B. Shall have internal isolation and sound muffling to

minimize vibration and noise, and be externally iso-
lated on a dedicated, independent mounting.

2. Coils:

A. Evaporator and condenser coils shall have alumi-

num plate fins mechanically bonded to seamless
internally-enhanced copper tubes with all joints
brazed.

B. Evaporator and Condenser coils shall be of the

direct expansion, draw-thru design.

3. Refrigerant Circuit and Refrigerant Safety Compo-

nents shall include:

A. Independent thermal expansion devices (TXV).

B. Solid-core filter dryer to eliminate any foreign matter.

C. Accessible service gage connections on both suc-

tion and discharge lines to charge, evacuate, and
measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge
and without disrupting condenser or evaporator air
flow.

D. The refrigeration system shall provide at least 10

 F

of liquid sub-cooling at design conditions.

E. Unit shall have a suction line accumulator and auto-

matic reversing valve.

4. Unit Controls:

A. Unit shall contain a large, low voltage Terminal

Board for easy connection of field low voltage wir-
ing.

B. Controls shall be mounted in a large control box with

tilt-out, hinged access door, allowing easy access
for trouble shooting and maintenance without affect-
ing the normal system operation pressures.

C. Unit shall contain a reliable demand defrost control

to provide defrost. The defrost control shall also
have an ìXî terminal to provide a 24 volt signal for

room thermostat ìLEDî indication of unit lockout.
Plus a built in 5 minute anti-short cycle protection.

D. Unit shall have large, easily removable panels, cov-

ering electrical controls and compressor, allowing
easy access for any maintenance or servicing.

ELECTRIC HEATING SECTION

1. An electric heating section, with nickel chromium

elements, shall be provided in a range of 5 thru 25

KW.

2. The heating section shall have an automatic reset

primary limit control to prevent the heating element

system from operating at an excessive tempera-

ture.

3. The heating section assembly shall slide out of the

unit for easy maintenance and service.

4. Units with electric heating sections shall be wired

for a single point power supply, with branch circuit

fusing (where required).

UNIT OPERATING CHARACTERISTICS

1. Unit shall be capable of starting and running at

125

 F outdoor temperature, exceeding maximum

load criteria of ARI Standard 210/240.

2. The compressor, with standard controls, shall be

capable of operation down to 45

 F outdoor tem-

perature. Accessory low ambient kit shall be avail-

able for operation to 0

 F.

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single 

factory provided location and be capable of side or bot-

tom entry. This will minimize roof penetrations and 

avoid unit field modifications. Separate side and bot-

tom openings shall be provided for the control wiring.

Summary of Contents for B1HP024 THRU 048

Page 1: ...aller can fit this unit between the wheel wells of full size pick up truck All models are under 500 pounds All units are completely wired charged with R 22 and tested prior to shipment Unique test sta...

Page 2: ...er water integrity Rounded corners with water drip edges add to the attractive appearance The cabi net panels have a non fibrous insulation that reduces insulation fibers into conditioned area TOP DIS...

Page 3: ...1 leak rate Includes hood and mesh bird screen filter integrated into the hood dry bulb sensor and relief damper Sepa rate field accessories of single enthalpy and dual enthalpy are also available SIN...

Page 4: ...provide single phase models from factory furnished 40 VA trans former capability to 75 VA transformer capability ELECTRIC HEATERS Each heater package provides easy installation of elec tric heat strip...

Page 5: ...RIC HEAT NOMINAL CAPACITY KW 47 F 17 F MBH SEER EER MBH COP MBH COP SINGLE PHASE THREE PHASE 024 24 4 13 0 11 3 7 6 79 21 8 3 40 11 0 2 00 5 0 7 5 10 0 N A 030 30 0 13 0 11 3 7 6 77 28 2 3 40 16 5 2 2...

Page 6: ...R INPUT kW 2 20 2 21 2 17 2 16 2 24 2 24 2 20 2 19 Sensible Capacity MBH 1 Entering Dry Bulb F 86 19 5 21 5 20 5 20 6 20 4 22 3 20 8 20 9 83 17 2 19 2 20 5 20 6 18 5 20 7 20 8 20 9 80 14 9 16 9 19 7 2...

Page 7: ...ER INPUT kW 3 14 3 12 3 04 3 06 3 24 3 22 3 14 3 16 Sensible Capacity MBH 1 Entering Dry Bulb F 86 21 7 26 6 25 0 26 7 23 9 27 9 26 0 27 7 83 18 8 24 1 25 0 26 7 20 6 26 3 26 0 27 7 80 15 9 21 1 25 4...

Page 8: ...PUT kW 3 61 3 52 3 44 3 45 3 70 3 61 3 53 3 54 Sensible Capacity MBH 1 Entering Dry Bulb F 86 23 9 29 4 29 5 30 4 26 2 31 9 30 2 31 1 83 20 9 26 6 29 2 30 0 22 7 28 9 30 2 31 1 80 17 9 23 6 27 8 28 6...

Page 9: ...PUT kW 4 01 3 98 3 89 3 88 4 06 4 03 3 94 3 93 Sensible Capacity MBH 1 Entering Dry Bulb F 86 28 1 34 5 35 2 35 6 29 4 35 8 35 4 35 7 83 24 5 31 6 34 8 35 1 25 6 33 0 35 2 35 5 80 21 0 28 1 33 7 33 8...

Page 10: ...T kW 4 71 4 62 4 52 4 47 4 81 4 71 4 61 4 56 Sensible Capacity MBH 1 Entering Dry Bulb F 86 32 0 40 2 40 1 43 2 33 5 41 8 40 3 43 5 83 28 0 36 5 39 7 41 8 29 2 38 0 40 1 42 7 80 23 9 32 4 39 6 39 3 24...

Page 11: ...e indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 9 HEATING CAPACITIES 2 1 2 TON BHP030 CFM RETURN AIR F CAP1 KW OUTDOOR AIR TEM...

Page 12: ...the indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 11 HEATING CAPACITIES 3 1 2 TON BHP042 CFM RETURN AIR F CAP1 KW OUTDOOR AIR...

Page 13: ...KW 2 408 2 634 2 861 3 088 3 315 3 542 3 769 3 996 70 MBH 13 702 16 887 20 812 25 650 31 612 38 961 48 017 59 179 KW 2 792 3 018 3 245 3 472 3 699 3 926 4 153 4 380 80 MBH 12 114 15 299 19 224 24 062...

Page 14: ...CFM 273 324 392 480 541 B1HP042 Electric Heat 1225 CFM 306 341 412 494 577 B1HP042 Cooling TB2 A 1300 CFM 338 395 470 551 640 B1HP042 Cooling TB2 B 1400 CFM 393 466 544 642 734 B1HP042 Heating TB2 A...

Page 15: ...used for all field installed 24 volt wire Only required on units with supplemental electric heat PROGRAMMABLE THERMOSTAT ONLY 24 VOLT TRANSFORMER Label all wires prior to disconnection when servicing...

Page 16: ...15 0 96 75 036 208 230 1 60 187 253 17 2 94 0 1 1 7 3 29 9 45 45 0 96 40 208 230 3 60 187 253 11 4 78 0 1 1 7 3 22 7 30 30 0 96 75 460 3 60 414 504 5 7 40 0 0 6 7 3 15 4 20 20 0 96 75 042 208 230 1 60...

Page 17: ...06 7 5 10 0 36 1 41 7 83 2 90 1 90 100 90 100 2NP04501506 11 3 15 0 54 2 62 5 105 8 116 2 110 125 110 125 2NP04502006 15 0 20 0 72 2 83 3 128 3 142 2 150 150 150 150 2NP04502506 18 8 25 0 90 3 104 2 1...

Page 18: ...102 89 92 042 440 435 120 115 101 104 048 485 480 132 127 111 115 FIGURE 4 UNIT CLEARANCES CLEARANCES NOTE FOR UNITS APPLIED WITH A ROOF CURB THE MINIMUM CLE ARANCE MAY BE REDUCED FROM 1 INCH TO 1 2...

Page 19: ...036 21528 001 A 0303 Unitary Products Group 19 FIGURE 5 UNIT DIMENSIONS...

Page 20: ...036 21528 001 A 0303 20 Unitary Products Group FIGURE 6 TYPICAL APPLICATIONS...

Page 21: ...036 21528 001 A 0303 Unitary Products Group 21 FIGURE 7 ROOF CURB DIMENSIONS...

Page 22: ...036 21528 001 A 0303 22 Unitary Products Group FIGURE 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Page 23: ...036 21528 001 A 0303 Unitary Products Group 23 FIGURE 9 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY...

Page 24: ...036 21528 001 A 0303 24 Unitary Products Group FIGURE 10 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY...

Page 25: ...l be provided to assure reliable transit of equipment overhead rig ging fork truck access and proper sealing on roof curb applications Base rails shall be removable when required to lower unit height...

Page 26: ...pressures C Unit shall contain a reliable demand defrost control to provide defrost The defrost control shall also have an X terminal to provide a 24 volt signal for room thermostat LED indication of...

Page 27: ...036 21528 001 A 0303 Unitary Products Group 27...

Page 28: ...001 A 0303 Copyright by Unitary Products Group 2003 All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive 73069 This product was manufactured in a plant whose qualit...

Reviews: