INSPECTION

As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s delivery receipt. A separate request for
inspection by the carrier’s agent should be made in writing. See Local
Distributor for more information.

Requirements For Installing/Servicing R-410A Equipment

Gauge sets, hoses, refrigerant containers, and recovery systems
must be designed to handle the POE type oils and the higher
pressures of R-410A.

Manifold sets should be 800 PSIG high side and 250 PSIG low
side with 550 PSIG low side retard.

All hoses must have a 700 PSIG service pressure rating.

Leak detectors should be designed to detect HFC refrigerant.

Recovery equipment (including refrigerant recovery containers)
must be specifically designed to handle R-410A.

Do not use an R-22 TXV.

A liquid-line filter drier is required on every unit.

LIMITATIONS

The unit should be installed in accordance with all National, State, and
Local Safety Codes and the limitations listed below:

1. Limitations for the indoor unit, coil, and appropriate accessories

must also be observed.

2. Only variable speed air handlers or variable speed furnaces should

be used with these models.

3. The outdoor unit must not be installed with any duct work in the air

stream. The outdoor fan is the propeller type and is not designed to
operate against any additional external static pressure.

4. The maximum and minimum conditions for operation must be

observed to ensure a system that will give maximum performance
with minimum service.

5. For 16 SEER models only, the unit should not be operated at out-

door temperatures below 65° F without an approved low ambient
operation accessory kit installed.

6. The maximum allowable line length for this product is 75 feet.

SECTION III: UNIT INSTALLATION

LOCATION

Before starting the installation, select and check the suitability of the
location for both the indoor and outdoor unit. Observe all limitations and
clearance requirements.

The outdoor unit must have sufficient clearance for air entrance to the
condenser coil, for air discharge, and for service access. See Figure 1
"Typical Installation with Required Clearances".

If the unit is to be installed on a hot sun exposed roof or a paved
ground area that is seasonally hot, the unit should be raised sufficiently
above the roof or ground to avoid taking the accumulated layer of hot
air into the outdoor unit.

Provide adequate structural support.

ADD-ON REPLACEMENT/RETROFIT

When this unit is being used as a replacement for an R-22 unit, it is
required that the outdoor unit, indoor coil, and metering device all be
replaced. Line-set change out is also recommended. The following
steps should be performed in order to insure proper system operation
and performance. 

1. Change-out of the indoor coil to an approved R-410A coil with the

appropriate metering device.

2. Change-out of the line-set when replacing an R-22 unit with an 

R-410A unit is highly recommended to reduce cross-contamination
of oils and refrigerants. 

3. If change-out of the line set is not practical, then the following pre-

cautions should be taken.

Inspect the line set for kinks, sharp bends, or other restrictions,
and for corrosion.

Determine if there are any low spots which might be serving as oil
traps. 

Flush the line set with a commercially available flush kit to
remove as much of the existing oil and contaminants as possible. 

Install a suction line filter-drier to trap any remaining contami-
nants, and remove after 50 hours of operation. 

4. If the outdoor unit is being replaced due to a compressor burnout,

then installation of a 100% activated alumina suction-line filter drier
is required, in addition to the factory installed liquid-line drier. Oper-
ate the system for 10 hours. Monitor the suction drier pressure drop.
If the pressure drop exceeds 3 psig, replace both the suction-line
and liquid-line driers. After a total of 10 hours run time where the
suction-line pressure drop has not exceeded 3 psig, replace the liq-
uid line drier, and remove the suction-line drier. Never leave a suc-
tion-line drier in the system longer than 50 hours of run time.

Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service, or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer, or service agency.

This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.

R-410A systems operate at higher pressures than R-22 systems.
Do not use R-22 service equipment or components on R-410A
equipment. Service equipment 

Must Be Rated 

for R-410A.

For multiple unit installations, units must be spaced a minimum of
24 inches apart (coil face to coil face).

NOTICE

Summary of Contents for CZH

Page 1: ...tage Wiring Diagram 5 Ton 23 Two Stage Wiring Diagram 24 LIST OF TABLES R 410A Saturation Properties 18 TEST Input Functionality 19 Operational Mode Display 19 Status Code Display 19 Status Code Displ...

Page 2: ...taking the accumulated layer of hot air into the outdoor unit Provide adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 22 unit it is requi...

Page 3: ...tightened 4 Position the unit on the base provided LIQUID LINE FILTER DRIER The air conditioning unit s copper spun filter dryer is located on the liq uid line TXV INSTALLATIONS The following are the...

Page 4: ...d dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valves by wrapping a wet rag around it as shown in Figure 4 Heat Protection Also pro...

Page 5: ...liquid and vapor valves 10 Leak test all refrigerant piping connections SECTION IV EVACUATION 1 It will be necessary to evacuate the system to 500 microns or less If a leak is suspected leak test with...

Page 6: ...rol 2 Route low voltage four conductor shielded thermostat communica tions harness into junction box and connect to communications port on control board See Figure 6 Communications Harness Connec tion...

Page 7: ...set properly Refer to the Technical Guide for the outdoor unit for the recommended air flow settings for each size condensing unit and matching indoor unit Set the cooling speed per the instructions f...

Page 8: ...ELEC SINGLE STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor SINGLE STAGE AIR CONDITIONER External Humidistat Optional Open on Humidity Rise Y...

Page 9: ...mpressor Y2 Second Stage Compressor SINGLE STAGE AIR CONDITIONER External Humidistat Optional Open on Humidity Rise Optional 24VAC Electronic Air Cleaner Optional Y1 First Stage Compressor COM 24 Volt...

Page 10: ...must be set to GAS SINGLE STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor SINGLE STAGE AIR CONDITIONER External Humidistat Optional Open on Hu...

Page 11: ...of the C terminal 24 Volt common is optional when used with batteries Thermostat Installer Setup 0170 System Type must be set to 8 2 Heat 2 Cool Multistage Conventional Connection of the C terminal 24...

Page 12: ...umper to YES if humidistat is to be used ID MODELS TWO STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor 24VAC Humidifier Optional External Humi...

Page 13: ...lt Hot Y1 Single Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FURNACE Y Y2 Second or Full Stage Compressor HUM Dehumidification Open on Humidity Rise W Mo...

Page 14: ...YES if humidistat is to be used 24VAC Humidifier Optional External Humidistat Optional Open on Humidity Rise C 24 Volt Common R 24 Volt Hot Y First Stage Compressor Y2 Second Stage Compressor G Fan D...

Page 15: ...optional when used with batteries Thermostat Installer Setup 1 System Type must be set to 6 2 Heat 2 Cool Multistage Conventional COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage H...

Page 16: ...on of the C Terminal 24 Volt Common is optional when used with batteries COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage...

Page 17: ...n Properties 6 Subcooling temperature TC Saturated Temperature ST Liquid Temp T Add charge if the calculated subcooling temperature TC in Step 6 is lower than the recommended level Remove and recover...

Page 18: ...control includes a TEST input connector that can be used for vari ous testing functions during installation and service Table 2 summa rizes the behavior of the control when the two TEST pins are conne...

Page 19: ...ster signals present Control behavior with system master signals present 2 No response No response 2 Display compressor type TS Ultratech or single stage compressor Ignore LPS Bypass ASCD Reduce timer...

Page 20: ...o be reset when the thermostat is satisfied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seconds When the soft lockout c...

Page 21: ...s started following a high pressure switch fault the control will start a six hour timer based on accumulated compressor run time If the control senses another opening of the high pressure switch befo...

Page 22: ...ITCH OFM OUTDOOR FAN MOTOR 562158 UWD B 0313 WIRING DIAGRAM S C R FAN MOTOR GND 6 3 5 PLUG 4 2 1 S C R COMPRESSOR USE COPPER CONDUCTORS ONLY 208 230VAC 60 Hz 1 PHASE SUPPLY GRN BRN RED BLK RED BRN BLK...

Page 23: ...UNICATION CONNECTIONS BLU PNK C M M1 M2 R C Y1 Y2 BLU PNK BRN PNK BRN PNK YEL BLK RED GRY AMB SENS HPS LPS WHT WHT CC RED SEE INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE CONNECTIONS BLK RED GRN YEL 3 BL...

Page 24: ...CATION CONNECTIONS BLU PNK C M M1 M2 R C Y1 Y2 BLU PNK BRN PNK BRN PNK YEL BLU YEL BLK RED GRY AMB SENS HPS LPS WHT WHT CC BLU RED SEE INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE CONNECTIONS 2 STAGE SOL...

Page 25: ...f applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is conn...

Page 26: ...th the owner s manual Explain thermostat use and programming if applicable to owner Cycle Test Operate the unit through several heating cycles if applicable from the thermostat noting and correcting a...

Reviews: