NOTE: Above data includes allowances for a dry indoor coil and no filters. For additional pressure drops, refer to the ìAdditional Static Pressure

Resistanceî table.

 

TABLE 13: SIDE & BOTTOM SUPPLY AIR BLOWER PERFORMANCE (208/230/460 VOLT

1

)

MODEL NO.

BHP

MOTOR SPEED

 SETTING

UNIT 

AIRFLOW

EXTERNAL STATIC PRESSURE - IWG

0.15

0.30

0.50

0.70

0.90

WATTS

B1HP024

Cooling TB2-A, Heating TB2-A, Electric Heat

800 CFM

91

125

161

206

240

B1HP024

Cooling TB2-B, Heating TB2-B

900 CFM

118

148

199

243

285

B1HP030

Cooling TB2-A, Heating TB2-A, Electric Heat

1000 CFM

280

321

389

449

500

B1HP030

Cooling TB2-B, Heating TB2-B

1125 CFM

356

413

490

557

620

B1HP036

Cooling TB2-A, Heating TB2-A

1050 CFM

209

261

319

372

438

B1HP036

Cooling TB2-B, Heating TB2-B, Electric Heat

1200 CFM

273

324

392

480

541

B1HP042

Electric Heat

1225 CFM

306

341

412

494

577

B1HP042

Cooling TB2-A

1300 CFM

338

395

470

551

640

B1HP042

Cooling TB2-B

1400 CFM

393

466

544

642

734

B1HP042

Heating TB2-A, TB2-B

1500 CFM

500

554

665

752

835

B1HP048

Heating TB2-A

1400 CFM

377

427

504

597

683

B1HP048

Cooling TB2-A

1500 CFM

455

516

601

703

788

B1HP048

Cooling TB2-B, Heating TB2-B, Electric Heat

1600 CFM

530

608

707

800

873

1.

All units are factory set to TB2-A.

TABLE 14: ADDITIONAL STATIC RESISTANCE

DESCRIPTION

RESISTANCE, IWG

CFM

500

600

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

1,600

1,700

1,800

1,900

2,000

Wet Indoor Coil

0.01

0.01

0.01

0.02

0.01

0.02

0.03

0.04

0.04

0.03

0.04

0.04

0.05

0.05

0.06

0.07

Economizer

0.00

0.00

0.00

0.01

0.01

0.01

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.07

0.08

0.08

Filter/Frame Kit

0.01

0.02

0.02

0.02

0.02

0.02

0.03

0.03

0.03

0.03

0.04

0.05

0.05

0.06

0.06

0.07

Electric Heat

0.02

0.03

0.03

0.03

0.04

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.01

0.11

0.11

0.12

Summary of Contents for B1HP024 THRU 048

Page 1: ...aller can fit this unit between the wheel wells of full size pick up truck All models are under 500 pounds All units are completely wired charged with R 22 and tested prior to shipment Unique test sta...

Page 2: ...er water integrity Rounded corners with water drip edges add to the attractive appearance The cabi net panels have a non fibrous insulation that reduces insulation fibers into conditioned area TOP DIS...

Page 3: ...1 leak rate Includes hood and mesh bird screen filter integrated into the hood dry bulb sensor and relief damper Sepa rate field accessories of single enthalpy and dual enthalpy are also available SIN...

Page 4: ...provide single phase models from factory furnished 40 VA trans former capability to 75 VA transformer capability ELECTRIC HEATERS Each heater package provides easy installation of elec tric heat strip...

Page 5: ...RIC HEAT NOMINAL CAPACITY KW 47 F 17 F MBH SEER EER MBH COP MBH COP SINGLE PHASE THREE PHASE 024 24 4 13 0 11 3 7 6 79 21 8 3 40 11 0 2 00 5 0 7 5 10 0 N A 030 30 0 13 0 11 3 7 6 77 28 2 3 40 16 5 2 2...

Page 6: ...R INPUT kW 2 20 2 21 2 17 2 16 2 24 2 24 2 20 2 19 Sensible Capacity MBH 1 Entering Dry Bulb F 86 19 5 21 5 20 5 20 6 20 4 22 3 20 8 20 9 83 17 2 19 2 20 5 20 6 18 5 20 7 20 8 20 9 80 14 9 16 9 19 7 2...

Page 7: ...ER INPUT kW 3 14 3 12 3 04 3 06 3 24 3 22 3 14 3 16 Sensible Capacity MBH 1 Entering Dry Bulb F 86 21 7 26 6 25 0 26 7 23 9 27 9 26 0 27 7 83 18 8 24 1 25 0 26 7 20 6 26 3 26 0 27 7 80 15 9 21 1 25 4...

Page 8: ...PUT kW 3 61 3 52 3 44 3 45 3 70 3 61 3 53 3 54 Sensible Capacity MBH 1 Entering Dry Bulb F 86 23 9 29 4 29 5 30 4 26 2 31 9 30 2 31 1 83 20 9 26 6 29 2 30 0 22 7 28 9 30 2 31 1 80 17 9 23 6 27 8 28 6...

Page 9: ...PUT kW 4 01 3 98 3 89 3 88 4 06 4 03 3 94 3 93 Sensible Capacity MBH 1 Entering Dry Bulb F 86 28 1 34 5 35 2 35 6 29 4 35 8 35 4 35 7 83 24 5 31 6 34 8 35 1 25 6 33 0 35 2 35 5 80 21 0 28 1 33 7 33 8...

Page 10: ...T kW 4 71 4 62 4 52 4 47 4 81 4 71 4 61 4 56 Sensible Capacity MBH 1 Entering Dry Bulb F 86 32 0 40 2 40 1 43 2 33 5 41 8 40 3 43 5 83 28 0 36 5 39 7 41 8 29 2 38 0 40 1 42 7 80 23 9 32 4 39 6 39 3 24...

Page 11: ...e indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 9 HEATING CAPACITIES 2 1 2 TON BHP030 CFM RETURN AIR F CAP1 KW OUTDOOR AIR TEM...

Page 12: ...the indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 11 HEATING CAPACITIES 3 1 2 TON BHP042 CFM RETURN AIR F CAP1 KW OUTDOOR AIR...

Page 13: ...KW 2 408 2 634 2 861 3 088 3 315 3 542 3 769 3 996 70 MBH 13 702 16 887 20 812 25 650 31 612 38 961 48 017 59 179 KW 2 792 3 018 3 245 3 472 3 699 3 926 4 153 4 380 80 MBH 12 114 15 299 19 224 24 062...

Page 14: ...CFM 273 324 392 480 541 B1HP042 Electric Heat 1225 CFM 306 341 412 494 577 B1HP042 Cooling TB2 A 1300 CFM 338 395 470 551 640 B1HP042 Cooling TB2 B 1400 CFM 393 466 544 642 734 B1HP042 Heating TB2 A...

Page 15: ...used for all field installed 24 volt wire Only required on units with supplemental electric heat PROGRAMMABLE THERMOSTAT ONLY 24 VOLT TRANSFORMER Label all wires prior to disconnection when servicing...

Page 16: ...15 0 96 75 036 208 230 1 60 187 253 17 2 94 0 1 1 7 3 29 9 45 45 0 96 40 208 230 3 60 187 253 11 4 78 0 1 1 7 3 22 7 30 30 0 96 75 460 3 60 414 504 5 7 40 0 0 6 7 3 15 4 20 20 0 96 75 042 208 230 1 60...

Page 17: ...06 7 5 10 0 36 1 41 7 83 2 90 1 90 100 90 100 2NP04501506 11 3 15 0 54 2 62 5 105 8 116 2 110 125 110 125 2NP04502006 15 0 20 0 72 2 83 3 128 3 142 2 150 150 150 150 2NP04502506 18 8 25 0 90 3 104 2 1...

Page 18: ...102 89 92 042 440 435 120 115 101 104 048 485 480 132 127 111 115 FIGURE 4 UNIT CLEARANCES CLEARANCES NOTE FOR UNITS APPLIED WITH A ROOF CURB THE MINIMUM CLE ARANCE MAY BE REDUCED FROM 1 INCH TO 1 2...

Page 19: ...036 21528 001 A 0303 Unitary Products Group 19 FIGURE 5 UNIT DIMENSIONS...

Page 20: ...036 21528 001 A 0303 20 Unitary Products Group FIGURE 6 TYPICAL APPLICATIONS...

Page 21: ...036 21528 001 A 0303 Unitary Products Group 21 FIGURE 7 ROOF CURB DIMENSIONS...

Page 22: ...036 21528 001 A 0303 22 Unitary Products Group FIGURE 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Page 23: ...036 21528 001 A 0303 Unitary Products Group 23 FIGURE 9 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY...

Page 24: ...036 21528 001 A 0303 24 Unitary Products Group FIGURE 10 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY...

Page 25: ...l be provided to assure reliable transit of equipment overhead rig ging fork truck access and proper sealing on roof curb applications Base rails shall be removable when required to lower unit height...

Page 26: ...pressures C Unit shall contain a reliable demand defrost control to provide defrost The defrost control shall also have an X terminal to provide a 24 volt signal for room thermostat LED indication of...

Page 27: ...036 21528 001 A 0303 Unitary Products Group 27...

Page 28: ...001 A 0303 Copyright by Unitary Products Group 2003 All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive 73069 This product was manufactured in a plant whose qualit...

Reviews: