LED DIAGNOSTIC INDICATORS

The control includes two LED’s that display diagnostic information.
LED1 is red and LED2 is green. These LED’s are used to display oper-
ational mode, fault information. A third LED, LED3 is used to display
status information.   LED3 is yellow. These LED’s are used to display
operational mode, status, and fault information.

OPERATIONAL MODE DETECTION

The control can be used in a variety of applications including AC units
with multistage compressors. The control uses various inputs to deter-
mine the proper mode of operation.

The control senses the connections that are made to M, M1, and M2
terminals and determines the correct operational mode for the control.
This is done each time power to the control is cycled. Therefore, it is
important that no loads be attached to the M1 or M2 terminals of the
control for single-stage compressors, and no loads be attached to the
M1 terminal of the control for a scroll two-stage compressor.

OPERATIONAL MODE DISPLAY

The control will display its active operational mode using the onboard
LED’s when the TEST pins are connected while no thermostat signals
are energized. Table 3 "Operational Mode Display" describes the oper-
ational modes. The control will display the operational mode as long as
the TEST pins are shorted and no thermostat signals are energized.
When the TEST pin short is removed, the control will return to normal
LED displays.

STATUS CODE DISPLAY

The control also provides status codes using the LED’s. Status codes
indicate the state of the operation of the unit but do not represent a
fault. Tables 4 & 5 describes the LED displays during status codes. Sta-
tus codes will not be displayed when a fault code is present.

TABLE 2: 

TEST Input Functionality

Duration of 

connection (seconds)

Control Behavior with no system 

master signals present

Control behavior with system 

master signals present

< 2

No response

No response

2 <

Display compressor type TS, Ultratech, or 

single stage compressor, Ignore LPS

Bypass ASCD (Reduce timer to zero immediately).

If Y1 (thermostat or communication) is present and the

 high-pressure switch is closed, contactors will be energized.

Clear soft lockout

Clear soft lockout

Clear hard lockout

Clear hard lockout

Reset TS anticipation mode counter 

to zero for TS systems.

Reset TS anticipation mode counter 

to zero for TS systems.

Reduce TS staging delays for TS 

systems as described below.

Connection removed

Resume normal LED display

Connection not removed

Nothing more than previously explained

Do not connect any loads to the M1 or M2 terminals of the control
for single-stage compressors, and no loads should be attached to
the M1 terminal of the control for scroll two-stage compressor.
Incorrect system behavior could result.

TABLE 3: 

Operational Mode Display

Compressor Type

LED1 (Red)

LED2 (Green)

Single Stage Compressor

1 flash

---

TS Compressor 

2 flashes

---

UltraTech Compressor

3 flashes

---

TABLE 4: 

Status Code Display

Description

Required Condition

LED1 (Red)

LED2 (Green)

No power to control

No power to control

OFF

OFF

First-stage compressor operation – TS or UltraTech

TS – M & M1 energized,
UltraTech – M energized,
Single Stage - NA

OFF

ON

Second-stage compressor operation - TS, UltraTech, or 
Single Stage 

TS and UltraTech – M & M2 energized, 
Single Stage – M energized

ON

ON

Control normal operation – no communication or call for 
compressor present

No faults active, Y1 or Y2 not present

OFF

2s ON / 2s OFF

Control normal operation – in ASCD period

No faults active, Y1 or Y2 present, 
ASCD timer not expired

OFF

0.1 sec ON / 
0.1 sec OFF

TABLE 5: 

Status Code Display

Description

Required Condition

LED3 (Yellow)

Control normal operation – with active communication present

System is active and presently communicating successfully.

0.1 sec ON / 
0.1 sec OFF

Control powered – without active communication present

System has 24 VAC present and the microprocessor is active.

2s ON / 2s OFF

Summary of Contents for CZH

Page 1: ...tage Wiring Diagram 5 Ton 23 Two Stage Wiring Diagram 24 LIST OF TABLES R 410A Saturation Properties 18 TEST Input Functionality 19 Operational Mode Display 19 Status Code Display 19 Status Code Displ...

Page 2: ...taking the accumulated layer of hot air into the outdoor unit Provide adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 22 unit it is requi...

Page 3: ...tightened 4 Position the unit on the base provided LIQUID LINE FILTER DRIER The air conditioning unit s copper spun filter dryer is located on the liq uid line TXV INSTALLATIONS The following are the...

Page 4: ...d dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valves by wrapping a wet rag around it as shown in Figure 4 Heat Protection Also pro...

Page 5: ...liquid and vapor valves 10 Leak test all refrigerant piping connections SECTION IV EVACUATION 1 It will be necessary to evacuate the system to 500 microns or less If a leak is suspected leak test with...

Page 6: ...rol 2 Route low voltage four conductor shielded thermostat communica tions harness into junction box and connect to communications port on control board See Figure 6 Communications Harness Connec tion...

Page 7: ...set properly Refer to the Technical Guide for the outdoor unit for the recommended air flow settings for each size condensing unit and matching indoor unit Set the cooling speed per the instructions f...

Page 8: ...ELEC SINGLE STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor SINGLE STAGE AIR CONDITIONER External Humidistat Optional Open on Humidity Rise Y...

Page 9: ...mpressor Y2 Second Stage Compressor SINGLE STAGE AIR CONDITIONER External Humidistat Optional Open on Humidity Rise Optional 24VAC Electronic Air Cleaner Optional Y1 First Stage Compressor COM 24 Volt...

Page 10: ...must be set to GAS SINGLE STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor SINGLE STAGE AIR CONDITIONER External Humidistat Optional Open on Hu...

Page 11: ...of the C terminal 24 Volt common is optional when used with batteries Thermostat Installer Setup 0170 System Type must be set to 8 2 Heat 2 Cool Multistage Conventional Connection of the C terminal 24...

Page 12: ...umper to YES if humidistat is to be used ID MODELS TWO STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor 24VAC Humidifier Optional External Humi...

Page 13: ...lt Hot Y1 Single Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FURNACE Y Y2 Second or Full Stage Compressor HUM Dehumidification Open on Humidity Rise W Mo...

Page 14: ...YES if humidistat is to be used 24VAC Humidifier Optional External Humidistat Optional Open on Humidity Rise C 24 Volt Common R 24 Volt Hot Y First Stage Compressor Y2 Second Stage Compressor G Fan D...

Page 15: ...optional when used with batteries Thermostat Installer Setup 1 System Type must be set to 6 2 Heat 2 Cool Multistage Conventional COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage H...

Page 16: ...on of the C Terminal 24 Volt Common is optional when used with batteries COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage...

Page 17: ...n Properties 6 Subcooling temperature TC Saturated Temperature ST Liquid Temp T Add charge if the calculated subcooling temperature TC in Step 6 is lower than the recommended level Remove and recover...

Page 18: ...control includes a TEST input connector that can be used for vari ous testing functions during installation and service Table 2 summa rizes the behavior of the control when the two TEST pins are conne...

Page 19: ...ster signals present Control behavior with system master signals present 2 No response No response 2 Display compressor type TS Ultratech or single stage compressor Ignore LPS Bypass ASCD Reduce timer...

Page 20: ...o be reset when the thermostat is satisfied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seconds When the soft lockout c...

Page 21: ...s started following a high pressure switch fault the control will start a six hour timer based on accumulated compressor run time If the control senses another opening of the high pressure switch befo...

Page 22: ...ITCH OFM OUTDOOR FAN MOTOR 562158 UWD B 0313 WIRING DIAGRAM S C R FAN MOTOR GND 6 3 5 PLUG 4 2 1 S C R COMPRESSOR USE COPPER CONDUCTORS ONLY 208 230VAC 60 Hz 1 PHASE SUPPLY GRN BRN RED BLK RED BRN BLK...

Page 23: ...UNICATION CONNECTIONS BLU PNK C M M1 M2 R C Y1 Y2 BLU PNK BRN PNK BRN PNK YEL BLK RED GRY AMB SENS HPS LPS WHT WHT CC RED SEE INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE CONNECTIONS BLK RED GRN YEL 3 BL...

Page 24: ...CATION CONNECTIONS BLU PNK C M M1 M2 R C Y1 Y2 BLU PNK BRN PNK BRN PNK YEL BLU YEL BLK RED GRY AMB SENS HPS LPS WHT WHT CC BLU RED SEE INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE CONNECTIONS 2 STAGE SOL...

Page 25: ...f applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is conn...

Page 26: ...th the owner s manual Explain thermostat use and programming if applicable to owner Cycle Test Operate the unit through several heating cycles if applicable from the thermostat noting and correcting a...

Reviews: