taking the accumulated layer of hot air into the outdoor unit Provide adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 22 unit it is requi...

Page 3: ...tightened 4 Position the unit on the base provided LIQUID LINE FILTER DRIER The air conditioning unit s copper spun filter dryer is located on the liq uid line TXV INSTALLATIONS The following are the...

Page 4: ...d dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valves by wrapping a wet rag around it as shown in Figure 4 Heat Protection Also pro...

Page 5: ...liquid and vapor valves 10 Leak test all refrigerant piping connections SECTION IV EVACUATION 1 It will be necessary to evacuate the system to 500 microns or less If a leak is suspected leak test with...

Page 6: ...rol 2 Route low voltage four conductor shielded thermostat communica tions harness into junction box and connect to communications port on control board See Figure 6 Communications Harness Connec tion...

Page 7: ...set properly Refer to the Technical Guide for the outdoor unit for the recommended air flow settings for each size condensing unit and matching indoor unit Set the cooling speed per the instructions f...

Page 8: ...ELEC SINGLE STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor SINGLE STAGE AIR CONDITIONER External Humidistat Optional Open on Humidity Rise Y...

Page 9: ...mpressor Y2 Second Stage Compressor SINGLE STAGE AIR CONDITIONER External Humidistat Optional Open on Humidity Rise Optional 24VAC Electronic Air Cleaner Optional Y1 First Stage Compressor COM 24 Volt...

Page 10: ...must be set to GAS SINGLE STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor SINGLE STAGE AIR CONDITIONER External Humidistat Optional Open on Hu...

Page 11: ...of the C terminal 24 Volt common is optional when used with batteries Thermostat Installer Setup 0170 System Type must be set to 8 2 Heat 2 Cool Multistage Conventional Connection of the C terminal 24...

Page 12: ...umper to YES if humidistat is to be used ID MODELS TWO STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor 24VAC Humidifier Optional External Humi...

Page 13: ...lt Hot Y1 Single Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FURNACE Y Y2 Second or Full Stage Compressor HUM Dehumidification Open on Humidity Rise W Mo...

Page 14: ...YES if humidistat is to be used 24VAC Humidifier Optional External Humidistat Optional Open on Humidity Rise C 24 Volt Common R 24 Volt Hot Y First Stage Compressor Y2 Second Stage Compressor G Fan D...

Page 15: ...optional when used with batteries Thermostat Installer Setup 1 System Type must be set to 6 2 Heat 2 Cool Multistage Conventional COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage H...

Page 16: ...on of the C Terminal 24 Volt Common is optional when used with batteries COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage...

Page 17: ...n Properties 6 Subcooling temperature TC Saturated Temperature ST Liquid Temp T Add charge if the calculated subcooling temperature TC in Step 6 is lower than the recommended level Remove and recover...

Page 18: ...control includes a TEST input connector that can be used for vari ous testing functions during installation and service Table 2 summa rizes the behavior of the control when the two TEST pins are conne...

Page 19: ...ster signals present Control behavior with system master signals present 2 No response No response 2 Display compressor type TS Ultratech or single stage compressor Ignore LPS Bypass ASCD Reduce timer...

Page 20: ...o be reset when the thermostat is satisfied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seconds When the soft lockout c...

Page 21: ...s started following a high pressure switch fault the control will start a six hour timer based on accumulated compressor run time If the control senses another opening of the high pressure switch befo...

Page 22: ...ITCH OFM OUTDOOR FAN MOTOR 562158 UWD B 0313 WIRING DIAGRAM S C R FAN MOTOR GND 6 3 5 PLUG 4 2 1 S C R COMPRESSOR USE COPPER CONDUCTORS ONLY 208 230VAC 60 Hz 1 PHASE SUPPLY GRN BRN RED BLK RED BRN BLK...

Page 23: ...UNICATION CONNECTIONS BLU PNK C M M1 M2 R C Y1 Y2 BLU PNK BRN PNK BRN PNK YEL BLK RED GRY AMB SENS HPS LPS WHT WHT CC RED SEE INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE CONNECTIONS BLK RED GRN YEL 3 BL...

Page 24: ...CATION CONNECTIONS BLU PNK C M M1 M2 R C Y1 Y2 BLU PNK BRN PNK BRN PNK YEL BLU YEL BLK RED GRY AMB SENS HPS LPS WHT WHT CC BLU RED SEE INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE CONNECTIONS 2 STAGE SOL...

Page 25: ...f applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is conn...

Page 26: ...th the owner s manual Explain thermostat use and programming if applicable to owner Cycle Test Operate the unit through several heating cycles if applicable from the thermostat noting and correcting a...

Reviews: